| 1 | Supply, installation, commissioning & testing of highly energy efficient, outdoor type oil immersed naturally cooled (ONAM) transformer copper wound type of capacity 400 KVA as per latest IS code, conforming to IS-1180, Level-II with off load tap changer on primary side to vary secondary voltage within limit (+) 5% to (-) 7.5% in step to 2.5% including standard fittings and first filling to transformer oil as per IS-335 of 1980 with cooling system. The transformer shall be provided with cable termination box to terminate outdoor type termination of suitable size on HT side 11 KV & LT side 1100 Volts.Transformer step down ratio 11000 Volts/ 433 Volts, 3 phase 4 wire, impedance as per oil type, ONAM cooled, suitable for outdoor installations and double wound core type with cold rolled grain oriented silicon shell insulated laminations and clamped to minimize vibration and noise. The winding shall be copper and shall be designed for full load current and with stand the thermal and electro magnetic stresses arising due to the through fault current vector group shall be DYN 11 including supply of all standard fittings & fixtures and comprising of the followings :-(a) HT cable termination box.(b) LT cable termination box.(c) Rating and diagram plate.(d) Earthing terminals. (e) Lifting lugs.(f) Oil level indicator with minimum level marking.(g) Thermometer pocket.(h) Conventional conservator with oil filling hole with cap and drain cum sampling valve.(j) Air release plug.(k) Silica gel breather. (l) Off circuit tap changer with locking provision. (m) Bi-directional rollers. (n) Jacking Pads. (o) Radiators/ Fins and all (Epoxy painted). (p) Danger Notice Board. |
| 2 | Supply, Installation & Testing of outdoor type LT Control Panel, CPRI type tested certified, suitable for 440 Volts (Three phase 4 wire system), made out of 3.15mm thick powder coated CRCA sheet, front & back side openable type and front side with double door, fixed with hinges and knob including locking arrangement, dust, weather & vermin proof, cubicle type of size not less than 0.80 x 0.60 x 0.40 mtr and fixed with angle iron leg of size 32mmx32mm and 6mm thick and 0.40 mtr long/ high - 04 Nos and welded the same and fixed in the trolly including high tensile nut, bolts and washers or welding etc, dully painted with two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete with and including copper bus bar of four pole in colour code of capacity 1000 Amps, fixed over epoxy insulator with and including one No 800 Amps ACB 4 Pole 65KA of microprocessor based thermal / magnetic controller including necessary copper spreader for main controlling switchgear with incoming and outgoing connection, Voltmeter 0-500 V - 01 No, Ammeter 0 to 650 Amps - 01 No, indicating lamp RYB - 01 Set, complete all as specified and directed by Engineer-in-Charge. |
| 3 | M&L for fabrication of towing type transformer trolley suitable for 400 KVA transformer step down, outdoor type 11 KV/433 V of capacity complete made out of MS \"I\" beam of size 250mm x 125mm x 6.9mm (37.3 Kg/mtr) and MS sheet for platform 6mm thick, mounted on 4 wheels (7.50x16 size) with rims mounted on 02 Nos front and rear axle wheel with leaf spring clamps cushioning arrangement, between platform and 02 Nos front and rear axles, complete with towing arrangement with tow hook to take full load of trolley and transformer, Jalli (XPM) around platform on angle iron frame of size 40mmx40mm and 5mm opening arrangement from both side with locking arrangement for loading and unloading of transformer including welding, bending and drilling holes, spray painting with two coats of synthetic enamel paint over a coat of red oxide primer over all surface, complete all as specified and directed by Engineer-in-Charge.(a) Size of the transformer trolley platform shall be 4 Mtr x 2.5 Mtr and sufficient space all around after transformer installation for ventilattion/ maint purpose as recommended by OEM and accomodate HT/ LT connecting cables loops on the platform.(b) The trolley shall be provided with steel square net of suitable guage fixed on angle iron in all around the trolley body with opening arrangement as protection.(c) Necessary provision for PVC insulated heavy duty copper cable multistranded single one core 95 sqmm with cable lugs to connect the earting as cut to required length - 50 mtrs.Notes :-(i)Any other works not mentioned in item above but required for smooth functioning of trolley shall be deemed to be included in the rates quoted by the contractor.(ii) Drawing of trolley shall be approved by GE before fabrication in factory/ workshop. |
| 4 | Supply, laying, commissioning & testing XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 Volts grade (Earthed) with aluminium conductor of size 120 Sqmm 3 Core rolled and kept in rotable (for opening and closing the cable) steel cable drum of suitable size on trolly, fixed to walls etc, complete all as specified and directed. |
| 5 | S&F for cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories, suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm 3 Core, complete all as specified and directed. |
| 6 | Supply, laying and testing of XLPELT cable, 1100 Volts grade,PVCinsulated, heavy duty, armoured, multistranded aluminium conductor cable of size 240 Sqmm 3.5 core, including glands and aluminium lugs and jointed in any description, complete all as specified and directed. |
| 7 | S&F manual operated cable reeling drum made out of MS sheet, fixed on trolly, suitable for reeling minimum 50 Mtr LT side 240 Sqmm 3.5 Core cable, HT Cable 120 Sqmm 3 core complete all as specified and directed. |
| 8 | Supply, fixing, testing and commissioning of 33 KV outdoor pole mounted copper three phase 33 KV CT&PT Combined Metering Unit Comprising with the following details :-(a)Insulation Level- 36 KW(b) Current type 33 KV outdoor CT & PT unit(c) Voltage 33 KV(d) Frequency 50 Hz(e)Cooling type outdoor oil colled(f) Coil type 3 Nos CT &PT(g) Current upto 300 Amps(h) Ratio of PT 33000V/√3/110/√3, burden 50 VA, V.F, 1.2 Cont 1.5 for 30 Sec, I.L 36/70/170KVPa, Freq 50HZ h) ratio of CT 15/5 A, Burden 7.5 VA, 0.5.Note : (i) Quoated rate of CT & PT combined unit Shall be deemed to included cost of any variation of ration of CT at the time of execution.(ii)Spare Parts required for fixing of CT & PT unit such as angle, nut bolt, washers bracing support etc., shall be measured and paid separetely.(iii) Test results will be submitted by the contractor after fixing. |
| 9 | Industrial model ER 300 3 Phase accuracy Class 0.2s Meter |
| 10 | MS Enclosere Surface mounted for HT CT Meter Box. |
| 11 | 33 KV 3 Core 95 Sqmm HT Cable XLPE armoured |
| 12 | End Termination Heat Kit 95 x 3 Core HT cable |
| 13 | Earthing Maintinance free with chemical back fill |
| 14 | Cross Arm for mounting CT PT |