Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 18-12-2025 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 25-12-2025 |
| 2 | 05-12-2025 | BOQ REPLACE | BOQ | 18-12-2025 |
| Sl. No. | Item Description |
| 1 | Supply and erecting LT Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9.0) metres long withrelevent IS and paintingthe pole upto 5 feet fromground level with black and yellow alternate strip of30 CM each with synthetic enamel paintone coat of red oxide and two coat of alumunium paint over complete outer surface of the pole. Complete all as specified and directed. Note:- (i) Excavation ,PCC shall be measured and paid separately. |
| 2 | Supply and fixing LED street light fitting 70 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete.Complete all as specified and directed. |
| 3 | S & F brackets 1.2 m long made to shape fabricated out of GI pipe Light grade ISI marked 40 mm dia incl provn of socket nipple welded at once end to suit the light fitting and fix to pole including clamps with nuts and bolts of suitable size cutting, drilling and welding its fix to pole and applying two coat of synthetic enamel paint over a coats of red oxide primer Complete all as specified and directed. |
| 4 | Supply and fixing street light sintex box of size 300 mm x 200 mm x 105 mm, made out of FRP sheet with weather proof hinged door including self locking arrangement, out door type weather and vermin proof complete comprising of insulated / high quality PVC sleeves aluminium bus bar of capacity 63 Amps 04 Nos (three phase RBY and black for neutral) with and including 6 Apms MCB single pole, single phase 230 volts, including 25 x 3 mm flat iron mounted on insulators, having arrangement of connecting incoming and outgoing cables complete and all as specified and directed. NOTE:- 40mm dia elbow from coping to GI pipe shall be deemed inclusive in this quoted rate. |
| 5 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5m in depth for laying of pipe, cable, foundation of electric pole etc and getting out in soft/loose soil, Complete all as specified and directed. |
| 6 | .-ditto as above but exceeding more than 1.5 m in depth |
| 7 | Returning, filling in including spreading leveling watering and well ramming in layers not exc. 25 cm thick complete all as specified and directed. |
| 8 | Removing surplus soil to a distance not exc. 50 M and depositing where directed at a level not exceeding 1.5 Mtr above the starting point complete all as specified and directed. |
| 9 | Supply and laying river bed fine sand in trenches/ ducts 15 cm under cable and 8 cm above the cable for cushioning / protection to cable including spreading, levelling and get thick 18cm after hand punning complete all as specified and directed. |
| 10 | Supply and laying for brick of common burnt clay, sub class \"B\" old size laid flat and dry on cables as in cable protection in trenches over cables perpendicular to direction of cables abutting each other complete all as specified and directed. Brick size-0.23x0.15x0.7 |
| 11 | Supply,laying,galvanised steel tubing light grade complete with all fitting & clamps of size 40 mm dia for cable protection along with pole across road etc. Complete with clamp and bolting Complete all as specified and directed. |
| 12 | Supply,laying, commissioning and testing or passing through pipe, XLPE insulated, armoured, electric power UG cable (Heavy duty) with aluminium conductor, 1100 volts grade in duct / trenches for small length for extension/replacement of the defective cable of nominal cross sectional area 16 sqmm 4.0 core including brass compression cable gland, terminal aluminium lugs etc making connection and testing complete all as specified and directed.Note :-(i) Pipes and bricks for protection, mild steel clamp nut and bolts sand cushioning shall be measured and paid separately. |
| 13 | M &lfor PCC (1:4:8) Type D-2 using 40 mm graded broken stone aggregate as in mass concrete in foundations etc . complete all as specified and directed. |
| 14 | M&L for PCC (1:2:4) type B-2 using 20 mm graded broken stone aggregate as in mass concrete in foundations of stay and grouting of Lt panel, filling of road cutting etc complete all as specified and directed . |
| 15 | Material and labour for PCC (1:3:6) type C-1 using 20 mm graded stone aggregate for coping around the pole strut above ground level and filling in depth of poles. including neccassory form work and finishing the surface fair and even without using extra cement all as directed and specified.Note- All installation final layout drawing should be provided by contractor. |
| 16 | Taking down copper /aluminium point wiring (light, fan, bell,socketor power) complete including fixture and fittings such as switches, ceiling roses, pendent, regulators, sockets, light fitting etc. Removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per condition seperately) and making good disturbed surfaces of walls, floors etc complete all as specified and directed. |
| 17 | Taking down old/unserviceable distribution board by disconnection of electric connection carefully SPN DBs/TPN DBs/ Main Switch including old unserviceable MCCBs/ MCBs, Isolators, etc and making good to disturbed surface complete all as specified and directed. |
| 18 | Taking down carefully copper/aluminium sub main wiring of any size fromsurface/ concealed/ existing conduit of any height and removing materials at site and making good disturbed surfaces of walls, floors roofs etc complete all as specified and directed. |
| 19 | M & L for point wiring using approved colour coding as per IS with multistranded copper conductor 1.5 Sqmm (nominal area), two single core, PVC insulated and unsheathed FRLS cable 1100 volts grade ISI-694 marked drawn through in and including heavy duty, PVC concealed conduit of white/ ivory colour including all accessories after chasing in wall/ ceiling etc, heavy duty ISI marked, with GI sunken boxes 1.2 mm thick, 60 mm deep with earth dolly duly, covered with modular white cover plate with inner frame suitable for modular switches, including PVC insulated multistranded copper conductor 1.5 Sqmm (nominal area) single core FRLSH cable as earth continuity conductor to common earth and connecting to earth dolly including cutting, chasses and making good disturbed surface to match with existing finish with plaster complete all as specified and directed for the following :- |
| 20 | (a) One light point controlled by one way switch 5 Amps |
| 21 | (b) One 3 pin 5 Amps switch socket outlet point controlled by one switch on the same board. |
| 22 | (c) One 3 pin 5 Amps switch socket outlet point controlled by one switch on independent board. |
| 23 | Description all as per item No 20here-in-before but using 2.5 Sqmm single core copper conductor cable of multistranded FRLSH, PVC insulated unsheathed 1100 volts grade for 5/15 amps switch socket combination point including necessary running of2.5 sq mm copper conductor FRLSH, PVC wire as earth continuity conductor along with wiring and connecting to the common earth dolly. |
| 24 | Description all as per item No. 20 here in before butusing 4.0 sq mm single core copper conductor FRLS cable of multistranded PVC insulated unsheathed 1100 volts grade for 5/15 amps switch socket cobmination point including necessary running of4.0 sq mm PVC insulated copper conductor FRLS cable as earth continuity conductor along with wiring and connecting to the common eath dolly. (for AC Point) |
| 25 | S & F switch piano flushtype, single pole, one way and 5/6 Amp single complete. |
| 26 | S & F socket outlet multipurpose with provision of 3 pin, 5/6 Amp and 2 pin, 5/6 Amp, 2 module piano flush type complete. |
| 27 | S &F switch socket combination2 in 1, 3 pin, 6 and 15 amp flush typeuniversal. |
| 28 | S & F ceiling rose, surface bakelite with 3 terminals, ISImarked for batten fitting complete all as specified. |
| 29 | M & L for sub main wiring with approved colour coding as per IS with four single core PVC insulated FRLS cable with stranded copper conductor of size 6 Sq mm nominal area and drawing into suitable size of PVC non metallic rigid heavy duty PVC conduit of white/ ivory colour and its accessaries ISI marked heavy duty of suitable sizeincluding concealed in wall etcone run of PVC insulated with 6.0 Sqmm (nominal area) stranded copper conductor FRLS cable as earth wire complete all as specified and as directed. |
| 30 | S & F for sheet metal enclosure MCB DB TPN 4 way vertical type with 200 Amps rated bus bar 415 volts double door suitable for incomer MCCB 4 pole 100-25 amps with magnitic locking system including necessary provision for inserting the DBs in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified and as directed. |
| 31 | S & F for sheet metal enclosure MCB DB SPN 8 way with 200 Amps rated bus bar 240 volts double door with magnitic locking system including necessary provision for inserting the DBs in wall by cutting the brick/stone masonary etc and making good of distrubed surface to match with existing colour of wall complete all as specified and as directed. |
| 32 | Supply and fix 4 Pole MCCB 100 to 125 Amp, 50 Hz, 415 V with rupturing capacity 35 KA complete all as specified and as directed. |
| 33 | S & F for MCB Single pole and neutral rated capacity 63 Amps, 240 Volts breaking capacity 10 KA, \"C\" curve complete all as specified and as directed. |
| 34 | S & F for MCB Single pole and neutral rated capacity 32 Amps, 240 Volts breaking capacity 10 KA, \"C\" curve complete all as specified and as directed. |
| 35 | S & F for MCB Single pole rated capacity 5 to 32 Amps, 240 Volts breaking capacity 10 KA, \"C\" curve complete all as specified and as directed. |
| 36 | S & F sheet metal enclosure for single pole and neutral with two pin and earth plug top and socket complete with one single pole MCB 20 Amps complete all as specified and directed. |
| 37 | Triple pole and earthencolsure with a three pin and earth plug with socket complete with one triple pole MCB |
| 38 | S & F for wall mounted LED tube light fitting 20 watts batten for surface mounted, anodized extruded aluminium housing, high transmissitivity diffuser, high lumen ouput box type fitting, 230 volts and intregrated electronic driverconnector block etc with warranty option of 5 years from date of installation complete with all accessories internally pre wired and necessary mounting arrangements, provision of new 3 core multistranded copper conductor of size 23/0.193 from ceiling rose to fitting complete all as specified and directed. |
| 39 | S & F for Energy saving new generation environmental friendly long life versatile presure die cast aluminium IP 66 for security light fitting luminaire with high power LEDs as light source and electronic driver of capacity 35 watts with pre wired andnecessary mounting arrangements and provision of 2.5 sq mm three core copper conductor cable multi stranded from ceiling rose to light fitting including necessary dia GI pipe medium grade bracket 1.5 mtr long bend to required shape with clamps, nut, bolts complete all as directed |
| 40 | M & L for earthing complete with copper earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground vertically (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.50 mtr deep below normal ground level, by means of bolts, nuts, check nuts, and washers of 20 x 3 mm copper strip for earth lead complete with charcoal and common salt including watering arrangement with galvanized iron pipe light grade 40 mm dia, PCC Chamber, CI frame and cover, MS funnel with wire mesh all as shown in electrical plate no 3 of SSR part I including excavation and earthwork in any type of soil/strata and testing on completion. |
| 41 | M&L for earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less\"than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron+E40 or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion |
| 42 | Supply, installation, commisioning and testing LT feeder pillar box out door type double door and single shutter front open including locking arrangement system made out of MS sheet of 3.15 mm CRCA sheet of size 0.6x0.6x0.3 mtr and double door, canopy, dust proof, bottom cable entry plate and gland for cable size 150/ 120/95/70/ 50/25/ 16/10 sqmm 3.5 core suitable MS angle iron 40x40x5 mm with aluminium busbar size 600 Amps system mounted on hygroscopic insulators bus bar including suitable nut, Bolt and Washer (16 Nos) & including powder coated paint with and providing necessary foundation/ plateform of the feeder pillar height 1.5 feet from groundwith PCC 1:2:4 type B2 including provision of for incomong and outgoing cable gland, thimbling for old / new cables as per site requirement and proper finshing as per existing surface complete all as specified and directed. |
| 43 | Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 70 Sqmm x 3.5 Core passing through DWC HDPE / in trench including necessary connection with lugs and cable gland etc complete all as specified and directed. |
| 44 | Galvanised iron steel tubes, ISI marked light grade of size 40mm bore for cable protection along the poles under road under drains complete all as specified. |
| 45 | M&L for point wiring for 3 pin 5 amps socket outlet independent controlled by one switch with 1.5 sqmm single core 1100v grade FRLSH PVC insulated unsheathed multistranded copper conductor with andincluding PVC concealed conduit of medium grade (ISI Marked) having dia. not less than 20mm with all fittingsincludingMS galvanised pressed steel terminal sunken boxes of thickness not less than 1.12mm of required module complete with frame plate and cover plate of required module for mounting modular switches, sockets etc. including 1.5 sqmm single core 1100v grade FRLSH PVC insulated unsheathed multistranded copper conductor as earth continuity conductor connected to common earth dollyand including cutting chases in walls / floors for concealed conduiting andmaking good disturbed surface areaand white wash/colour wash to matching with the existing colour and all as specified and directed . |
| 46 | All as per item No. 46 here-in-before but by using 2.5 Sqmm FRLSH copper conductor cable with continuous earth wire of 2.5 Sqmm FRLSH copper conductor for one 3 pin 15 Amp socket outlet point controlled by one switch. |
| 47 | S&F switch modulartype 5/6 Amps, 230 V AC, single pole, one way complete all as specified anddirected. |
| 48 | S&F socket out let multipurpose modularfor 2 pin and 3 pin, 5 Amp flush type with shutter complete all as specified and directed. |
| 49 | S&F socket outlet, multipurpose, modular 6 pin, 6 /15Amp with shutter complete all as specified and directed. |
| 50 | M & L for subamain wiring with spproved colour coding as per is standard two single core PVC insulated FRLS cable with stranded copper conductor of size 10.0 sq. mm x 4, 6.0 sq. mm x 2 earth wire mm nominal area and drawing into suitable size of PVC non metallic rigid heavy duty PVC conduit of white/ivory colour and its accessories ISI marked heavy duty of suitable size including concealed in waltt etc all specified and as directed. |
| 51 | M & L for subamain wiring with spproved colour coding as per is standard two single core PVC insulated FRLS cable with stranded copper conductor of size 6.0 sq. mm x 4 x4.0 sq. mm x 2 earth wire mm nominal area and drawing into suitable size of PVC non metallic rigid heavy duty PVC conduit of white/ivory colour and its accessories ISI marked heavy duty of suitable size including concealed in waltt etc all specified and as directed. |
| 52 | M & L for subamain wiring with spproved colour coding as per is standard two single core PVC insulated FRLS cable with stranded copper conductor of size 4.0 sq. mm x 4 x 2.5 sq. mm x 2 earth wire mm nominal area and drawing into suitable size of PVC non metallic rigid heavy duty PVC conduit of white/ivory colour and its accessories ISI marked heavy duty of suitable size including concealed in waltt etc. All specified and as directed. |
| 53 | Supply and fix sheet TP&N Vertical Loadline MCCB Incomer, 4 WAY, Loadline DBs are fitted with Bus Bars, Neutral Links, Blanking Plates (without MCCB) G-FRAME MCCB INCOMER DB (Busbar Rating - 160 A) and flush to wall including all cutting etc. in wall and making good to the disturbed surfaces to match the existing complete all as specified and directed. |
| 54 | Supply and fix sheet metal enclosure distribution board, TPN, AC, 415V, 4 way, Double door with 200AMP rated copper bus bar and metal door with IP-43 & IK 09 protection and flush to wall including all cutting etc. in wall and making good to the disturbed surfaces to match the existing complete all as specified and directed. |
| 55 | Supply and fixing TPN/FP 32 AMP, 415V 10KA \"B\" curve miniature circuit breaker (MCB) in the DB complete with connection testing and commissioning. including providing thimble for out going cables. Completa all as specifeid and directed. |
| 56 | Supply and fixing TPN/FP 63, 415V 10KA \"B\" curve miniature circuit breaker (MCB) in the DB complete with connection testing and commissioning. including providing thimble for out going cables. Completa all as specifeid and directed. |
| 57 | Supply and fixing MCCB 4 Pole, 415 V, Adjustable type, 125 Amps with breaking capacity 36 KA in the DB complete with connection testing and commissioning. including providing thimble for out going cables. Completa all as specifeid and directed. |
| 58 | Supply and fixing TPN/FP 100 AMP, 415V 10KA \"B\" curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the DB complete with connection testing and commissioning. including providing thimble for out going cables. Completa all as specifeid and directed. |
| 59 | Supply,laying, commissioning and testing or passing through pipe, XLPE insulated, armoured, electric power UG cable (Heavy duty) with aluminium conductor, 1100 volts grade in duct / trenches for small length for extension/replacement of the defective cable of nominal cross sectional area 35 sqmm 3.5 core including brass compression cable gland, terminal aluminium lugs etc making connection and testing complete all as specified and directed.Note :-(i) Pipes and bricks for protection, mild steel clamp nut and bolts sand cushioning shall be measured and paid separately. |
| 60 | Supply,laying, commissioning and testing or passing through pipe, XLPE insulated, armoured, electric power UG cable (Heavy duty) with aluminium conductor, 1100 volts grade in duct / trenches for small length for extension/replacement of the defective cable of nominal cross sectional area 95 sqmm 3.5 core including brass compression cable gland, terminal aluminium lugs etc making connection and testing complete all as specified and directed.Note :-(i) Pipes and bricks for protection, mild steel clamp nut and bolts sand cushioning shall be measured and paid separately. |
| 61 | M & L for Earthingcomplete with galvanized earth plate electrode60 cm x 60cm x 6mm thick buried directly in ground to the depth of not less than 2.25 mtr below ground level with top edge of earth plate or a depth not less than 1.50 m below ground levelconnected to GI strip 32 x 6mm as earth lead by means of galvanized bolts, nuts check nuts and washers and necessary excavation and earth work PCC 1:2:4 type B-1 using 20mm graded brick aggregate for earth pit RCC cover , charcoal & common salt filled in alternate layers funnel with 20mm bore light grade watering pipe, 40mm dia GI pipe light grade for protection of GI strip, wire mesh andconnected to earth point including testing on all as specified and shown in electric plate No 3 of SSR part I. |
| 62 | Supply installation, testing and commissioning LT sub Feeder panelboard , outdoor type cubicle panel board suitable for 3 phase,4 wire 415 volt 50 hz factory febricated approved CPRI powder coated made out of 3.00 mm thick CRCA sheet and MS angle iron sectiom 40X40X6mm frame with front and back openable double door system with locking arragement louver and air vent gaket for netural flow of air with conopy, with 400 Amps on -load changeover switch,inner compartment made out of 2 mm the CRCA sheet duly compartmentalized for each MCCB\"s as incoming and outgoing with MCCB\"s,lockable arrangement with aluminium bus bar three phase and neutral of capacity of 600 amp marked red, yelllow, black and blue inslulators, made of high strength insulated material suitable 1100 voltage all controll PVC wires shall be with 2.5 sq mmmultistrand copper conductor and shall be properly bunched, tied, frerruled for proper indication , fixed on PCC foundation complete. Note:-PCC shall be measured and paid separately.INCOMING:- (a) MCCB 250 A,415V 4Pole, thermal and magnetic type 35 KA---- 1 Nos (Ics-100%Icu)(b) CT of suitable size(c) Digital type Ammeter 0-400 Amps square typewith selector switch- 01 No.(d) Indicator lamp LED type, set of three marked red, yellow & blue - 01 Set.(e) Digital type Volt meter 0-500 Volts square typewith selector switch- 01 No.OUT GOING:- (a) MCCB 100A,thermal and magnetic type 415V 4Pole, 25 KA---- 1 Nos ( Ics-50%Icu)(b)MCCB 160A, thermal and magnetic type 415V 4Pole, 25 KA---- 1 Nos ( Ics-50%Icu)(c) MCCB 63A,thermal and magnetic type 415V 4Pole, 25 KA---- 2 Nos (Ics-50%Icu)(d) Wiring complete with copper wire of suitable size (e) Cable glands brass of suitable size for cable. |
| 63 | Cutting of walls/hardstanding for laying cable including match with surface through cement mortar complete all as specified and directed |
| 64 | Taking down old/unserviceable distribution board by disconnection of electric connection carefully SPN DBs/TPN DBs/ Main Switch including old unserviceable MCCBs/ MCBs, Isolators, etc and making good to disturbed surface complete all as specified and directed. |
| 65 | Taking down carefully copper/aluminium sub main wiring of any size fromsurface/ concealed/ existing conduit of any height and removing materials at site and making good disturbed surfaces of walls, floors roofs etc complete all as specified and directed. |
| 66 | One ceiling fand point controlled by one way switch 5 Amps |
| 67 | S&F Modular socket outlet multipurpose with provision of 3 pin, 5/6 Amp and 2 pin, 5/6 Amp, 2 modled piano flush type complete |
| 68 | S&F Lamp holder, PVC/Polycarbonatetype with back plate suitable forbatten fittings |
| 69 | S & Fmodular white cover plate with frame 3 module |
| 70 | S & Fmodular white cover plate with frame 6/8 module |
| 71 | S & Fmodular metal flush box for 3 module |
| 72 | S & Fmodular metal flush box for 6/8 module |
| 73 | M & L for sub main wiring with approved colour coding as per IS with two single core PVC insulated FRLS cable with stranded copper conductor of size 6 Sq mm nominal area and drawing into suitable size of PVC non metallic rigid heavy duty PVC conduit of white/ ivory colour and its accessaries ISI marked heavy duty of suitable sizeincluding concealed in wall etcone run of PVC insulated with 6.0 Sqmm (nominal area) stranded copper conductor FRLS cable as earth wire complete all as specified and as directed. Note:- Two runs of 6 sqmm cable, one run of 6 sqmm cable and one run of PVC conduit will be measured as one unit |
| 74 | Supply and fixMCCBDistribution boarddouble door made out of CRCA mild steel sheet surfce with insulated material like polyester or with epoxy powder coating and IP 43& IK 09protection surface/concealed mounting vertical TPN 4 way, 440 volts with bus bar rating 200 Amps (vertical operation) and suitble size of cable gland -02 Nos, dust and vermin proofsuitable for incorporation of MCCB 4 pole 125 amps 16 kA and MCB\"s and making all necessary connections complete all as specified and directed. |
| 75 | Supply and fix 4 Pole MCCB 100 to 125 Amp, 50 Hz, 415 V with rupturing capacity 35 KA complete all as specified and as directed. |
| 76 | Re-fixing of ceiling fans complete with blades, down rods, electronic regulator and accessories complete all as specified and as directed. |
| 77 | S & F LED bulb10 Watt 230 V AC. |
| 78 | S & F in replacement LED lights fitting 1x 20W 220V, polycarbonate LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete with warranty option of 5 years from date of installation complete with all accessories internally pre wired and necessary mounting arrangements,complete all as specified and as directed. |
| 79 | S&F in replacement of LED panel light fitting 36 watt LED (2x2 ft), LED panel fitting, including LED in white230 volt energy saving environmental friendly, long life, corrosion resistant, impact proof, surface mounting IP-65 luminaire with PC housing in opal finish suitable for wet location with brighness LEDs with all accessories internally prewired and including connected with twin core twisted flexible wire copper conductor cable with suitable size complete all as specified and directed. |
| 80 | S & F building security lightfitting 1 x 35/36 W LED new generation energy saving & environmental friendly long life LED street/bldg security light made up of pressure die cast aluminium housing with mid power LED as lighting source and PC cover having top opening including driver compartment driver with IP66 protection and impact resistance of IK07 including with suitable for 32mm dia medium grade G I bracket not exc 1.5 mtr length made to shape & fixing on pole/wall with 2 nos of MS clamp including necessary connection from LT OH line/buildings |
| 81 | Dismantling of asbestos cement (corrugated, semicorrugated etc,) sheets in roof coverings. |
| 82 | Dismantling wrought iron or mild steel work of any description not otherwise provided for all as spcfd and directed. |
| 83 | S&F of Roof trusses (framed), trussed, purlins, crane gantries, rails and fastenings and heavy bracket framing including distance pieces, cleats etcFe 410 W (Gde E - 250 quality). |
| 84 | S & F of Pre-painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws as Completa all as specifeid and directed. |
| 85 | S & F pre-painted galvalume aluminum zinc coating (AZ 150)GI based plain steelsheet 0.5mm thick of any coloure in ridge having tensile strength of 550 Mpafixed with self tapping screws as spd and directed. |
| 86 | Demolition of brick work or stone/boulder masonry built in cement mortar including all quoins, arches, pillars etc complete all as specified and directed. |
| 87 | Demolition of cement concrete not exc. 15 cm thicknes above or below ground level. |
| 88 | M&L Brick work using old size bricks with sub class \"B\" bricks straightor curved on plan exc 6m mean radius built in cement mortar 1:6 complete all as spd and directed. |
| 89 | Taking down cement plaster on brick or stone wall etc including raking out joints, hacking for key, scrubbing down with water etc. |
| 90 | M&L for rendering 10mm thick internal surfaces on other than fair faces of brick work in CM (1:6) Completa all as specifeid and directed. |
| 91 | M & L rendering 15mm thick on brick wall or concrete s.urface in cement mortar 1:4 finished even and smooth without using extra cement including WPC as per manufacturer instruction complete all as specified and directed. (WPC will be measured seperately) |
| 92 | Supply only liquid water proofing compound ISI marked. |
| 93 | S & F of Framed work such as grills, gratings, etc.. with ends of bars shouldered and/or riveted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework of water tanks and similar work conforming to Fe.290.Gde-E-165 |
| 94 | M&L two coats of syntetic enamel paint overnewsteel surface of any description over 10cm in width or grithnot otherwise describedover one coat red oxide primerincluding preparation of surfaces complete all specified and directed. |
| 95 | M&L for 1 mmthick Birlawhite putty/JK white wall care putty on walls surfaces. |
| 96 | M&L for applying two coats of plastic emulsion paint over a coat of primer incl preparation of new plastered wall surfaces. Completa all as specifeid and directed. |
| 97 | M & L preparation of new plastered and applying two coat weather coat paint on walls complete all as specified and directed. |
| 98 | Taking down chowkhats or frames not exc 1.5 Sqm ( without taking shutters from the frame). |
| 99 | Taking down chowket or frame with shutter (without taking off shutters from the frames) areaexceeding 1.5 Sq mtr but not exceeding 4 Sq mtr each |
| 100 | S & F Powder coated aluminium frame/shutters for windows, ventilators sliding/openable etc icluding joining cleat for fixing, locking arrangement, rubber beading, screws,etc complete all as specified.Note : (i) Glazing and wire mesh shall be measured and paid separetely only as the labour element included in the relavent item.(ii) Item shall be paid as per weight of aluminium section (iii)The rate quoted shall be inclusive of the cost of neoprene beading, glazing pin, screws and powder coated fittings such as locking arraangement etc as required, which shall not be measured for arriving the weight (iv) The rate shall also be inclusive of complete packing with silicon gel around contacting surfaces of aluminium work, and including matching the existing. |
| 101 | M & L for 75mm thick PCC 1:3:6 type C2 (using 40mm graded aggregate as in plinth protection and similar work finishing surfaces even and smooth without using extra cement. |
| 102 | Dismantling of wall and ceiling boards (fibre, pulp, insulation, etc.) or insulation boards/slabs/blankets, any thickness, including cover fillets |
| 103 | M & L for anodised aluminium snap grid frame work for false ceiling all as specified and as directed. |
| 104 | S & F of 4 mm thick HPSC (High Pressure steam cured) pre-primed textured designer board, water resistant, be placed in the grid system duly suspended with 2 mm dia GI bar hangers fixed with steel dash through fasteners from purlins of the roof complete all as specified. |
| 105 | Dismantling floor, hearth or wall tiling including cement mortar bedding (but not backing), removing serviceable tiles to store and rubbish off the premises |
| 106 | M&L 40 mm thick cement concrete type B-0 (1:2:4) using 12.5 mm graded stone aggregate as in levelling coarse of floor complete. |
| 107 | M & L for vitrified ceramic tiles double charge light shed of 7.5 mm thick (square/ rectangular) polished, area of each tiles n.exc 0.36 sqm in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match including screed bed or bedding layer of mortar 15mm thick in cement mortar (1:4) complete. |
| 108 | S&F aluminium handles, cast type, anodised of size 150mm. |
| 109 | S& F 100mm butt hinges, extruded aluminium with galvanised MS hinge pin anodised type C - 21 |
| 110 | S&F in repair Aluminium body ISI marked Door closer hydraulically regulated, designation No. 3, universal type, suitable for door shutters of 851 to 1000 mm in width and of weight between 61 to 80 kg and fixed complete all as specifiedand directed. |
| 111 | S&F 4mm thick sheet glass, ordinary quality and glazing with oil putty in a square n exc 0.5 Sq m in each pane(to be fixed upto four storey of bldgs) Completa all as specifeid and directed. |
| 112 | S&F 4mm thick figured glass, pin head type and glazing with oil putty in a square n exc 0.5 Sq m in each pane(to be fixed upto four storey of bldgs) Completa all as specifeid and directed. |
| 113 | S & F galvanised mild steel wire cloth 0.56 mm nominal dia of wire and average width of aperture 1.18mm fixed with tinned tacks or galvanised wire staples (to be fixed upto four storey of bldgs) complete. Completa all as specifeid and directed. |
| 114 | S&F in repair Mortice lock, vertical type, size 100 mm 2 levers aluminium type Completa all as specifeid and directed. |
| 115 | S&F in repair 24-25mm bore cut to length as required stainless steel draphery rods as required of colour as selected & directed |
| 116 | S&F in repair 24-25mm bore stainless steel decorative brackets as required of colour as selected & directed |
| 117 | S&F as in repair 150mm long aluminium anodised barrel tower bolt Completa all as specifeid and directed. |
| 118 | S & F in replacement LED lights fitting 1x 20W 220V, LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete with warranty option of 5 years from date of installation complete with all accessories internally pre wired and necessary mounting arrangements,complete all as specified and as directed. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy