| 1 | M & L for repair/routine maintenance including daily checking of fire alarm and fire fighting system complete with electronic control panel in the following buildings, attending fire alarm faults, testing, checking and replacement of unserviceable minor components such as nuts, bolts, washers, fuses, loop cards, detector circuits etc. other than those mentioned separately in the schedule, complete all as specified and directed by Engineer-in-Charge.The fire alarm system comprises of:(a) Indicators(b) Electronic fire control panel(c) Manual call points(d) Smoke detectors(e) Heat detectors(f) Electronic fire control panels (Main/Zone type)(g) Batteries of fire panel DC supply(h) All wiring and cable connectionsDetails of buildings covered:(a) R1 to R10, R12 to R21, R23 to R35 ,Mithun Buildings – G+14 floors, (15 storeys)(b) R11, R22, R25, R36 to R39 (G+6/7 storeys)(c) NCS School(d) WNC (O) MessNote:(i) Contractor shall provide adequate skilled manpower for testing of fire alarm/fire fighting system as per schedule issued by user section. The cost of testing shall be deemed to be included in the quoted rate.(ii) Minor consumables such as fuses, loop cards, and detector circuits required to keep the system functional are included in the item rate.(iii) Contractor’s technician and helper shall report daily to JE E/M for routine maintenance work at site. |
| 2 | Supply and replacement, installation, testing & commissioning of micro processor based 2 wire fault tolerant loop, required loop networkable type 2 loop (each loop accessing maximum 99 detectors and 99 modules ) fire alarm/detection control panel. The panel shall be cable to give location of all fire/fault conditions of addressable units via the address. The panel shall have rectifier, Loop cards, LCD unit to indicate Fire/Fault Signal with address. The panel shall have a built in power supply and battery charger along with maintenance free SMF Lead acid batteries as per manufacturers design with battery charger complete as required and as per specifications duly approved by EN 54 complete including making connections all as specified and directed by Engineer-in-charge. Make : Morley-IAS by Honeywell model Name/Number DXc2/714-001-225 or Bosch model NO FPA-1000-V2/Schneider cat No FFSULH1002 Model No ESM, ULTIMA. |
| 3 | S & F in repair rubber hose pipe, 20 mm dia, 30 metres long, high pressure, 2-ply rayon braided, complete with necessary fittings, all as specified and directed.Make: Minimax / Safex / Dunlop or equivalent. |
| 4 | S & F in repair shut-off nozzle, stainless steel, 20 mm dia, conforming to IS 903, complete all as specified and directed.Make: Minimax / Safex / Dunlop or equivalent. |
| 5 | Supply & fix in repair canvas fire hose 63 mm bore 15 m long confirming to IS 636-1988 having male/female SS coupling both end complete all as specified and directed.Make:-Minimax / Safex / DUNLOP |
| 6 | S & F in repair stainless steel nozzle, 63 mm x 15 mm bore, suitable for 63 mm dia canvas hose, conforming to IS:903–1993, complete all as specified and directed.Make: Minimax / Safex / Dunlop or equivalent. |
| 7 | S & F in repair hose reel drum, suitable for 30 metres long, 20 mm dia rubber hose pipe, complete with necessary fittings, all as specified and directed.Make: Minimax / Safex / Dunlop / Jyothi or equivalent. |
| 8 | S & F in repair maintenance-free battery, 12 Volts, 7.2 Ampere-hour (AH), duly charged, complete all as specified and directed.Make: Exide / Tata Green / Amaron or equivalent. |
| 9 | Supply,replacement, installation, testing and commissioning of addressable type manual call point, operating voltage 12/24 VDC, IP-24D protection, complete all as specified and directed.Make: Schneider / Honeywell / Bosch / Siemens or equivalent. |
| 10 | Supply,Installation, testing and commissioning of addressable electronic sounder cum strobe, output 115 dB, three tones, suitable for indoor and limited outdoor applications, with red ABS housing, complete all as specified and directed.Make: Schneider / Honeywell / Bosch / Siemens or equivalent. |
| 11 | S & F in repair addressable type multisensor detector, heat and smoke combination type, with fixed temperature of 59 °C, incorporating dual LEDs for 360° visibility, complete all as specified and directed.Make: Bosch / Honeywell / Schneider / Morley / Siemens or equivalent.Note: Loop cards, circuits, and accessories required to make the system functional shall be deemed to be included in the quoted rate and no extra payment shall be made to the contractor. |
| 12 | M & L for repair of existing unserviceable electronic sounder cum strobe, manual call points, smoke detectors including loop cards, etc., comprising opening, soldering of circuits, cleaning, replacement of glass, testing and painting, complete all as specified and directed by Engineer-in-Charge. |
| 13 | Supply,laying, joining and testing in replacement of PVC insulated and PVC sheathed copper conductor cable, 1100 volts grade, 4 core, 1.5 sqmm, including fixing on wall, making necessary connections with busbar/MCCB/DBs and testing, complete all as specified and directed.Make: Polycab / Havells / HPL / Gloster or equivalent. |
| 14 | Supply, laying, joining and testing in repair PVC insulated PVC sheathed armoured copper conductor cable 1100 Volts of size 2 Core x 1.5 Sqmm including fixing on wall making necessary connection, with busbar/MCCB/DB\"s & testing complete all as specified and directed. Make :- Polycab / Havells / HPL / Gloster |
| 15 | S & F in repair hydrant valve wheel made of cast iron, complete all as specified and directed. |
| 16 | S & F in repair hydrant gunmetal female coupling, 63 mm dia, complete all as specified and directed. |
| 17 | S & F in repair brass ball valve, 15 mm bore, high pressure, with polythene float and fly-nut, complete, screwed for GI pipe or brass ferrule and fixed, including necessary GI fittings such as elbow, reducer, nipple, etc., complete all as specified and directed. |
| 18 | S & F in repair brass ball valve, 20 mm bore, high pressure, with polythene float and fly-nut, complete, screwed for GI pipe or brass ferrule and fixed, including necessary GI fittings such as elbow, reducer, nipple, etc., complete all as specified and directed. |
| 19 | S & F in repair/replacement of gunmetal gate valve, with iron wheel head, Class–I, screwed both ends for GI pipe, ISI marked, including unions and fixing in existing line in position, complete all as specified and directed by Engineer-in-Charge offollowing :- |
| 20 | 25 mm bore |
| 21 | 40 mm bore |
| 22 | 50 mm bore |
| 23 | M & L for factory-fabricated hose box made of 18 gauge MS sheet, size 800 × 600 × 250 mm, with double doors having 4 mm thick glass and door frame made of 16 gauge MS sheet, painted fire-red externally and brilliant white internally, fixed on wall with necessary nuts, bolts or welding to existing MS pipe by supporting angle, complete all as specified and directed by Engineer-in-Charge. |
| 24 | S & F in repair MS ERW pipe 100 mm dia, heavy grade, ISI marked to IS 1239, for suction and delivery of pump and rising main, including all necessary fittings, welding, painting with red-oxide primer and two coats of synthetic enamel paint, and providing necessary PCC supports, complete all as specified and directed.Make : Jindal / Tata / Zenith / BST / Sail |
| 25 | S & F in repair MS ERW pipe 150 mm dia, heavy grade, ISI marked to IS 1239, for suction and delivery of pump and rising main, including all necessary fittings, welding, painting with red-oxide primer and two coats of synthetic enamel paint, and providing necessary PCC supports, complete all as specified and directed.Make : Jindal / Tata / Zenith / BST / Sail |
| 26 | S & F in repair MS ERW pipe 80 mm dia, heavy grade, ISI marked to IS 1239, for suction and delivery of pump and rising main, including all necessary fittings, welding, painting with red-oxide primer and two coats of synthetic enamel paint, and providing necessary PCC supports, complete all as specified and directed.Make : Jindal / Tata / Zenith / BST / Sail |
| 27 | S & F in repair non-return valve for fire brigade inlet, gun-metal, ISI marked, suitable for 63 mm dia fire-hose connection, complete all as specified and directed by Engineer-in-Charge. |
| 28 | S & F in repair gun-metal two-way fire-brigade inlet connection with adaptor of size 80 mm dia × 63 mm dia, complete all as specified and directed.Make: Minimax / Safex / Dunlop or equivalent. |
| 29 | Supply, installation, testing and commissioning of four-way fire-brigade inlet connection conforming to IS 5290:1993, comprising four 63 mm NB in-built gun-metal non-return valves and four 63 mm NB instantaneous couplings arranged on a 100 mm NB pipe manifold, connected to fire-hydrant ring main and fire-hydrant wet-riser pipe, including taking down old and unserviceable unit, complete all as specified and directed by Engineer-in-Charge.Make: Coffco / Newage / AAAG / Minimax / Safeguard or equivalent. |
| 30 | S & F in repair gun-metal twin-outlet hydrant valve 100 mm dia having 63 mm outlets with lock-pin wheel, complete all as specified and directed.Make: Minimax / Safex / Dunlop or equivalent. |
| 31 | S & F in repair gun-metal single-outlet hydrant valve 100 mm dia having 63 mm outlet with lock-pin wheel, complete all as specified and directed.Make: Minimax / Safex / Dunlop or equivalent. |
| 32 | S & F in repair stainless steel hose drum adaptor connection (shank reducer), 63 mm dia, complete all as specified and directed by Engineer-in-Charge. |
| 33 | S & F in repair stainless steel lock pin for 63 mm dia coupling, complete all as specified and directed by Engineer-in-Charge. |
| 34 | S & F in repair PVC female blank cap for hydrant, with chain, complete all as specified and directed by Engineer-in-Charge. |
| 35 | S & F in repair sluice valve 150 mm size, both ends flanged, with high-tensile stainless steel spindle, body conforming to IS:14846, ISI-marked, PN–1.6, including all joints with rubber or fibre board, nuts, bolts, and washers, complete all as specified and directed.Make: Kirloskar / Leader / L&T (Andco) or equivalent. |
| 36 | S & F in repair sluice valve 100 mm size, both ends flanged, with high-tensile stainless steel spindle, body conforming to IS:14846, ISI-marked, PN–1.6, including all joints with rubber or fibre board, nuts, bolts, and washers, complete all as specified and directed.Make: Kirloskar / Leader / L&T (Andco) or equivalent. |
| 37 | S & F in repair sluice valve 80 mm size, both ends flanged, with high-tensile stainless steel spindle, body conforming to IS:14846, ISI-marked, PN–1.6, including all joints with rubber or fibre board, nuts, bolts, and washers, complete all as specified and directed.Make: Kirloskar / Leader / L&T (Andco) or equivalent. |
| 38 | S & F in repair foot valve, ball type, of cast iron, ISI-marked, suitable for 10/15 kg/cm² pressure, including making flanged joints, repairs, and making good to existing PCC surface, complete all as specified and directed of following sizes:Make: Normex or equivalent in Kartar / Kirloskar. |
| 39 | 100 mm dia |
| 40 | 150 mm dia |
| 41 | S& F Compound girders and stanchions, lattice girders, aerial masts, staging for water tanks and the like including caps, bases, splices etc. built up from two or more beam or channel sections or angles with plates, including all lattice bars, stiffeners, gusset plates, of size Fe 410-W(GdeE- 250) quality B or all as specified and directed by Engineer-in-Charge. |
| 42 | M & L for taking down/removing old plaster, broken bricks, PCC, MS channel, MS plate and debris inside existing valve chamber, and repair/maintenance of brick masonry valve chamber of internal size 1.2 m × 1.2 m × 1.2 m (above GL 0.30 m), with 15 cm thick PCC 1:4:8 type D-2 foundation over 15 cm thick hardcore of broken stone, 23 cm thick brick walls in cement mortar 1:4, 15 mm thick internal and external plaster in cement mortar 1:3, finished smooth, and 5 mm thick MS plate cover over complete chamber fixed on 50 × 50 × 6 mm MS angle frame embedded in PCC 1:2:4 type B-1 coping, with hinged opening (150 × 100 mm) and locking arrangement, holdfasts, one coat of red oxide primer and two coats of synthetic enamel paint on steel surfaces, including earthwork and disposal of debris outside MD land, complete all as specified and directed by Engineer-in-Charge.Note: Rates for removal of old plaster, stones/bricks, PCC, earthwork, MS channel, and MS plate are deemed to be included in the quoted rate. |
| 43 | S & F in repair DOL/star-delta starter suitable for 5 HP to 10 HP pump set, current relay range 7.5–16 Amp, 3-phase 430 V, 50 Hz, complete all as specified and directed.Make: L&T / Havells / HPL / Siemens. |
| 44 | M & L for disconnecting motor from pump of capacity 5 HP to 20 HP of any make and model, removing bearings using puller gear, fixing new bearings at DE/NDE, applying necessary greasing, checking shaft alignment to ensure vibration-free operation, complete all as specified and directed by Engineer-in-Charge. |
| 45 | All as per item no 39 but for pump sets of capacity 75 HP to 120 HP |
| 46 | M & L for disconnecting LT cables from electric motor of 5 HP to 10 HP capacity and decoupling from pumping set; removing and transporting the motor carefully to authorised workshop for rewinding; dismantling rotor and stator assembly; cutting and removing old burnt copper winding from stator; cleaning stator slots with carbon-tetrachloride solution; rewinding stator assembly with super-enamelled copper wire of suitable gauge matching existing; applying two coats of insulating varnish and heating in chamber to improve insulation value; reassembling the motor, transporting to site, coupling with pumping set, aligning properly, reconnecting LT cables and commissioning complete, all as specified and directed by Engineer-in-Charge. |
| 47 | All as per item no 41 but for pump sets of capacity 75 HP to 120 HP |
| 48 | S & F in repair air release valve complete with hand-operated ball valve of 25 mm dia, including all related fittings required for proper installation, complete all as specified and directed by Engineer-in-Charge. |
| 49 | S & F in repair butterfly valve (ISI marked), hand-operated type, 150 mm bore, made of ductile iron, suitable for working pressure not less than 15 kg/cm², with complete set, complete all as specified and directed by Engineer-in-Charge. |
| 50 | S & F in repair butterfly valve (ISI marked), hand-operated type, 100 mm bore, made of ductile iron, suitable for working pressure not less than 15 kg/cm², with complete set, complete all as specified and directed by Engineer-in-Charge. |
| 51 | M & L for servicing of diesel engine pump set of 90 HP capacity, including repair and replacement of worn-out or defective spare parts, carrying out preventive maintenance, and servicing of radiator and all connected assemblies, complete all as specified and directed by Engineer-in-Charge.The servicing shall include replacement of the following components:(a) Oil filter(b) Fuel filter(c) Air filter(d) Coolant(e) Engine oil (as per engine capacity) |
| 52 | Supply and fix in repairs 32 Amp,415 Volt, 50 Hz , AC MCBtriple pole and earth encolsure with a three pin and earth plug with socket complete with one triple pole |
| 53 | M & L for cleaning of existing valve chamber and removing unwanted material such as plastic waste, soil, debris, mud, etc., and depositing where directed, complete all as specified and directed by Engineer-in-Charge. |
| 54 | M & L for applying two coats of synthetic enamel paint on hydrant stand post, fire brigade inlet, fire hose box cabinet, and fire main rising line, including preparation of disturbed surfaces such as brickwork and cement work on existing MS plate and MS channel of valve chamber, and carrying out minor repair/maintenance of hinges, openings, and holdfasts, complete all as specified and directed by Engineer-in-Charge. |
| 55 | S & F in repair pressure gauge, 150 mm dia, range 0–10 kg/cm², oil-filled type, as per approved sample, complete all as specified and directed by Engineer-in-Charge.Note: Quoted rate shall include provision of adopter, ferrule, check nut, and other necessary fittings required for fixing the pressure gauge, including minor alterations to MS or CI pipe for tapping, if required. |
| 56 | S & F in repair non-return valve ((ISI marked) made of cast iron, conforming to IS:5312 (Part–1) – 2004, including all necessary nuts, bolts, washers, flanges, gaskets, welding, and jointing works, complete all as specified and directed of following sizes. |
| 57 | 150 mm dia |
| 58 | 100 mm dia |
| 59 | 80 mm dia |
| 60 | Supplying, installing ,testing and commissioning of MS air cushion tank, conforming to IS 4736:1968 on top of each riser fabricated from 6 mm thick MS plate, 200 mm in diameter and 1.2 m in height with dished ends fabricated from 8 mm thick MS plate with Air release valve with stop cock, flanged inlet connection and drain arrangement with 25 mm NB valve, pressure gauge with gun metal stop cock including taking down old and u/s air cushion tank complete all as specified and directed by the engineer-in-charge. |
| 61 | Supply and fixing in repair/ replacement of steel water tubing, galvanised, Medium grade with all fittings such as nipple, union, socket, elbow, bends, fixed to wall including work to be done at any installation or buildings in short piece/length, including breaking the existing brick wall for replacement of corroded GI pipe in/ on wall including concealed pipe and making good the disturbed surfaces to match previous structure with complete all as specified and directed by Engineer-in-charge of following sizes :- |
| 62 | 15 mm bore |
| 63 | 20 mm bore |
| 64 | 25 mm bore |
| 65 | S&F in repair PVC water storage Tank 5000 ltr capacity 3 layers, ISI marked, hosting and fixing in position at any location removing existing tank disconnecting all incoming & out going connection, provision of new tank fittings & connecting it at existing position up to 50 mm GI Pipe connection including replacement of tank nipples and GI fittings as required at site complete all as specified and directed. Note : Rate deemed to be included demolition of existing foundation and reconstruction of same. |
| 66 | Supply and fixing in repair MS fittings bend/ tee/ flange/ elbow/ blind flange/ slip on flange of size 80/100/150/200 mm ISI marked IS 1239 for suction and delivery for pump and for rising main including necessary fitting including welding, painting with red oxide primer & two coat of synthetic enamel paint and providing necessary PCC support, all as specfied and directed by Engineer-in-chargeMake:- Jindal /Tata /Zenith/BST / Sail |
| 67 | Supply and laying in replacement of spigot and socket ductile iron water tubing,class K-9, 150 mm bore cement mortar lining on inner surface and one coat of bituminous paint over exposed surface ISI marked, IS No. 8329: 2000, including rubber joint of suitable size laid on roof/floor/trenches with proper alignment as per site requirement and carrying out testing against leakage before returning and filling in trenches etc complete all as specified and directed by Engr-in-Charge. |
| 68 | Supply and laying in replacement of spigot and socket ductile iron water tubing,class K-9, 100 mm bore cement mortar lining on inner surface and one coat of bituminous paint over exposed surface ISI marked, IS No. 8329: 2000, including rubber joint of suitable size laid on roof/floor/trenches with proper alignment as per site requirement and carrying out testing against leakage before returning and filling in trenches etc complete all as specified and directed by Engr-in-Charge. |
| 69 | Material and labour for Cast Iron/ Ductile Iron specials conforming to IS-1538, spigot /socket or flanged fitting such as bends, tees, collars, flanged/ socket /spigot, Tappers and tail pieces etc suitable for 100/150 mm borepipes including lead joints complete all as specified and directed by Engr-in-Charge. |
| 70 | Excavation in trenches not exceeding 1.5 metre wide not exceeding 1.5 mtr in depth and getting out in soft/loose soil complete all as specified and directed by Engr-in-Charge. |
| 71 | Returning filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cms in soft/loose of soil complete all as specified and directed by Engr-in-Charge. |
| 72 | Removing excavated material exc 250 M but n.exc 500 M and depositing where directed complete all as specified and directed by Engr-in-Charge. |
| 73 | Demolition of Exisiting cement concrete supporting block of pumps and motor exceeding 15 cm thickness above ground level complete all as specified and directed by Engr-in-Charge. |
| 74 | Material and labour for cement concrete 1:2:4, type B-2 (using 40 mm graded stone aggregate) as in foundation, filling and mass concrete for providing support for Base frame with MS bolts placed in concrete finishing even and fair without using extra cement complete all as specified and directed by Engr-in-Charge. Note: Location and size of bolts should match as per the previous concrete supporting blocks. |
| 75 | Supply and fixing in repair rubber vibration pads heavy duty for base frame as per sample suitable for the following capacity of pumpsets complete all as specified and directed by Engr-in-Charge.:- |
| 76 | 50 HP to 75 HP |
| 77 | 05 HP to 15 HP |
| 78 | Supply and fixing in repair soft starter 3 phase,415 volt with comprehensive motor protection, programmable over load protection built in RTD and thermistor input with constant current adoptive acceleration and deceleration for smooth start and stop operation of motor of following capacity :- |
| 79 | 150 HP |
| 80 | 75 HP |
| 81 | 60 HP |
| 82 | Suppy and fix in repair bitumen pachment on damaged road not exceeding 15 cm depth and make well ramming complete all as specified and directed. |
| 83 | Material & Labour for Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, surrounded by alternate layers of charcoal dust and common salt, connected to galvanised iron strip 25 x 4 mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel, all as shown in Electrical Plate No. 3, including GI protection pipe 40 mm dia (light grade) for earth lead, GI watering pipe 40 mm dia (light grade) with funnel and wire mesh, PCC chamber and RCC cover, and testing on completion, complete all as specified and directed. |
| 84 | Supply and laying in replacement of PVC insulated unarmoured copper power cable of sizes given below including HDPE pipe of suitable size fixing on walls with saddles complete all as specified and directed by Engr-in-Charge |
| 85 | Single core 35 Sq mm cable. |
| 86 | Single core 25 Sq mm cable. |
| 87 | Single core 16 Sq mm cable. |
| 88 | Supply and fix in repairs hydrant stainless steel female coupling 63 mm dia all as specified and directed |