| 1 | Taking down carefully copper/aluminium point wiring (light,fan,bell, socket or power)complete,including fixtures and fittings such as switches, ceiling roses, holders,regulators, sockets, tube light fittings i.e removingmaterials to store forkeeping in safe custody or for taking credit (credit for above items should be made for conditions separately )and including making good the disturbed surfaces to match with existing surface and colour shade with puttyfor smooth finishing without andulations complete all as specified and directed. Note:- All old unsv credit materials should be deposited in MES yard day wise after completed of the job, the same material will beissued to contractorthrough gate passas schedule of credit against after completion of the work. |
| 2 | Material and labour for cutting chasing,pinning ofbrick/ stone/concrete wallat any height wall cutting and chases for concealedwiring for 20/25 mm PVC conduit dia pipe,water tubing,etc and making good to facings where required and pointing in cement motor 1:3 to ends or edges of landigs,wall surfaces etc,cutting not exc 10 cm girth and including making good the disturbed surfaces to match with existing surface and colour shade with proper putty for smooth finishing with existing wall complete all as specified and directed |
| 3 | M&L for point wiring using approved colour coding incl providing circuit wiring with 1.5 sqmm PVC insulated, FRLSH type, ISI marked,conf to IS-694/1990 unsheathed,multistranded,single core, coppercable 1100 volts grade cablesdrawn through in PVCConduit 20/25 mm dia medium grade ISI marked (MMS) at any height/places and all accessoriesare concealedinwalls / roofs / floors / ceiling etc. including suitable arrangements for flush mounting modular MS/GI boxes as per site requirement/suitable for modular top cover and framefor fixing of modular switches,sockets,fan regulators, blank plate etc andincluding 1.5 Sqmm PVC insulated multistranded FRLSH type unsheathed(Green colour),single core cable with coppercable as earth continuity conductor andconnecting to common earth dolly and including making good the disturbed surfaces to match with existing surface and colour shade with necessary putty for smooth finishing complete all as specified and directedforOne light point controlled by one 10amps switch. |
| 4 | All as per item no. 3 but for Onefan point controlled by one switch 10 amps, and oneregulator. |
| 5 | All as per item no. 3 but for Oneexhaust fan point controlled by one 10 amps switch . |
| 6 | All as per item no. 3 but for One 5 pin 6 amps socket point controlled by one 10 amps switch on independent board . |
| 7 | All as per item no. 3 but for One 5 pin 6 amps socket point controlled by one 10 amps switch on same board . |
| 8 | All as per item no. 3 but for One bell/buzzer point controlled by onebell push. |
| 9 | All as per item no. 3 but for One light point controlled by two 2 way switches/bed switch point |
| 10 | All as per item no. 3 but for point wiring with 2.5 sqmm and earth conductor of size 2.5 sqmm incl circuit wiring complete all as specified and directed for One 6 pin 16/6 amps socket outlet point controlled by one 16/20 amps switchon independent board. |
| 11 | All as per item no. 4 but for One 6 pin 16/6 amps socket outlet point controlled by one 16/20 amps switch on same board. |
| 12 | All as per item no. 3 but forpoint wiring with 4.0 sqmm and earth conductor of size 4 sqmm incl circuit wiring complete all as specified and directed. |
| 13 | M&L for point wiring using approved colour coding incl providing circuit wiring with 1.5 sqmm PVC insulated, FRLSH type, ISI marked,conf to IS-694/1990 unsheathed,multistranded,single core, coppercable 1100 volts grade cablesdrawn throughPVCcasing and caping 20/25 mm width double locking medium grade ISI marked (MMS) at any height and all accessories such as Tee,bend,short piece & elbow on surface on walls / roofs / floors / ceiling etc. including providing suitable arrangements for flush mounting modular MS boxes as per site requirement/suitable for modular top cover and framefor fixing of modular switches,sockets,fan regulators, blank plate etc andincluding 1.5 Sqmm PVC insulated multistranded FRLSH type unsheathed(Green colour),single core cable with coppercable as earth continuity conductor andconnecting to common earth dolly and including making good the disturbed surfaces to match with existing surface and colour shade with necessary putty for smooth finishing complete all as specified and directedfor One light point controlled by on switch |
| 14 | All as per item no. 13 but for Onefan point controlled by one switch and regulator |
| 15 | All as per item no. 13 but for One exhaust fan point controlled by one switch. |
| 16 | All as per item no. 13 but forOne 5 pin 6 amps socket point controlled by one 6 amps switch on independent board . |
| 17 | All as per item no. 13 but forOne 5 pin 6 amps socket point controlled by one 6 amps switch on same board . |
| 18 | All as per item no. 13 but forOne bell point controlled by one bell push. |
| 19 | All as per item no. 13 but forOne light point controlled by two 2 way switches. |
| 20 | All as per item no. 13 but for point wiring with 2.5 sqmm and earth conductor of size 2.5 sqmm and incl providing circuit wiring complete all as specified and directed for One 6 pin 6/16 amps socket outlet point controlled by one 16 amps switchon independent board. |
| 21 | All as per item no. 20 but forOne 6 pin 6/16 amps socket outlet point controlled by one 16 amps switch on same board. |
| 22 | All as per item no. 13 but for point wiring with 4.0 sqmm and earth conductor of size 4 sqmm incl providing circuit wiring complete all as specified and directed. |
| 23 | Supply & fixing and fixing in repairs modular type switch 10 Amps, single pole,1way,1 module,240V,AC,ISI Markedcomplete all as specified and directed. |
| 24 | Supply & fixing and fixing in repairs modular type switch 10 Amps ,2way,single pole,1 module,240V,AC, ISI Markedcomplete all as specified and directed. |
| 25 | Supply & fixing and fixing in repairs modular type bell push 6 Amps,1 module, single pole, 240 volts,AC,ISI Marked complete all as specified and directed. |
| 26 | Supply & fixing and fixing in repairs modular type switch 16 Amps, single pole,1way,1 module,240V,AC, ISI Marked complete all as specified and directed. |
| 27 | Supply & fixing and fixing in repairs modular type socket shuttered type 6 Amps, 2/3 Pin combined 2 module,240V,ACISI Marked complete all as specified and directed. |
| 28 | Supply & fixing and fixing in repairs modular type socket 6 A/16 Amps, 6 Pin combined shuttered socket 2 module,240V,ACISI Markedcomplete all as specified and directed . |
| 29 | Supply & fixing and fixing in repairs modular type step fan speed regulator 120W, 2 module,230volts,AC, 360 degree rotation 0 to 4/5 steps,ISI Markedcomplete all as specified and directed. |
| 30 | Supply & fixing and fixing in repairs call bell AC, 230 Volts single pole, multi music typeISI marked, complete all as specified and directed. |
| 31 | Supply & fixing and fixing in repairs call bellding dong AC, 230 Volts single pole, multi music typeISI marked, complete all as specified and directed. |
| 32 | Supply & fixing and fixing in repairs angle lamp holder, insulated body with back plate for batten fittingscomplete all asspecified and directed. |
| 33 | Supply & fixing and fixing in repairs ceiling rose, 3 terminal ,PVC/polycarbonate body ISI marked, complete all as specified and directed. |
| 34 | Supply & fixdecorative box type 20 watt light fitting,blue coloured end caps, pre-wired and including providing single/double sideLED tubelight(tube rod) white/warm 20 watt-01 Nomade of aluminium extrusion with high efficientLED driver,IP-20, Tube efficiency of 100lm/w, including PVC/Wooden round/square block -02 Nosand connected with LED fitting to ceiling roseand including removing old unserviceable fitting complete all as specified and directed. |
| 35 | Supply & fixdecorative box type 9 watt light fitting,blue coloured end caps, pre-wiredproviding single side LED tube 9 watt-01 No, and including PVC/Wooden round/square block -02 Nosand connected with LED fitting to ceiling roseand including removing old unserviceable fitting complete all as specified and directed. |
| 36 | Supply and fixing, in repairs 20 watt LED pride plus NXT batten white/warm decorative type,high quality materials,240V,50Hz, and slim integrated body,easy to install,PC diffuser and connected with LED fitting to ceiling rose terminaland incl removing old unserviceable fitting complete all as specified and directed. |
| 37 | Taking down old unsv light fitting from existing location and Supply and fixed aesthetically designed LED flat panel for surface mounting which provides soft-light and glare free symmetrically illumination 2\"x2\" LED 40/42 Watt(600x600x70mm) light fitting and including providing internally prewired,LED driver,connector and also can besuspended with provided kit,nut,bolts and washers as per site requirement and including connecting up with ceiling rose to fittingcomplete all as specified and directed. |
| 38 | Taking down old unsv light fitting from existing location and Supply and fixed in repairs recess mounting 2\"x2\" LED 40/42 Watt light fitting slimmest 9 mm thin in class LED ceiling panel with best in class aesthetick white powder coated frame blended seamlessly with ceiling layout suitable for 600X600mm mudular ceiling grid and also can besuspended with provided kit and including connecting up with ceiling rose to fittingcomplete all as specified and directed complete all as specified and directed. |
| 39 | Supply and fixing, in repairs 40 watt LED pride plus NXT batten, warm light decorative type,high quality materials,240V,50Hz, and slim integrated body,easy to install,PC diffuser and connected with LED fitting to ceiling rose terminaland incl removing old unserviceable fitting complete all as specified and directed. |
| 40 | Supply and fixing, in repairs20 watt LED batten nicolaus glamtubeintegrated design, easy to install,efficency,125 lm/w,PC diffuser and robust housing, high quality materials,pre-wired and connect with LED fitting to ceiling rose terminal and incl removing old unserviceable fitting complete all as specified and directed. |
| 41 | Supply and fixing , in repairs 36 wattsLED supernovalight fitting high wattage complete,energy efficient, integrated design, easy to install,PC diffuser, high quality materials,pre-wired incl connect with LED fitting to ceiling rose terminaland incl removing old unserviceable fitting complete all as specified and directed. |
| 42 | Supply &fixing, in repairs 40 watt LED light fittingwhite lighting, high quality materials and intergrated design, PC diffuser, reliable and robust housing structure, easy to install, efficency 125 lm/wnecessary arrangements for fixing with LED fitting to ceiling rosecomplete all as specified and directed. M |
| 43 | Supply & fixing , in repairs 20 watts LEDAustra mirror light fitting,contemporary designdecorative LED lighting with extruded polycarbonate, environmentalfriendly, energy efficient, easy to install,PC diffuser, high quality materials,pre-wired incl connect with LED fitting to ceiling rose terminal and incl removing old unserviceable fitting complete all as specified and directed. |
| 44 | Supply &fixing , in repairs energy efficient and energy saving new generation 10 watts LED bulk head light fitting IP-65 luminaire with opel diffuser pre-wired ofluminaires including LED light driver and connected with LED fitting to ceiling rose terminaland incl removing old unserviceable fitting complete all as specified and directed. |
| 45 | Supply &fixing , in repairs LEDbldg secruity light fitting of capacity 35 Watt LED street light fitting in aluminium PDC housing, toughened glass cover with IP65/66 protectionand including removing of old unserviceable item complete all as specified and directed. |
| 46 | Supply &fixing , in repairs LEDbldg secruity light fitting of capacity 60 Watt LED street light fitting in aluminium PDC housing, toughened glass cover with IP65/66 protectionand including removing of old unserviceable item complete all as specified and directed. |
| 47 | Supply and fix GI bracket pipe of size 25 to 32 mm diaas suitable medium grade of 1.2 mtr long bent to shape suitable degree of bending as per site requirementwith hot or coldbending method of process for making the one end of GI pipe bracket suitable for fixing of any type street light fitting and shall be fixedonwall surfaces and including providingsuitable fabricate galvanised flat ironclamps of 20X4 mm thick-02 Nossuitable for fixing at any place/height with hole fastners,nuts,bolts & washers including grouting on wall etc and including removing of old unserviceable item complete all as specified and directed. |
| 48 | Supply &fixing , in repairs 70 Watt LED fitting energy saving,environmental friendly,long lifewith SMD LEDs aslight source with driver included, light fitting in aluminium PDC housing, toughened glass cover with IP65 protection with inbuilt surge protector and cable connection from ceiling rose to light fitting and testing and including removing of old unserviceable item complete all as specified and directed. |
| 49 | Supply &fixing , in repairs in sheet metal enclosurewith DD/AD type,415 volts AC,TPNDB, 4 way,8+12 modules, flush mounting with 200amps copper busbar, 2 neutral/earth bars links and MCB incomer,and MCB SPN/SP/TPNas outgoing and complete forIP43&54 DBs protection and includingremoving old unserviceable DBs and incl making good the disturbed surfaces to match with existing surface and colour shade complete all as specified and as directed. |
| 50 | Supply &fixing , in repairs in sheet metal enclosuredouble door ,415 volts AC,VTPNDB, 4 way,8+12 modules, flush mounting with 200amps copper busbar, 2 neutral/earth bars links and MCCB incomer,and MCB SPN/SP/TPNas outgoing and complete forIP43&54 DBs protection and includingremoving old unserviceable DBs and incl making good the disturbed surfaces to match with existing surface and colour shade complete all as specified and as directed. |
| 51 | Supply &fixing , in repairssheet metal enclosure, , double door, 240 volts AC,SPN,DB, 16 way, flush mounting with 200amps copper busbar,neutral bar,earth bar links and MCB incomer MCB SPN/DP and MCB SP as outgoingforIP 43& IP54 DBs protection nd includingremoving old unserviceable DBs and making good the disturbed surfaces to match with existing surface and colour shade acomplete all as specified and as directed. |
| 52 | All as per item No.51 but 12 way SPN DB,DD,240v complete all as specified and directed. |
| 53 | All as per item No.51 but 8 way SPN DB,DD 240v complete all as specified and directed. |
| 54 | All as per item No.51 but 4 way SPN DB,DD 240v complete all as specified and directed. |
| 55 | All as per item No.51 but 2 way SPN DB,SD 240v complete all as specified and directed. |
| 56 | Supply & fix andfixing in repairs mini MCB,32 A,DP \"C and motor starter with socket including with suitable sunken box in concealed/surface and internally connected properly suitable for cooking electrical appliancesincluding protection and includingremoving old unserviceable items and making good the disturbed surfaces to match with existing surface and colour shade complete all as specified and as directed. |
| 57 | Supply & fix andfixing in repairsMCB SP 6 to 32 Amps 10 KA,\"C\" series,AC,240Volts,50Hz , ISI marked and including removing old unsv items complete all as specified and directed. |
| 58 | Supply & fix andfixing in repairsMCB SPN 32 to40 Amps 10 KA,\"C\" series,AC,240Volts,50Hz, ISI marked and including removing old unsv items complete all as specified and directed. |
| 59 | Supply & fix andfixing in repairsMCB SPN 40 to63 Amps 10 KA,\"C\" series,AC,240Volts,50Hz, ISI marked and including removing old unsv items complete all as specified and directed. |
| 60 | Supply & fix andfixing in repairsMCB TPN 32 to40 Amps 10 KA,\"C\" series,AC,440Volts,50Hz, ISI marked and including removing old unsv items complete all as specified and directed. |
| 61 | Supply & fix andfixing in repairsMCB TPN 40 to63/100 Amps 10 KA,\"C\" series,AC,440Volts,50Hz, ISI marked and including removing old unsv items complete all as specified and directed. |
| 62 | M & L for sub main wiring complete in repairs with 2 run of 10 sqmm single core copper conductor (ISI marked)cable1100 volts grade, ISI marked,FRLSH type (conforming to IS-694/1990 as amended) PVC insulated, unsheathed,flexible,multi strandedcolour coded cables drawn drawnthroughand including PVC conduit in concealed ISI marked medium grade(MMS) accessories such as Tee,corner, overlaping connector etcand including one run of 10 sqmm single core copper conductor cable flexible, PVC insulated, unsheathed, multistranded, 1100 volts grade, ISI marked,FRLSH type as earth continuity conductor connected to common earth dolly and including making good the disturbed surfaces to match with existing surface and colour shade and complete all as specified and directed.Note : - Two run of 10 sqmm single core copper conductor cable and one run of 10 sqmm single core copper conductor cable as earth continuity and one run of PVC conduit shall be measured as one unit. |
| 63 | All as per ditto item No .62, but 2 run x 6 sqmm+1 run earth wire complete all as specified and directed. |
| 64 | All as per ditto item No 62, but 2 run x 4 sqmm+1 run earth wire complete all as specified and directed. |
| 65 | All as per ditto item No .62, but 2 run x 2.5 sqmm+1 run earth wire complete all as specified and directed. |
| 66 | All as per ditto item No .62, but 2 run x 1.5 sqmm+1 run earth wire complete all as specified and directed. |
| 67 | Supply & fix andfixing in repairs suitable for flush mounting sheet steel enclosure metal clad plug and socket including MCB SP 20Amps, 10KA \"C \"series, 230 Volts,50Hzsuitable for AC\"s/Geysers complete all as specified and directed. |
| 68 | Supply & fix andfixing in repairsMCCB,125 Amps,4 pole,415 Volts , 16/18KA thermal magnetic type with necessary lugs,thimbles, nuts bolts and washersand including removing old unserviceable itemcomplete all as specified and as directed. |
| 69 | Taking down old unsv ceiling fan from existing location and supply and fix ceiling fan with blades, down rods, and connected accessories, 230 V, 1200 mm sweep, with squirrel cage induction motor, anti dust painted, dust free,high speed. Star ratedcomplete all as specified and directed. |
| 70 | Taking down old unsv ceiling fan from existing location and supply and fix ceiling fan with blades, down rods, and connected accessories, 230 V, 1400 mm sweep, with squirrel cage induction motor, anti dust painted, dust free,high speed. Star ratedcomplete all as specified and directed. |
| 71 | Taking down old unsv exhaust fan from existing location and supply and fix new exhaust fan, steel body AC single phase.230Volts of size 300 mm sweep with blades and frame with louvers complete all as specified and directed. |
| 72 | Taking down old unsv exhaust fan from existing location andsupply and fix new exhaust fan, steel body AC single phase.230Volts of size 150 mm sweep with blades and frame with louvers complete all as specified and directed. |
| 73 | Taking down old unsv exhaust fan from existing location andsupply and fix new exhaust fan, steel body AC single phase.230Volts of size 200 mm sweep with blades and frame with louvers complete all as specified and directed. |
| 74 | Taking down old unsv exhaust fan from existing location andsupply and fix new exhaust fan, steel body AC single phase.230Volts of size 230-250 mm sweep with blades and frame with louvers complete all as specified and directed. |
| 75 | Taking down old unsv exhaust fan from existing location andsupply and fixing newexhaust fan made of sturd engineering plastic complete with louvers shutters, voltage 230v,50hz,rpm 1200 copper winding of sweep 250 mm complete all as specified and directed. |
| 76 | Taking down old unsv exhaust fan from existing location andsupply and fixing newexhaust fan made of sturd engineering plastic complete with louvers shutters, voltage 230v,50hz,rpm 1200 copper winding of sweep 200 mm complete all as specified and directed. |
| 77 | Taking down old unsv wall fan from existing location and supply and fixing wall fan 450 mmHi-sweep, 50 watts with double string, low noise, air delivery 70CMM, RPM-1320, overload thermal protector, 240 volts, 50 Hz complete all as specirfied and directed. |
| 78 | Material and labour for earthing complete with galvanised steel earth plate electrode 600mmX 600mmX 6mm thick buried directely in ground vertically ( earth pit not less than 2.25 metres deep below ground level) with top edge of plate not less than 1.5 metres belowground level, connected to and including galvanised iron strip of size 32 X 6 mm with suitable GI LG pipefrom earth electrodeto test point or up to 7.5mtr whichever is less by means of GIbolts, nuts, check nuts and washersall as per electrical plate no 3 of SSR Pt-I and GI watering pipe of 40 mm dia medium grade,GI funnel with wire mesh,including char coal, salt packed all around the earth electrode plate in layers,PCC earth pit chamber 1:3:6 type C1,RCC cover 1:2:4 type B1, including excavation,earth work in any strata and returning filling, removal of surplus soil and testing for required value completeall as specified and directed. |
| 79 | S&F for PVC non-metalic rigid conduit incl boxes,junctions boxes 1 to 4 way & terminals but incl of all tees,bends,elbows,reducers,bell mouth tube ends and fixing accessories such as couplers lock nuts,saddles,pipes hookes etc ISI marked heavy duty of size 20/25 mm dia for LAN,telephone and TV connections cablesincluding cutting,chasses and making good disturbed surfaces to match with existing surfaces with plaster/putty and including removing of old unserviceable item complete all as specified and directed. |
| 80 | Supply and fixing TVsockets one module with top cover plate and inner frameincluding all necessary accessories and including removing of old unserviceable item complete all as specified and directed. |
| 81 | Supply & fix andfixing in repairs Telephone socket(RJ11) one module with top cover plate and inner frameincluding all necessary accessories and including removing of old unserviceable item complete all as specified and directed. |
| 82 | Supply & fix andfixing in repairscopper conductor cable, PVC insulated, sheathed,flexible, multistranded,ISI marked, 1100 volts grade 3 core ;2.5 sqmm and including electric connection through PVC conduit in concealed/casing caping in surface from ceiling fan to ceiling roseand including removing old unserviceable item complete all as specified and directed. |
| 83 | Supply & fix andfixing in repairs20 watts LED post top lantern made in cast aluminium spigot housing with decorative opal polycarbonate diffser and IP65 protectionand providing suitable fixing arrangements such as necessary civil works,nuts,bolts and washers andincluding removing old unserviceable itemcomplete all as specified and directed. |
| 84 | Supply & fix andfixing in repairs 40 watts LED post top lantern made in cast aluminium spigot housing with decorative opal polycarbonate diffser and IP65 protectionand providing suitable fixing arrangements such as necessarycivil work, nuts,bolts and washers andincluding removing old unserviceable itemcomplete all as specified and directed. |
| 85 | Supply & fix andfixing in repairs LED flood light light fitting of capacity 170 Watt LED, light fitting in aluminium PDC housing, toughened glass cover with IP-65 protection and including removing of old unserviceable item complete all as specified and directed. |
| 86 | All as per item No.85 but forcapacity 120 watts,240V,LED light fitting complete all as specified and directed |
| 87 | All as per item No.85 but for capacity 100 watts,240V,LED light fitting complete all as specified and directed |
| 88 | All as per item No.85 but forcapacity 70 watts,240V,LED light fitting complete all as specified and directed |
| 89 | Supply and fixing and in repairsgalvanised metal flush box 1/2 moduleISI marked,and suitable for existing type as per site requirement and including removing old unserviceable item from existing loaction complete all as specified and as directed. |
| 90 | All as per item No-89but formetal box 3 module |
| 91 | All as per item No-89but formetal box 4/5 module |
| 92 | All as per item No-89but formetal box 6 module |
| 93 | All as per item No-89but formetal box 8/9 module |
| 94 | All as per item No-89but formetal box 12 module |
| 95 | All as per item No-89but formetal box 16 module |
| 96 | All as per item No-89but formetal box 18 module |
| 97 | Supply and fixing in repairs modular any type cover plate with frame 1 module,ISI marked and suitable for existing type as per site requirement and incl screws,washears etc and including removing old unserviceable item from existing loaction complete all as specified and as directed. |
| 98 | All as per item No- 97but formodular any type cover plate with frame 2 module |
| 99 | All as per item No- 97but formodular anytype cover plate with frame3 module |
| 100 | All as per item No- 97but formodular any type cover plate with frame4/5 module |
| 101 | All as per item No- 97but formodular any type cover plate with frame6 module |
| 102 | All as per item No- 97but formodular any type cover plate with frame8/9 module |
| 103 | All as per item No- 97but formodular any type cover plate with frame12 module |
| 104 | All as per item No- 97but for modular any type cover plate with frame 16 module |
| 105 | All as per item No- 97but formodular any type cover plate with frame18 module |
| 106 | Taking down and Hanging only ceiling fan, wall fans after cleaning and connecting up including provision of cable from ceiling rose/switch socket or connector to fan and including providing necessary accessoriescomplete all as specified and as directed. |
| 107 | Taking down and fitting only exhaust fanafter cleaning and connecting up including provision of cable from ceiling rose or connector to fan and including providing necessary accessoriescomplete all as specified and as directed. |
| 108 | Fixing only and connecting electric meters 10-60 Amps any type single or three phase complete all as specified and directed and including providing necessary accessoriescomplete all as specified and as directed. |
| 109 | Taking down carefully existing electric meters of any type/capacity from work site and deposit to MES store yard/ Charge holder without damage for safe custody and supply and fixingsingle phase electronic meters temper proof LCD display with polycarbonate cover 230Volts,10-60 Amps, accuracy class-I,50Hz, confirming to IS-13779,IP-54,with parameters to show data,time current reading,load,PF,voltage and KWH including connected necessary items for functioning complete all as specified and directed. |
| 110 | Taking down carefully existing electric meters of any type/capacity from work site and deposit to MES store yard/ Charge holder without damage for safe custody and Supply only three phaseelectronic meters temper proof LCD display with polycarbonate cover 415Volts,10-60 Amps, accuracy class-I,50Hz, confirming to IS-13779,IP-54,with parameters to show data,time current reading,load,PF,voltage and KWH including connected necessary items for functioning complete all as specified and directed. |
| 111 | Supply and fixing 1 or 2 module fan regulator piano switch type/socket type as per site requirement, electronic, stepped type, 100/120 Watts,240Volts,AC,ISI marked complete all as specified and directed. |
| 112 | Supply and fixingswitch piano type, 6 Amps, flush mounted,1 way, 240 volts,ISI markedand including removing old unserviceable item complete all as specified and directed. |
| 113 | Supply and fixing bell push6 Amps,240 volts, ISI marked and including removing old unserviceable item complete all as specified and directed. |
| 114 | Supply and fixingswitch socket outlet6Amps,5 pin,flush type 240 volts,ISI marked and including removing old unserviceable item complete all as specified and directed. |
| 115 | Supply and fixing switch socket combination 6Amps,5 pin, flush type 240 volts,ISI marked and including removing old unserviceable item complete all as specified and directed. |
| 116 | Supply and fixing switch socket combination 6/16Amps,6pin 240 volts withneon indicator type,ISI markedand including removing old unserviceable item complete all as specified and directed. |
| 117 | Supply and fixing switch socket combination 6/16Amps,6pin ,240 volts,ISI marked and including removing old unserviceable item complete all as specified and directed. |
| 118 | Supply and fixing junction boxe topplastic round cover,four terminals and including removing old unserviceable item complete all as specified and directed. |
| 119 | Taking down old unserviceableair conditions complete indoor and outdoor units and incl disconnecting the electrical connections from switch board, MS stand etc from existing bldgs/location without any damages andfurther deposited in MES store yard for safe custodyand Supply and fixing, install, new wall splitindoor & outdoor unit of capacity 1.5TRwith copper condenser complete,dual/swing inverter type compressor, complete with cordless remote control unit with suitable batteries and remote holder and complete indoor and outdoor units and standard accessories i.e necessary copper tube as per site requirement, Heavy duty MS stand for out door unit,indoor unit plug top,holefastners,necessary suitable three core PVC sheathed copper conductor for inter connections indoor and out door units, heavy suty drain pipe from indoor unit to outside bldg with minimum 5 star ratingcomplete all as specified and directed. |
| 120 | Servicing and Survey/Audit of central ACPlants by authorised OEM Service Engineer for Central AC plants/ Package type AC plants / Walking cooler (Cold Room Systems)/Chillers/Central AC plant Compressors/Mother board circuits/VFDs/Cooling towers/condensor uits/sensors/AHU units(At all plants)etc for complete techical audit in each quarterlyinspectionsand corrective repairs /technical requirements/spare parts analisation and replacemet of burnt/damaged /unsv spare partsand rectifing troubles / offroad rectifications in the stipulated time period by OEMauthorised Engineer ( Blue Star/Carrier/ACCEL as per site OEM requirement) Complete all as specified and directed. Note:1 . Checking the all AC plantsby the authorised OEMservice Engineer and Technicians making a complete surveyreportaganistAC plant/Eqpt for our records duly signatured by him.2. Spare parts will be measured and paid separately. |
| 121 | M&L for preparation of old surface by scraping and smoothing the surface with water emery paperandpainting with approved colour of synthetic enemelled paint of two coat over a coat of primer red oxide and writing letters/numbers(SM/MES Nos.) ofCompressor with motor, foundation frame, including foundation of A/c plants of capacities 30 to 33 TR and cleaning the surrounding area up to three metre out side area of the plant by cutting grasses and surface dressing including white wash of plantroom complete all as specified and directed by Engineer in charge.(Note: The arrangement ofmen power,T&P and necessary items shall be contractors responsibility) |
| 122 | All as peritemNo 121 above butCondenser assembly of AC plant of capacity 30 to 33 TR. |
| 123 | All as per item No 121 above butCondenser water pump with motor, foundation frame and including foundations, rubber washers,glands, nuts, bolts and washers of AC plant of capacity 30 to 33 TR |
| 124 | All as per item No 121above butexposed water circulation and gas circulations pipe lines including marking direction of flow of AC plant of capacity 30 to 33 TR. |
| 125 | All as per item No 121above but Cooling tower cleaning with proper cleaning agents twise in the contract periodwithout any damages in cooling towers complete of AC plant of capacity 30 to 33 TR |
| 126 | All as per item No 121above but for 22/30 TR capacity A/C plant complete all as specified and directed as Compressor with motor, foundation frame including foundation. |
| 127 | All as per item No 121above butCondenser assembly of AC plant of capacity 22/30 TR. |
| 128 | All as per item No 121above butCondenser water pump with motor, foundation frame and including foundation rubber washers,glands, nuts, bolts and washers of AC plant of capacity 22/30 TR. |
| 129 | All as per item No 121above butExposed water circulations and gas circulates pipe lines including marking direction of flow of AC plant of capacity 22/30 TR. |
| 130 | All as per item No 121above butCooling tower complete of AC plant of capacity 22/30 TR. |
| 131 | M&L for replacement of cast iron sluice valve with stainless steel spindles with flanged ends duly ISI marked confirming to IS 780 part1, PN 1 type complete suitable as per exiting AC plant for the 100 MM bore sizes complete all as specified and directed. |
| 132 | All as per item No 131 above but 80 MM bore |
| 133 | All as per item No 131 above but 65 MM bore |
| 134 | Taking down old unsv butterfly valve from existing location and supply and fixing new butterfly valve of size 100 mm dia and including necessary pipe fittings nuts,bolts,washers and rubber washers etc complete all as specified and directed . |
| 135 | All as per item No 134 above but size 80 mm dia. |
| 136 | All as per item No 134 above but size 65 mm dia. |
| 137 | All as per item No 134 above but size 50 mm dia. |
| 138 | Taking down old unsv Non return valve from existing location and supply and fixing new non return valveof size 100 mm dia and including necessary pipe fittings, nuts,bolts,washers and rubber washers etc complete all as specified and directed . |
| 139 | All as per item No 138 above but size 80 mm dia. |
| 140 | All as per item No 138 above but size 65 mm dia. |
| 141 | All as per item No 138 above but size 50 mm dia. |
| 142 | Taking down old unsv Non return butterfly valve from existing location and supply and fixing new non return butterfly valve valve of size 100 mm dia and including necessary pipe fittings, nuts,bolts,washers and rubber washers etc complete all as specified and directed . |
| 143 | All as per item No 142 above but size 80 mm dia. |
| 144 | All as per item No 142above but size 65 mm dia. |
| 145 | All as per item No 142above but size 50 mm dia. |
| 146 | Taking down old unsv pipe line from existing loaction and supply and fixing new MS ERWheavy duty pipe of size 100 mm dia with fittinmgs and including providing necessary fabrication,welding work and accessoriesnuts,bolts and washers complete all as specified and directed. |
| 147 | All as per item No 146 above but size 80 mm dia. |
| 148 | All as per item No 146 above but size 65 mm dia. |
| 149 | All as per item No 146 above but size 50 mm dia. |
| 150 | Taking down old unsv pipe line from existing loaction and supply and fixing new GIheavy duty pipe of size 100 mm dia with fittings and including providing necessary fabrication,welding work and accessoriesnuts,bolts and washers complete all as specified and directed. |
| 151 | All as per item No 150 above but size 80 mm dia. |
| 152 | All as per item No 150 above but size 65 mm dia. |
| 153 | All as per item No 150 above but size 50 mm dia. |
| 154 | All as per item No 150 above but size 40 mm dia. |
| 155 | All as per item No 150 above but size 32 mm dia. |
| 156 | All as per item No 150 above but size 25 mm dia. |
| 157 | Taking down old unsv gate valves from existing loaction and supply and fixing new gate valve of size 100 mm dia with necessary accessoriesnuts,bolts and washers complete all as specified and directed. |
| 158 | All as per item No 157 above but size 80 mm dia. |
| 159 | All as per item No 157 above but size 65 mm dia. |
| 160 | All as per item No 157 above but size 50 mm dia. |
| 161 | All as per item No 157 above but size 25 mm dia. |
| 162 | Taking down old unsv strainer for suction from existing loaction and supply and fixing new strainer of size 150 mm dia with necessary accessoriesnuts,bolts and washers complete all as specified and directed. |
| 163 | All as per item No 162 above but size 100mm dia. |
| 164 | M&L for Dismantling and removing defective fins of FRP type cooling tower and supply and fixing new PVC finsbrick containing suitable for existing cooling tower system, eleven layers size of brick 600 mm x 300 mm x 150 mm complete all as specified and directed. |
| 165 | M&L for dismantling and removal of old unserviceable motor and Supply and fixing in replacement of cooling tower fan motor with long shaft,flange mounted (induction motor) of capacity 2/2.5 HP, 415 V as per site conditions/suitable and incl providing necessary shaft key,shaft,nuts,bolts and wahsers complete all as specified and directed. Note- Old u/s motor to be deposite in AGE E/M store.(Note: The arrangement ofmen power,T&P, settings shall be contractors responsibility) |
| 166 | M&L for dismantling and removal of old unserviceable motor and Supply and fixing in replacement of cooling tower fan motor with long shaft,flange mounted (induction motor) of capacity 3 HP, 415 V as per site conditions/suitable and incl providing necessary shaft key,shaft,nuts,bolts and wahsers complete all as specified and directed. Note- Old u/s motor to be deposite in AGE E/M store.(Note: The arrangement ofmen power,T&P, settings shall be contractors responsibility) |
| 167 | M&L for dismantling and removal of old unserviceable motor and Supply and fixing in replacement of cooling tower fan motor with long shaft,flange mounted (induction motor) of capacity 5 HP, 415 V as per site conditions/suitable and incl providing necessary shaft key,shaft,nuts,bolts and wahsers complete all as specified and directed. Note- Old u/s motor to be deposite in AGE E/M store.(Note: The arrangement ofmen power,T&P, settings shall be contractors responsibility) |
| 168 | M&L for dismatling and removal of old uservieable cooling tower alluminium fan hub 38 mm bore assembly with 4 blades with connected clamps and connected accessories nuts, bolts and washers.S & F new cooling tower alluminium fan hub 38 mm bore assembly with 4 blades as per site requirement wih all connected accessories,uts,bolts and washers complete all as specified and directed. Note- Old u/s fan hub to be deposite in AGE E/M store (Location 9 ESR KTA area)(Note: The arrangement ofmen power,T&P, settings shall be contractors responsibility) |
| 169 | Opening of shell and tube condensor end covers for inspection, pressure testing for leakage detection of condensor and identification of leakage, arresting the same with brazing, pressure testing after repairs, reassembling of end covers including cost ofrubber gasket and making water connections, testing and commissioning to the entire satisfaction of Engineer-in-charge complete all as specified. (Note: The arrangement ofmen power,T&P, Nitrogen gas,welding eqpts shall be contractors responsibility) |
| 170 | M&L for dismantling and removal of old unserviceable chilled water tank and S & F in replacement of chilled water storage tank stainless steel with installation for AC plant as per existing size and specification complete all as specified and directed. |
| 171 | M&L for dismantling and refixing after proper alignment with & including providing new belt,nut bolt and fixing accessories for fan & motor of cooling tower of AC plant complete all as specified and directed. |
| 172 | S&F in replacement blower shaft both end bearing with casing self revolving type NTN P-207 as per existing complete all as specified and directed by EIC |
| 173 | Supply and fixing in replacement cooling tower fan with hub as per sample/suitable for 60/70/80 TR of existing size as directed by Enigneer-in-charge. |
| 174 | M&L for dismantling and removal of old unserviceable motor and S & F in replacement of blower motor of capacity 20 HP, 415 V with installation for AC plant as per existing specification and conditions complete all as specified and directed. Note- Old u/s motor to be deposite in AGE E/M store. |
| 175 | Supply and charging refrigerant gas R-22 complete all as specified and directed. |
| 176 | Taking out / purging of refrigerant gas from the system of A/c plant 1 x 30/33 TR capacity carrying out vacuum test by vacuuming the whole A/c plant with the help of vacuum pump and checking the complete system for leakages. Carrying out the pressure test by chargingthe nitrogen gas in the system and checking of any leakagepoint , repair / rectification of the same and removing the nitrogen gas from the system and charging of refrigerant gas including charging of additional gas as required and complete all as specified and directed. (Note: The arrangement ofmen power,T&P and Nitrogen gas shall be contractors responsibility) |
| 177 | All as per item No 176 above for 1 x 12.5/22 TRunit of A/c plant, complete all as specified and directed. |
| 178 | S & F in repairs thermostat expansion valve suitable for 12.5 to 33 TR complete all as specified and directed. |
| 179 | S & F in repairs water temparature sensor suitable for 12.5 to 33 TR complete all as specified and directed. (Make: as per existing model and make or suitable any other approval) |
| 180 | M&L for dismantling and removal of old unserviceable condensor coil and S&F in replacement condensor coil for 5.5 TR capacity condensor as per existing site requirement for package type AC plant complete all as specified and directed. |
| 181 | Supply and fixing in replacement ofliquid line stainer filter for SMC-6-65/SMC-4-100 complete all as specified and directed. |
| 182 | Supply and charging of compressor oil complete all as specified and directed. |
| 183 | M&L for dismantling and removal of old unserviceable motor with pump and S&F in replacement monoblock pump motor of capacity 10 HP, 415 V as per site requirement and conditions for AC plant complete all as specified and directed and Old u/s pump motor to be deposite in AGE E/M store. (Note: The arrangement ofmen power,T&P, settings shall be contractors responsibility) |
| 184 | M&L for descaling ofthe entire water circulating system for central AC plant water cooled of capacity upto 3 x 33 TR along with condensers, cooling tower/piping pumps etc.Opening condenser by disconnecting nut bolts and cleaning withMAIC descalingsolution with help of descaling pump/wire brush, cleaning rod etc circulating above solutionin condenser pipe lines as required time, flushing out the complete solution from condensers pipe line by fresh water with pressure.Re-assembling by replacement of unserviceable nut bolts washers gaskets etc all as specified and directed.Note:- cleaning and descaling shall be carried out by pump with acid as required to keep head pressure within safe limit. If any damage during cleaning/descaling repair shall be carried out by contractor without any extra cost. (Note: The arrangement ofmen power,T&P, settings by mechanicshall be contractors responsibility) |
| 185 | M&L for clean the filter & cooling coil, gas leakage testing and electrical fault detection of any kind for package type AC plant of capacity 4.5/5 TR complete all as specified and directed. |
| 186 | M&L for clean the filter & cooling coil, gas leakage testing and electrical fault detection of any kind for package type AC plant of capacity 10/13.5 TR complete all as specified and directed. |
| 187 | Checking of air conditioning plant water cooled any size , capacity and location forfunctioning of motors, condenser , blower fan motors , unusual noise,refrigerant standing pressure and nut bolt washers etc including testing for smooth functioningand inform Engr in Chargefor repair if required complete all as directed by Engr-in-charge.(Note: The arrangement ofmen power,T&P, settings by mechanic shall be contractors responsibility) |
| 188 | S&F in repair fan belt No C-112 complete all as specified and directed, |
| 189 | S&F in repair fan belt No B-86 complete all as specified and directed. |
| 190 | S&F in repair fan belt No B-84 complete all as specified and directed. |
| 191 | S&F in repair fan belt No C-108complete all as specified and directed,. |
| 192 | S&F in repair fan belt No B-66complete all as specified and directed. |
| 193 | S&F in repair AHU V belt No B-104complete all as specified and directed. |
| 194 | S&F in repair fan belt No PB82Bcomplete all as specified and directed. |
| 195 | S&F in repair AHUAir filter 20 micronof size 20\"\"x20\"\"x2\"\" complete all as specified and directed |
| 196 | Dismantling complete ACCEL Compressor set Model SMC-4-65 of 30 TR Capand overhauling the compressor with repairand checking ofwornout holes of studs and providing over size studs with nuts & washers and gaskets .Rematlling and balancing of piston,replacement of piston ring,scrapper ring, split pin, castle nut, connecting rod bolt ,bushing for piston pin, and set of sealing ring of compressor and refitting the same after the repair/replacement duly all as specified and tested for smooth functioning of model SMC-4-100 complete all as specified and directed by Engr-in-charge. (Note-1:The all spare parts are measured and paid separately in relevent items) (Note-2: The arrangement ofmen power,T&P, settings by mechanic and testing shall be contractors responsibility) |
| 197 | S&F in repair for compressor set Model No SMC-4-65 suction valve ring plate 1.2mm |
| 198 | S&F in repair for compressor set Model No SMC-4-65 Discharge valve ring plate 1.20mm |
| 199 | S&F in repair for compressor set Model No SMC-4-65 Safty valve assembly |
| 200 | S&F in repair for compressor set Model No SMC-4-65 connecting rod bolt |
| 201 | S&F in repair for compressor set Model No SMC-4-65 Castle nut |
| 202 | S&F in repair for compressor set Model No SMC-4-65 Split pin |
| 203 | S&F in repair for compressor set Model No SMC-4-65 Half section of BRGSTD |
| 204 | S&F in repair for compressor set Model No SMC-4-65 Bushing with collar STD |
| 205 | S&F in repair for compressor set Model No SMC-4-65 Shaft seal including 10 A-G |
| 206 | S&F in repair for compressor set Model No SMC-4-65 Piston with pin and rings |
| 207 | S&F in repair for compressor set Model No SMC-4-65 Piston ring |
| 208 | S&F in repair for compressor set Model No SMC-4-65 Scrapper ring |
| 209 | S&F in repair for compressor set Model No SMC-4-65 Bushing for piston pin |
| 210 | S&F in repair for compressor set Model No SMC-4-65 Valve spring |
| 211 | S&F in repair for compressor set Model No SMC-4-65 Spring for unloading ring |
| 212 | S&F in repair for compressor set Model No SMC-4-65 Set of GasketASL-1453 |
| 213 | S&F in repair for compressor set Model No SMC-4-65 Set of sealing ring |
| 214 | S&F in repair for compressor set Model No SMC-4-65 Set of Neoprene Oring |
| 215 | S&F in repair for compressor set Model No SMC-4-65Cylinder W/O suction valve (R-22) |
| 216 | S&F in repair for compressor set Model No SMC-4-65 Gasket F-10 |
| 217 | S&F in repair for compressor set Model No SMC-4-65 Gasket F-12 |
| 218 | S&F in repair for compressor set Model No SMC-4-65 Seeger ring |
| 219 | S&F in repair for compressor set Model No SMC-4-65 GasketB-05 |
| 220 | S&F in repair for compressor set Model No SMC-4-65 GasketL-17 |
| 221 | S&F in repair for compressor set Model No SMC-4-65 Liquid line stainer (R-22) |
| 222 | S&F in repair for compressor set Model No SMC-4-65 Pilot control solenoid valve |
| 223 | S&F in repair for compressor set Model No SMC-4-65 Expansion valve |
| 224 | S&F in repair for compressor set Model No SMC-4-65 Hand shut off valve |
| 225 | S&F in repair shaft seal assembly of compressor of ACCEL make Model SMC-4-65 complete all as specified and directed |
| 226 | Dismantling complete ACCEL Compressor set Model SMC-4-100 of 33 TR Capand overhauling the compressor with repairand checking ofwornout holes of studs and providing over size studs with nuts & washers and gaskets .Rematlling and balancing of piston,replacement of piston ring,scrapper ring, split pin, castle nut, connecting rod bolt ,bushing for piston pin, and set of sealing ring of compressor and refitting the same after the repair/replacement duly all as specified and tested for smooth functioning of model SMC-4-100 complete all as specified and directed by Engr-in-charge. (Note-1:The all spare parts are measured and paid separately in relevent items) (Note-2: The arrangement ofmen power,T&P, settings by mechanic and testing shall be contractors responsibility) |
| 227 | S&F in repair for compressor set Model No SMC-4-100 suction valve ring plate 1.2mm |
| 228 | S&F in repair for compressor set Model No SMC-4-100 Discharge valve ring plate 1.20mm |
| 229 | S&F in repair for compressor set Model No SMC-4-100 Safty valve assembly |
| 230 | S&F in repair for compressor set Model No SMC-4-100 connecting rod bolt |
| 231 | S&F in repair for compressor set Model No SMC-4-100 Castle nut |
| 232 | S&F in repair for compressor set Model No SMC-4-100 Split pin |
| 233 | S&F in repair for compressor set Model No SMC-4-100 Half section of BRGSTD |
| 234 | S&F in repair for compressor set Model No SMC-4-100 Bushing with collar STD |
| 235 | S&F in repair for compressor set Model No SMC-4-100 Shaft seal including 10 A-G |
| 236 | S&F in repair for compressor set Model No SMC-4-100 Piston with pin and rings |
| 237 | S&F in repair for compressor set Model No SMC-4-100 Piston ring |
| 238 | S&F in repair for compressor set Model No SMC-4-100 Scrapper ring |
| 239 | S&F in repair for compressor set Model No SMC-4-100 Bushing for piston pin |
| 240 | S&F in repair for compressor set Model No SMC-4-100 Valve spring |
| 241 | S&F in repair for compressor set Model No SMC-4-100 Spring for unloading ring |
| 242 | S&F in repair for compressor set Model No SMC-4-100 Set of GasketASL-1453 |
| 243 | S&F in repair for compressor set Model No SMC-4-100 Set of sealing ring |
| 244 | S&F in repair for compressor set Model No SMC-4-100 Set of Neoprene Oring |
| 245 | S&F in repair for compressor set Model No SMC-4-100 Cylinder W/O suction valve (R-22) |
| 246 | S&F in repair for compressor set Model No SMC-4-100 Gasket F-10 |
| 247 | S&F in repair for compressor set Model No SMC-4-100 Gasket F-12 |
| 248 | S&F in repair for compressor set Model No SMC-4-100 Seeger ring |
| 249 | S&F in repair for compressor set Model No SMC-4-100 GasketB-05 |
| 250 | S&F in repair for compressor set Model No SMC-4-100 GasketL-17 |
| 251 | S&F in repair for compressor set Model No SMC-4-100 Liquid line stainer (R-22) |
| 252 | S&F in repair for compressor set Model No SMC-4-100 Pilot control solenoid valve |
| 253 | S&F in repair for compressor set Model No SMC-4-100 Expansion valve |
| 254 | S&F in repair for compressor set Model No SMC-4-100 Hand shut off valve |
| 255 | S&F in repair shaft seal assembly of compressor of ACCEL make Model SMC -4-100 complete all as specified and directed |
| 256 | S & F in repair of Sprinkler system for cooling tower complete all as specified and directed. |
| 257 | S&F in repair shaft seal assembly SMC 6-65 complete all as specified and directed |
| 258 | M&L in repairs to the cooling tower of 2 x 30/33 TR capacity by replacing the rusted GI wire mesh of existing gauge and weight of size 1.075Mx0.60x04 Nos with clamps, nuts and bolts etc complete all as specified and directed. |
| 259 | S&F in replacement fresh air grill of size 600mmx350mm having wire mesh, closing/opening dampers of suitable size with handle of PGI sheet of 20 gauge complete all as specified and directed. |
| 260 | S & F in replacement of Battery 12Volt 180 AH with initial charging maintenance free suitable for DG Sets complete all as specified and directed. |
| 261 | S & F in replacement of Battery 12Volt 150 AH with initial charging maintenance free suitable for DG Sets complete all as specified and directed. |
| 262 | Supply and charging refrigerant gas R-404/R-407, complete all as specified and directed. |
| 263 | Dismantling the power supply of electric motor any type including dismantling from pump and taking to workshop with necessary transportation and opening the complete motor and rewinding the rotor with super enameled copper wire as per the existing gauge with necessary insulation, sticks and varnishing, including replacement of shaft bearing 02 Nos complete of capacity 20 to 30HP complete all as specified and directed. (Note-1: The arrangement ofmen power,T&P,transport and testing shall be contractors responsibility) |
| 264 | All as per item No.263 above but of capacity5 to 7.5 HP electric motor any type complete all as specified and directed. |
| 265 | All as per item No.263above but of capacity10 to 15 HP electric motor any type complete all as specified and directed. |
| 266 | All as per item No.263above but 1 to 3 HP electric motor any type complete all as specified and directed. |
| 267 | Dismantling complete Centrifugal /Mono Block pump set of any type and overhauling the pump re-threading of wornout holes of studs and providing over size studs with nuts & washers.Rematlling and balancing of shaft, replacement of gunmetal bush bearing and gland packing,nuts,bolts,washres,rubber gasketsof pump set.and refitting the same after the repair/replacement duly all as specified and tested for smooth functioning of capacity 10 to 15 HP complete all as specified and directed.(Note-1: The arrangement ofmen power,T&P,transport and testing shall be contractors responsibility) |
| 268 | All as per item No.267above but capacity 5 to 7.5 HP complete all as specified and directed. |
| 269 | M&L for clean the fins & tank with acid/bleaching powder, tightening of nut bolt and clean the strainer of cooling tower of AC plant of any capacity complete all as specified and directed. |
| 270 | Supply and fixing in replacement of MCB 32 Amp TPNAC, 415 volts, 10 KAs complete all as specified and directed. |
| 271 | Supply and fixing in replacement of MCB 40 Amp TPNAC, 415 volts, 10 KA s complete all as specified and directed. . |
| 272 | Supply and fixing in replacement of MCB 25 Amp TPNAC, 415 volts, 10 KA s complete all as specified and directed. . |
| 273 | Supply and fixing in replacement of MCB 10 Amp TPNAC, 415 volts, 10 KA s complete all as specified and directed. |
| 274 | Supply and fixing in replacement of MCB 63Amp TPNAC, 415 volts, 10 KA s complete all as specified and directed. |
| 275 | Supply and fixing in replacement of moulded case circuit breaker panel mounting type , AC, 415 volts,16 KA of capacity 63amps 4 pole complete all as specified and directed. |
| 276 | Supply and fixing in replacement of moulded case circuit breaker panel mounting type , AC, 415 volts, 25 KA of capacity 100 amps 4 pole complete all as specified and directed. |
| 277 | Supply and fixing in replacement of moulded case circuit breaker panel mounting type , AC, 415 volts, 35 KA of capacity 125 amps, 4 pole complete all as specified and directed. |
| 278 | Supply and fixing in replacement of moulded case circuit breaker panel mounting type , AC, 415 volts, 36 KA of capacity 250 amps 4 pole complete all as specified and directed. |
| 279 | Supply and fixing in replacement of moulded case circuit breaker panel mounting type ,AC, 415 volts, 50 KA of capacity400 amps 4 pole complete all as specified and directed. |
| 280 | M&L for clean the filter, cooling coil & blower of AHU for AC plant of any capacity complete all as specified and directed. |
| 281 | Taking down old unserviceable AHU complete cooling coil assembly from existing location and checking of water leakages in AHUcooling coilmaking repairs by brazing, gas welding,necessary copper tubes, copper jointing rods, joints etc after refixing the same its location properly and carry out the pressure testing after repairs of AHU for AC plant of any capacity complete all as specified and directed. (Note-1: The arrangement ofmen power,T&P,transportations etc and testingcomplete job shall be contractors responsibility) |
| 282 | Supply and fixing in replacement ofPower contactor , 4Pole ,440v,50Hz ,400amp, : MNX 400 2 NO+2 NC complete all as specified and directed. |
| 283 | Supply and fixing in replacement Contactor, 3poles with AC coil of MNX265 amps capacity complete all as specified and directed. |
| 284 | Supply and fixing in replacement Contactor, 3poles with AC coil ofMNX225 amps capacity complete all as specified and directed. |
| 285 | Supply and fixing in replacement Contactor, 3poles with AC coil ofMNX185 amps capacity complete all as specified and directed. |
| 286 | Supply and fixing in replacement Contactor, 3poles with AC coil ofMNX70 amps capacity complete all as specified and directed. |
| 287 | Supply and fixing in replacement Contactor, 3poles with AC coil ofMNX50 amps capacity, complete all as specified and directed. |
| 288 | Supply and fixing in replacement Contactor, 3poles with AC coil ofMNX45 amps capacity, complete all as specified and directed. |
| 289 | Supply and fixing in replacement Contactor, 3poles with AC coil ofMNX40 amps capacity, complete all as specified and directed. |
| 290 | Supply and fixing in replacement Contactor, 3poles with AC coil ofMNX32 amps capacity, complete all as specified and directed. |
| 291 | Supply and fixing in replacement Contactor, 3poles with AC coil ofMNX25 amps capacity, complete all as specified and directed. |
| 292 | Supply and fixing in replacement Contactor, 3poles with AC coil ofMNX18 amps capacity, complete all as specified and directed. |
| 293 | Supply and fixing in replacement of temperature gauge (thermometer) digitaltype 0-50 degree centigrade complete all as specified and directed. |
| 294 | Supply and fixing in replacement ofcontrol switches pressure gauge low pressure (LP) complete all as specified and directed. |
| 295 | Supply and fixing in replacement ofcontrol switches pressure gauge Highpressure (HP) complete all as specified and directed. |
| 296 | Supply and fixing in replacement of HRC Fuse unit 400 Ampscomplete all as specified and directed. |
| 297 | Supply and fixing in replacement of HRC Fuse unit 200 Amps complete all as specified and directed. |
| 298 | Supply and fixphase failure preventor for the protection motorscomplete all as specified and directed. |
| 299 | Supply and fixing in replacement Aluminium lugs suitable for above 120 sqmm upto 240sqmm cable complete all as specified and directed. |
| 300 | Supply and fixing in replacement Aluminium lugs suitable for upto 120 sqmm cable complete all as specified and directed. |
| 301 | Supply and fixing in replacement thermal over load relay of range 6.5 to 10 Amps complete all as specified and directed |
| 302 | All as per item No301 but for 15 to 22 Amps capacity complete all as specified and directed. |
| 303 | All as per item No301 but for 30 to 50 Amps capacity complete all as specified and directed. |
| 304 | All as per item No301 but for50 to 70 Amps capacity complete all as specified and directed. |
| 305 | All as per item No301 but for70 to 100 Amps complete all as specified and directed. |
| 306 | Supply and fixing in replacement of indicating lamp set (RYB) LED type complete all as specified and directed. |
| 307 | S&F in replacement Star Delta Timer 0-30 Seconds duration complete all as specified and directed. |
| 308 | Supply and fixing in replacement of electronic adjustable cyclic timer complete all as specified and directed. |
| 309 | Supply and fixing in replacement industrial water pressure switch meter as per existing complete all as specified and directed. |
| 310 | Supply and fixing in replacementof On off push bottonswitch electrical complete all as specified and directed. |
| 311 | Supply and fixing in replacement Voltmeter digital type (0-500V) complete all as specified and directed. |
| 312 | Supply and fixing in replacement Ammeter digital type (0- 100 Amps) complete all as specified and directed. |
| 313 | S&F in repair Rotary selector switch 3 position complete all as specified and directed. |
| 314 | Supply and fixing in replacement CT Coil 100/5 Amps complete all as specified and directed. |
| 315 | Supply and fixing in replacement CT Coil 60/5 Amps complete all as specified and directed. |
| 316 | Supply and fixing in replacement CT Coil 30/5 Amps complete all as specified and directed. |
| 317 | M & L for ladder of GI Pipe heavy 40 mm dia for cooling tower approx 6 mtr length complete all as specified and directed. |
| 318 | M&L in renewal for making of computerised colour/ printed of layout plan or brief details i.e history of installation/ machinery of various installations on and including1.0mm thick plastic laminated acrylic sheet of size 1500x1200mm fixed to new hard boards with & including PVC beading of suitable size fixed to all edges of board with & including mild steel screws of suitable size complete all as specified and directed.Note:- Details i.e layout plan and brief details shall be provided by Engineer-in-Charge separately during execution. |
| 319 | M&L in renewal for making of computerised colour/ printed of name of installation and details of various installations on and including1.0mm thick plastic laminated acrylic sheet of size 1000x600mm fixed to new hard boards with & including PVC beading of suitable size fixed to all edges of board with & including mild steel screws of suitable size complete all as specified and directed.Note:- Name & details of installations shall be provided by Engineer-in-Charge separately during execution. |
| 320 | M&L for Repairs to cooling tower of 12.5/22 TR by replacing the rusted GI Wire mesh of existing gauge and weight of size nuts ,clamps,and bolts etc complete all as specified and directed. |
| 321 | Supply,install, Commissioning and testing of capacity of cooling tower 100 TR, one no twin cell type corrosion resistant,fire retardant,FRP induced draft,rectangular/square type counter flow cooling tower of capacity 120% of plant running capacity with maximium allowable temperature 50 degree centigrade,drift loss 0.005% of water circulation,such as 80TR,water flow rate USGPM-1500,Inlet temp-97.5F,outlet temp-90F,wet bulb temp-83F,FRP materials,suitable mechanical eqpt-hot dip galvanized UV stabilized,PVC piping work,incl aluminium fan hub and blades-06 Nos,suitable size blades,fan motor 5 HP,960 rpm, dry weight 500 kgs,operating weight approx 1750 kgs, size suitable for as existing,incl sprinklers and functioning required connected items and including removing old unserviceable complete all as specified and directed. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail