| 1 | Takingout carefully copper/aluminium point wiring,Light,fan,socket or powercomplete with all fitting, fixtures such as switch socket out let, ceiling rose ,holder ,regulator, DBs etc including making good the disturbed surface of wall/floors complete all as specifed and as directed. |
| 2 | Taking down distribution boards/wooden board ,switch fuse units,steel enclosures for MCB of any type and removing from site complete all as specified and as directed. |
| 3 | Taking down ceiling fan/exhaust fan and deposit to MES store yard from site complete all as specified and as directed. |
| 4 | Taking down existing unserviceable submain wiring any size and making good the disturbed surface complete all as specified and as directed. |
| 5 | Material and labour for point wiring for one light controlled by one way switch with 1.5 Sqmm PVC insulated unsheathed single core multi-stranded copper conductor (FRLS) cable 1100 Volts grade drawn through and includingrigid non metallic PVC concealed conduit (medium grade) of suitable dia along with 1.5 sqmm continuous PVC insulated unsheathed single core multi-stranded copper conductor (FRLS) cable for earth continuity wire, connected to earth dolly and to be terminated in and includingpressed steel sunken boxes , readily available (Having wall thickness not less than 1.22 mm for boxes upto a size of 200 mmX300 mm and beyond that the wall thickness shall be not less than 1.63 mm) concealed type for mounting of modular switches, sockets, fan regulators alongwith modular plate etc including testing on completion complete including cutting chases for concealed conduit pinning in making good to facing and pointing in using cement mortar 1:3 and making good disturbed surface complete all as specified and as directed. |
| 6 | All as per item No 5 above but for one fan/exhaust fan point controlled by one piano switch complete all as specified and as directed. |
| 7 | All as per item No 5 above but for one light point controlled by two way switch complete all as specified and as directed. |
| 8 | All as per item No 5 above but for one bell point controlled by one bell push complete all as specified and as directed. |
| 9 | All as per ser item No 5 hereinbefore but for one 3 pin socket outlet 5 Amp Same board complete all as specified and as directed. |
| 10 | All as per ser item No 5 hereinbefore but for one 3 pin socket outlet 5 Amp independent complete all as specified and as directed. |
| 11 | All as per Item no 5 here-in-before but for one15 Amp 3pin switch socket outlet, independent with 2.5 Sqmm single core multi-stranded copper conductor cable (FRLS) along with 2.5 sqmm continuous PVC insulated unsheathed single core multi-stranded copper conductor (FRLS) cable for earth continuity wire all as specified and as directed. |
| 12 | Supply and fix modular type switch, one way 6 Amps , 1 module complete all as specified and directed. |
| 13 | Supply and fix modular type switch, two way 6 Amps , 1 module complete all as specified and directed. |
| 14 | Supply and fix modular type switch, one way 16 Amps, 1 module complete all as specified and directed. |
| 15 | Supply and fixmodular type socket 5 pin, 6 Amps 2 module complete all as specified and directed. |
| 16 | Supply and fixmodular type socket 5 pin, 6 A/16 Amps2 module complete all as specified and directed. |
| 17 | Supply and fixof Ceiling rose surface bakelite three terminals 240 volts complete all as specified and as directed. |
| 18 | Supply and fixLamp holder PVC case body of Bakelite with back plate suitable for batten fittings, complete all as specified and as directed. |
| 19 | S&F LED Bulb cool white 10 Watt Elegant design direct fit for easy installation complete all as specified and as directed. |
| 20 | S&F for modular type bell push 6Amps, 1 module complete all as specified and as directed. |
| 21 | S&F for bell multi music 230V, AC complete all as specified and as directed. |
| 22 | Supply and fixof Tube light fitting integrated type suitable for LED 20W indoor decorative aluminium extrudedLED batten complete with hosing with all accessories pre wired and making connection with threecore copper flexible cable of size 23/0.0076 from ceiling rose to PVC connection to light fitting complete all as specified and directed. |
| 23 | Supply and fixof Tube light fitting integrated type suitable for LED 10W indoor decorative aluminium extrudedLED batten complete with hosing with all accessories pre wired and making connection with threecore copper flexible cable of size 23/0.0076 from ceiling rose to PVC connection to light fitting complete all as specified and directed. |
| 24 | Supply and fix factory made epoxy powder coated Distribution board VTPN 6 ways ,415 Volts with metal door (IP-43 protection) fabricated from minimum 1.6mm thick CRCA sheet and fixed flush to wall and suitable for universal mounting and including 100 Amp copper bus bar, neutral bar, standard DIN rail, Earth bar and cable ties for cale management, top and bottom removable gland plates with Knockouts and suitable for one SPN/DP-MCB as incomer and SP MCBs outgoing and confirming to IS : 8623 complete all as specified and as directed. |
| 25 | Supply and fix in replacement of Thermal magnetic release MCCB 4 pole 415 volt rapturing capacity 16 KA of 125 amp complete all as specified and as directed. |
| 26 | Supply and fixfactory made epoxy powder coated Distribution board SPN 12 ways (SPN MCB DB) with metal door (IP-54 protection) fabricated from minimum 1.6mm thick CRCA sheet and fixed flush to wall and suitable for universal mounting and including 200 Amp copper bus bar, neutral bar, standard DIN rail, Earth bar and cable ties for cale management, top and bottom removable gland plates with Knockouts and suitable for one SPN/DP-MCB as incomer and SP MCBs outgoing complete all as specified and confirming to IS : 8623. |
| 27 | Supply and fixof MCB SP-06 to 32 Amp,10KA, 240 volts complete all as specified. |
| 28 | Supply and fixof MCB SPN 32 Amp, 240 volts 50Hz AC supply, complete all as specified and as directed. |
| 29 | S&F for single core PVC insulated unsheathed multistranded copper conductor cable 1 sqmm, 1100volts ISI marked drawn in the same point wiring conduit complete all as specified and as directed. |
| 30 | Material and labour for sub main wiring with two single core PVC insulated (unsheathed) multi strand copper conductor FRLS cable of size 6 sqmm and one single core PVC insulated (unsheathed) solid copper conductor FRLS cable of size 6 sqmm as in continuous earth wire drawn into and including concealed PVC conduit medium grade 25mm dia ISI marked complete with fittings and fixings accessories complete and including cutting chases pinning in making good to facing and pointing in using cement moter 1:3 and making good disturbed surface complete all as specified and as directed. |
| 31 | M & L for earthing complete with galvanized steel earth plate 600x600x6mm thick buried vertically in ground to depth not less than 2.25 mtr below ground level, with top edge of the plate not less than 1.50 mtr below normal ground level, connected to GI earth lead wire4 mm dia by means of bolts, nuts,check nuts and washers of galvanized iron and connection to main switch board of panel, including watering pipe GI 20 mm bore light grade 15mm bore for earthing lead, wire mess, funnel, salt, charcoal dust, excavation and refilling pit with PCC 1:2:4 type B1(using 20mm dia stone aggregate) reinforced with 6mm dia round bar @ 75mm cement concrete both always with MS handle 12mm dia and frame all as shown in electric plate No 3 in page 497 of SSR Part I (2009) and pouring extra Clay Soil of qty not less than one cubic meter into the earth pit and alsoremoval of excavated soil not less than 50 mtr from the earthing place all as specified and directed and tested on completion. including testing complete all as specified and directed. |
| 32 | Supply and fix Integral LED security light luminaire 35W LED 230 volts made of pressure die cast aluminium housing with high power LED’s lens & toughned glass IP-66suitable for mounting existingbracket of size 32/40mm dia G I pipe, fixing clamps ,bolts, nuts of suitable size as required at site complete all as specified and as directed |
| 33 | S & F LED light fitting 1x9W/1X10Wbulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size complete all as specified and as directed. |
| 34 | S&F for ceiling fan complete with blades, electronic regulator and accessories, 230V, 1200mm sweep, Min air delivery 210 CFM with service value 6.00 BEE, five star rated with brushless direct current motor (BLDC) including supply and fix Anti Suicide fan rod of suitable size and length with the provn, if the load on fans exceeded 22Kgs, than the smart rod/pipe opens from its centre and spring in the pipe expands. the fan rod should be tested at Govt of India\"s MSME Labs for its functionality and the test report from Labs should be submitted to Engr-in-Charge while installation complete all as specified and directed. |
| 35 | M&L for cutting of suitable size of holes for 300/250mm exhaust fan in wall and grouting of nuts and bolts in wall and making good to match with existing walls complete all as specified and directed. |
| 36 | Taking down electric energy meter single phase any size or type form the existing site and refixing the same at same place after carrying out necessary repair work in building and making the surface good to match with existing surface all as specified and directed by Engr-in-Charge. |
| 37 | Supply and fix exhaust fan, steel body AC single Phase. 230V of size 300mm sweep with, blades, and frame and louvers connecting electrically using 3 core 0.75 Sq mm PVC insulated flexible copper conductor cable over all sheathed all as required at site and as directed.complete all as specified and directed. |
| 38 | Supply and fix exhaust fan, PVC body AC single Phase. 230V of size 250mm sweep with, blades, and frame and louvers connecting electrically using 3 core 0.75 Sq mm PVC insulated flexible copper conductor cable over all sheathed all as required at site and as directed.complete all as specified and directed. |
| 39 | S&F 3 pin 15/16 Amps plug top suitable for 240V 50Hz AC supply complete all as specified and directed. |
| 40 | Supply, install and testing water heater storage type (Geyser) single phase 230V, 50Hz, 5 star energy saving high density PUF insulation tank made of heavy duty magnesium anode rod with steel core to protect enamelled tank from rust & corrosion, vertical installation type, 25 ltrs capacity, 2000watts rated power, incoloy 800 glass coated heating element, tank coateding of feroglass powder, tank made of ultra thick super cold rolled steel plates, rated pressure 0.8MPa, IPx4 protection consist of safety valves, thermal cut off, thermostat including connecting up fixed to walls by drilling of holes, grouting of bolts of suitable size with nuts etc and making good disturbed surface complete all as specfied and directed. |
| 41 | S&F for 15mm bore tubing, medium grade with all fittings and fixedto walls and ceiling or laid in floors complete all as specified and as directed. |
| 42 | S&F for angle cock fancy type chromium plated with capstan head, screwed down, high pressure screwed both ends for 15mm bore iron pipe or for unions and fixed complete all as specified and directed. |
| 43 | S&F for bib tap 15mm chromium plated fancy type cast copper alloy with crunch or butterfly handle screwed down for iron pipe and fixed complete all as specified and as directed. |
| 44 | Material and labour for point wiring for one exhaust fan controlled by one way switch with 1.5 Sqmm PVC insulated unsheathed single core multi-stranded copper conductor (FRLS) cable 1100 Volts grade drawn through and includingrigid non metallic PVC concealed conduit (medium grade) of suitable dia along with 1.5 sqmm continuous PVC insulated unsheathed single core multi-stranded copper conductor (FRLS) cable for earth continuity wire, connected to earth dolly and to be terminated in and includingpressed steel sunken boxes , readily available (Having wall thickness not less than 1.22 mm for boxes upto a size of 200 mmX300 mm and beyond that the wall thickness shall be not less than 1.63 mm) concealed type with 3mm thick bakelite sheet cover for mounting switches, sockets, fan regulators etc including testing on completion complete including cutting chases for concealed conduit pinning in making good to facing and pointing in using cement mortar 1:3 and making good disturbed surface compllete all as specified and as directed. |
| 45 | S&F for switch piano flush type single pole, one way 5 Amp, complete all as specified and directed. |
| 46 | S&F for exhaust Fan metallic body, AC single phase, 230V of size 300mm sweep with, blades and frame and louvers connecting electrically using 3 core 0.75 Sqmm PVC insulated flexible copper conductor cabel over all sheathed all as required at site complete all as specified and directed. |
| 47 | S&Ffor exhaust Fan plastic body, AC single phase 230V of size 25mm sweep with, blades and frame and louvers connecting electrically using 3 core 0.75 Sqmm PVC insulated flexible copper conductor cable over all sheathed all as required at site complete all as specified and directed. |