| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sqmm FRLS PVC insulated copper conductor single core cable etc. as required. Group C. |
| 2 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
| 3 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 4 | Supplying and fixingfollowing size/modules, G.I box along with modular base & cover plate for modular switches in recess etc. as required |
| 5 | 6 Module (200 mm X 75 mm) |
| 6 | Supplying and fixing following modular switch/socket on the existingmodular plate & switch box including connections but excluding modular plate etc. as required. |
| 7 | 5/6 A Switch |
| 8 | 3 pin 5/6 A socket outlet |
| 9 | 15/16 A Switch |
| 10 | 6 pin 15/16 A Socket outlet |
| 11 | Supplying of LED surface mounted Industrial Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sinkof aluminum housing such that LED junction temperature shall not rise above 90°C).Powder coated die cast / Extruded aluminium Body (Thickness ≥ 1.20 mm) |
| 12 | 40 watt |
| 13 | Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent/LED fitting of all types, complete with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 14 | Supply, installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electroic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C(max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 15 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar,din bar, interconnections, powder painted including earthing etc.as required. (But without MCB/RCCB /Isolator) |
| 16 | 6 way, SPN double door |
| 17 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (but without MCB/RCCB/Isolator) |
| 18 | 4 way (4+12), Double door |
| 19 | Supplying and fixing of following rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 20 | Single pole (10 A) |
| 21 | Single Pole & neutral (32A) |
| 22 | Triple Pole Neutral (32 A) |
| 23 | Supply and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/PVC conduit as required. |
| 24 | 2 x 6 sq. mm |
| 25 | Supplying of following size XLPE insulated & PVC tape innersheathed aluminium conductor armoured cable of 1.1 KV grade of following size confirming to IS:7098 (Part- I) 1988 with up to date ammendment as required. |
| 26 | 2 x 10 Sq. mm |
| 27 | 4 x 16 Sq. mm |
| 28 | Providing, laying and fixing following dia G.I pipe (medium Class) in ground complete with G.I fittings including trenching (75 cm deep) and refilling etc as reqd. |
| 29 | 32 mm Dia nonimal Bore |
| 30 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of followig size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
| 31 | Upto 35 sq. mm |
| 32 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/HUME/METAL pipe as required. |
| 33 | Upto 35 sq. mm |
| 34 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 35 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 36 | Earthing with G.I. earth pipe 4.5 mtr long 40 mm dia including accessories ,and providing masonary enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal /cokeand salt etc as required. |
| 37 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 38 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ sub main wiring/ cable as required. |
| 39 | Supplying and fixing of 32 mm dia X 3.2 meters long G.I. pipe(medium class) bracket for mounting of fluorescent /HPMV / HPSV street light fitting on pole including bending the pipe to the required shape, 2 nos 40 mm X 3 mm flat iron clamp with nuts, bolts and washer, paintaing the flat iron with primer and finish paint stc. as required. |
| 40 | P/F of cable termination of PVC box of size 20cm X 15cm X 10 cm with compression termination arrangements, 6-10 Amp SP MCB and double natural link etc as required. |
| 41 | Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminum body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP-66,IK-10, CRI >80, under voltage and over voltage protection, EMIEMC. As per CISPR 15 , lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). |
| 42 | 90 watt |
| 43 | Supply,installation,testing & commissioning of integral well glass luminaire compressed of dia cast canopygear box housing and glass driver surge with heat resistance glass of LED well glass fitting of 70 watt. 110 Lm/watt to 125Lm/Wattor Luminous should not be less than 7700 as per direction of Engineer in-chargeas per direction of engineer-In-Charge. |
| 44 | Providing and fixing following rating and breaking capacity 4 pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 45 | 100 A MCCB |
| 46 | Credit items for old dismantled non functionalunserviceable 10/20Amps SP MCB |
| 47 | Credit items for old dismantled non functional unserviceable heat resistance glass of LED well glass fitting of 70 watt |
| 48 | Credit items for old dismantled non functionalunserviceable 18 watt 1 x 1 led surface light |
| 49 | Credit items for old dismantled non functionalunserviceable 36 watt 2 x 2 led surface light |
| 50 | Credit items for old dismantled non functional unserviceable T8 LED Tube |
| 51 | Credit items for old dismantled non functional unserviceable LED street light fitting of 60 watts |