Provision Of Fire Safety Measures At Ahq, Vayu Bhawan, New Delhi.-SUB HEAD - 1 GAS SUPPRESSION SYSTEM 1 Design, Supply, Installation, Testing, and Commissioning of seamless cylinders with the following capacity that is approved by PESO and appropriate for UL/ FM/ VDS listed agent FK-5-1-12 gas The installed cylinder should be equipped with bracket assembly, pressure gauge, warning signage, cylinder strap, cylinder cap, end cap, valve assembly, valves and cylinders should also be in accordance to the PESO approved rules and specifications, The fire protection fluid should be FK-5-1-12 , filled in liquid form at the site (fill density not exceeding PESO certification) at 42 bar & above i/c hydraulic UL/FM/VD flow calculated for the suppression areas that is calculated from OEM software in accordance with specifications, drawings, and as per the engineer-incharges instructions, also includes fixing of M.S. stands of the appropriate size as per site requirement for cylinders complete system should be UL/FM/VDS from same OEM. Complete system should be UL/ FM/ VDS approved & gas should be filled in UL/FM/VDS approved filling station. a 34 LTR b 80 LTR. 2 Supplying and filling of fire suppression gas agent or Fire Protection Fluid FK-5-1- 12. (UL/FM VDS Approved) in the existing seamless cylinder etc. as per specification/drawings and direction of Engineer In Charge etc. as required. 3 Supply, Installation, Testing & Commissioning of UL/ FM/ VDS Listed Electric cum Manual Actuator with Assembly for Primary Cylinder as per specification/drawings and direction of Engineer In Charge etc. as required. 4 Supply, Installation, Testing & Commissioning of UL/ FM /VDS Listed Pressure Operated control Head with Assembly & Actuator for Secondary Cylinder as per specification/drawings and direction of Engineer In Charge etc. as required. 5 Supply, Installation, Testing & Commissioning of UL/ FM /VDS Listed Cylinder Low Pressure Supervisory Switch as per specification/drawings and direction of Engineer In Charge etc. as required. 6 Supply, Installation, Testing & Commissioning of UL/ FM/ VDS Listed Manifold Pressure Switch as per specification/drawings and direction of Engineer In Charge etc. as required. 7 Supply, Installation, Testing & Commissioning of UL/ FM/ VDS Listed Master Discharge Flexible Hose as per specification/drawings and direction of Engineer In Charge etc. as required. 8 Supply, Installation, Testing & Commissioning of UL/ FM/ VDS Listed Actuation Flexible Hose as per specification/drawings and direction of Engineer In Charge etc. as required. 9 Supply, Installation, Testing & Commissioning of UL/ FM/ VDS Listed Manifold Check Valve for above Cylinder, complete with Listed Adapters & Accessories as required as per specification/drawings and direction of Engineer In Charge etc. as required. 10 Supply & Installation of Manifold fabricated out of seamless pipe (ASTM - A-106 Grade B) as per approved flow calculation from UL/FM/VDS (OEM provided) Software with 100/80/65 mm pipe with all accessories like socket weld fittings, tees, elbows fasteners etc. to connect the discharge hose to cylinders. The Manifold should include all the support and necessary fittings to mount on the wall/surface complete as per specification/drawings and as directed by Engineer In Charge 11 Supply, Installation, Testing & Commissioning of UL/FM/VDS Listed brass Nozzles, 360 Deg / 180 Deg Throw, selection as per approved UL/FM/VDS Listed flow calculations generated from UL/FM/VDS (OEM provided) Software etc as per drawings and direction of Engineer In Charge etc. as required. a) Standard Nozzle 50 mm b) Standard Nozzle 40 mm c) StandardNozzle 32 mm d) Standard Nozzle 25 mm 12 Providing laying testing & commissioning of following sizes SCH 40 Seamless Pipe (ASTM -A-106 Grade B) suitable for distribution of fluid agent including welding, fittings like elbow, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the pipe on the wall/celling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as per drawings and direction of Engineer In Charge etc. as required. a 100 MM b 65 MM c 50 MM d 40 MM e 32 MM f 25 MM SUB HEAD- 2 (INTELLIGENT ADDRESSABLE FIRE ALARM AND GAS RELEASE SYSTEM) 1 Supplying, installation, testing and commissioning of microprocessor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non-volatile memory (EPROM), power supply unit (230 ± 5 % V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories. The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. a) Two Loop Panel. 2 Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required. 3 Supply, installation, testing and commissioning of Intelligent Addressable UL/FM/VDS approved manual abort stations/manual release stations, shall be fitted with transparent hinged covers to avoid possibility of accidental operation. The abort will be monitored simultaneously by the main fire alarm. 4 Supply, Installation, Testing & Commissioning of Warning Sign of Acrylic Board 150mm X 300mm with Marking GAS DISCHARGE. DO NOT ENTER/GAS DISCHARGE. EVACUATE IMMEDIATELY. Shall Operate on 24 V DC, Driven Through file cum extinguisher Panel. (for use outside room) as per specification/drawings and as directed by Architect / Engineer in charge. 5 Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. 6 Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. 7 Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. 8 Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed temperature thermistor complete with base as required. 9 Supplying, installation, testing & commissioning of intelligent addressable programmable sounder complete as required. 10 Supplying, installation, testing & commissioning of addressable manual call point complete as required. 11 Supplying, installation, testing & commissioning of addressable fire control module complete as required. 12 Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS/HFFR outer sheath complete as required. 13 Supplying & laying of 4x1.5 sqm. fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required etc complete as reqd.. 14 Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required. 15 Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. a) 100 mm width X 50 mm depth X 1.6 mm thickness Total of Sub-Head 2 SUB HEAD- 3 CLEAN AGENT BASED FIRE SUPPRESSION SYSTEM IN ELECTRICAL PANEL 1 Supplying, installation, testing & commissioning of 2 Kg capacity IS approved cylinder filled with clean agent FK-5-1-12/HFC-236Fa (UL Listed, LPCB Certified for the enclosed enclousers, open with natural air flow and open with forced air flow)with zero ozone depletion potential complete with approved DLP valve assembly, push in connector to connect the tube, mounting brackets. 2 Supplying, installation, testing & commissioning of 4 Kg capacity IS approved cylinder filled with clean agent FK-5-1-12/HFC-236Fa (UL Listed, LPCB Certified for the enclosed enclosures, open with natural air flow and open with forced air flow) with zero ozone depletion potential complete with approved DLP valve assembly, push in connector to connect the tube, mounting brackets. complete as reqd. 3 Supplying, installation, testing & commissioning of automatic fire detection and suppression system made by special modified Polyamide (PA), Color Red RAL300, High grade quality, Inner diameter 4mm, Outer Diameter 6 MM, Melting Point approx. 222 degrees Celsius when heating up with 10 K/minute, Burst Pressure 100 bar at 20°C. Temperature range : minus 40°C to +80°C. Working Pressure 20Bar at 20°C. Burst Temperature : when Pressurized with dry Nitrogen at 16 bar pressure approx 100°C to 110°C, UL approved as per UL 521 standard for heat detectors for Fire Protective Signaling System. complete as reqd. 4 Supplying, installation, testing & commissioning of End of Line adapter with Pressure gauge for Automatic fire suppression tube used for fitting at the end of the tube for pressurizing and are pressurizing the tube. Fitting made by brass (plated / unplated), Stainless steel, Elastomeric Sealings, Copper Nickle plated, Temperature range TS -20 Deg C till + 60 Deg C, Maximum working pressure 25 Bars, made as per PED Pressure Equipment Directives. complete as reqd. 5 Supplying, installation, testing & commissioning of Pressure Switch to monitor Pressure drop in the tube, switch point 5 Bars. Switch Type SPST, Normally Open, Electric Rating: 120/240 VAC-375 VA, 24 VAC-125 VA, Open 160 psi y-7, Close 185 psi y-5, Pressure switch + adaptor / 5bar / M10x1 / FM approved / SPST- UL Listed Pressure switch assembly. complete as reqd. 6 Supplying, installation, testing & commissioning of T Connection, Brass, Nickel plated, for 4x6 mm Sensor Tube, quick and easy disassembly using special tool, working pressure 15 bars at 15 Deg Temperature, temperature range-40 Deg C till + 80 Deg C, Elastomeric Sealings, External Diameter tube 6mm. complete as reqd. 7 Supplying, installation, testing & commissioning of End of Line Plug for Automatic fire suppression tube used for fitting at the tube end to terminate the point. Fitting made by brass nickel plated material with Elastomeric sealings, Temperature range TS -20 Deg C till+ 60 Deg C, Maximum working pressure 25 Bars, made as per PED pressure equipment Directives. complete as reqd. 8 Supplying, installation, testing & commissioning of microprocessor based 2 Zone Low weight Master Control Unit panel Built in Power Supply and battery Charger.-System Operating Voltage 12VDC-Reset/ON-off Switch- Evacuate/Lamp Test/Silence Switch.- Visual Indication for Zone-1,Zone- 2,Hooter and Power ON.-3 Sets of NO/NC/C dry contact.-12VDC out for Hooter.-Mains 230VAC-Fabrication MS CRCA sheet of 20 SWG colour RED with screw lock. Complete with hooter cum flasher with wiring (Max 15 Mtrs.) to make complete system operational. The control Panel should have provision for integration with fire Alarm /SCAD/BMS System-(CE/ERTL approved) complete as reqd.