| 1 | Supply installtion and commissioning Fire alarm control panel addressable complying with BS EN 54 two loop panel of capacity from 99 detectors & 99 modules upto 200 detector and modules per each loop complete all as specified and as directed. |
| 2 | Dismantling and taking down carefully Circuitwiring any sizeand making good the disturbed surfaces of wall/ floor to match the existing wall/ floor etccomplete all as specified and as directed. |
| 3 | Supply and fixing Circuit wiring with single core cable 2x1.5 sq mm PVC insulated Unsheathed stranded copper conductor cable 1100 Volts grade drawn through existing PVC/steel Surface/Concealed conduit alongwith 1x1.5 Sq mm PVC insulated unheathed copper conductor cable as earth wire connected with complete all as specified and as directed. |
| 4 | S & F in replacement of Butter fly valve of size 80 mm diacomplete all as specified and as directed. |
| 5 | Material and labour for hose box made of 18 gauge MS sheet 800mm X 600mm X 250mm with double door with 4 mm thick glass and door frame made of 16 gauge MS sheet painted fire red oxide and brilliant white inside yardcomplete all as specified and as directed. |
| 6 | Material and Labour for fire extinguishers manual swing type mild steel fire hose reel drum of size 20/25 mm dia, 30 mtr length with brass nozzle, minimum inlet pressure 220kPa, maximum working pressure 1.2 Mpa (12 Bar), side plates, sheet steel pwd coated red colour, spindle mild steelcomplete all as specified and as directed. |
| 7 | Rewinding of three phase electric motors of capacity 60 HP with super enamelled copper winding wire as per existing size, turns andappropriate gauge including all insulating material i.e Varnish , Cotton tape , insulating paper and soldering etccomplete all as specified and as directed. |
| 8 | Material and labour for replacement of branch pipe gun metal 63 mm instantaneous inlet, made threaded outlet, with 15 mm bore nozzle longcomplete all as specified and as directed. |
| 9 | Material and labour for carrying out maintenance of Industrial RO of cap 500 ltr/Hr Model EDS-100, AC Supply 230V/50Hz,4Kg/cm2 with FRP Tank Model-1248, Maximum pressure 150 psi,controllerwater purifier by replacement of pre filter candle ,CARBON FILTER ,Membrane , sediment filter etc sleek and carbon block twice in a year and servicing twice after regular intervals, including the replacement of circuit board, Digital RO Controller, and any other part as required at site to make functional throughout the year complete all as specified and as directed. |
| 10 | Supply and fixing in replacement of V Belt No B-102 for Washing Machine 50 Kg complete all as specified and as directed. |
| 11 | Supply and fixing in replacement of V Belt No B-100 for Washing Machine 60 Kg complete all as specified and as directed. |
| 12 | Supply and fixing in replacement of V Belt No B-72 for Drying Tumbler 60 Kg complete all as specified and as directed. |
| 13 | Supply and fixing in replacement of V Belt No B-64 for Washing Machine 50 Kgs complete all as specified and as directed. |
| 14 | Material and labour for replacement of HP 120 communication system equipped to have 04 analog lines, 04 digital extns & 12 anolog extensions intercom system with features like welcome voice guidance, conference calls - 5 party, caller line identification, built in music on hold, over voltage over current protection, flexible number, different ring tones, hot line suitable of existing EPABX system in lifts - 6 No and machine roomcomplete all as specified and as directed. |
| 15 | Supply and fixing in replacement of telephone set sleek model complete all as specified and as directed. |
| 16 | Supply and fixing in replacement of jelly field cable 10 pair for making connections in existing system of EPABXcomplete all as specified and as directed. |
| 17 | M&l for repair of washing/sluicing machine cap upto 15 kgs by replacement of Door Gas kit, Glen dori, belt etccomplete all as specified and as directed. |
| 18 | Supply and fix in repairof Steam Boiler Burner Rod Assembly with replacement ofPhotocell CEM-8205, Solenoid Coil, Ignition Electrode and Ignition Transformer, Electrode Cap, diffuser plate, burner gauge, nozzel denfoss complete all as specified and as directed. |
| 19 | Supply and fix in repairof Steam Boiler Steam Line spares main stop valve-1&2, Safety Valve 1/1.1/2\", Pressure Gauge 0.25 kg/cm2complete all as specified and as directed. |
| 20 | Supply and fix in repairs of Steam Boiler Water pump spares Gasket packing, Circlip, Washer packing, Oil Ring, bearing set, oil seal, connecting rod, piston complete all as specified and as directed. |
| 21 | Supply and fix in repairof Steam Boiler Water line spares Booster pump, filter element, pressure gauge 0-25 kg/cmv 2, mettalic hose 1/1.2 mcomplete all as specified and as directed. |
| 22 | Supply and fix in repairsof Steam Boiler Fuel line spares, Oil Seal-AJ6, O Ring - AJ6, Simplex Oil Filter, Filter Element, Sealing Ringcomplete all as specified and as directed. |
| 23 | Supply and fix in repairof steam boiler control panel boardby replacement of its accessories like: safty switches, contol cable, fire alarm, steam pressure switch, Digital temperature Display, lit switches with high quality lamps, atmospheric economiser, burner safty valve, sensorcomplete all as specified and as directed. |
| 24 | Supply and fix in replacement of Steam Boiler Tubes (Coil) made with hot rolled seamless carbon and alloys (nickel) of steam boiler (Non-IBR type) of cap 600 Kg/Hrhaving reverse fuel technologycomplete all as specified and as directed. |
| 25 | M&L for replacement of lower ducting of steam Boiler cap 600 Kg/Hrcomplete all as specified and as directed. |
| 26 | M&L for replacement of upper ducting of steam Boiler cap 600 Kg/Hrcomplete all as specified and as directed. |
| 27 | M&L for repalcement of fuel pump of steam Boiler of cap 600 kg /Hr make themax model Revomaxcomplete all as specified and as directed. |
| 28 | M&L for repalcement of water feed pump of steam Boiler of cap 600 kg /Hr make themax model Revomaxcomplete all as specified and as directed. |
| 29 | Supply and fix in replacement of metalic Non-return valve of size 25 mm of steam boilercomplete all as specified and as directed. |
| 30 | Supply and fix in replacement of Eonomiser for the steam boiler cap 600 Kgs/Hr by taking out the defective by opening the Nuts, bolts & Washers and fixing fixing new one in existing position suitable for thermax make Steam Boilercomplete all as specified and as directed. |
| 31 | Supply and fix in replacement of elevator cabin fan of passenger lift(15 person) AC 230 Volt five blade Model: GF-300A, 53W, 1300 RPM of air flow 1100 m3/H of 40 dbcomplete all as specified and as directed. |
| 32 | Supply & fixmono block pumping set of cap 0.5 HP AC 230 V along with PVC connection pipe of 20 mm dia 10 Mtr longcomplete all as specified and as directed. |
| 33 | Supply and fixing in replacement Laundry timer 0-60 minutes complete all as specified and as directed. |
| 34 | S&F in replacement of MCB TPN 32 Amp \"C\" seriescomplete all as specified and as directed. |
| 35 | Electric Hand press heavy duty suitable for laundry commercial type 1250 watt operated on single phase AC supply with suitable size electric cord 2 mtr longcomplete all as specified and as directed. |
| 36 | M&L in replacement of steam radiator with stainless steel tube and aluminum pulley suitable for drying tumbler 60 kg(as per sample)complete all as specified and as directed. |
| 37 | M&L in repair MS sheet 2mm thick for replacing casing of boiler steam coil & tubing cut to size and made to shape as per site requirment including cutting, welding etc for Boilers complete all as specified and as directed. |
| 38 | Rewinding of three phase electric motors of capacity 2 HP/3 HP with super enamelled copper winding wire as per existing size, turns andappropriate gauge including all insulating material i.e Varnish , Cotton tape , insulating paper and soldering etccomplete all as specified and as directed. |
| 39 | Rewinding of three phase electric motors of capacity 5HP/7.5 HP with super enamelled copper winding wire as per existing size, turns andappropriate gauge including all insulating material i.e Varnish , Cotton tape , insulating paper and soldering etccomplete all as specified and as directed. |
| 40 | Rewinding of three phase electric motors of capacity 10 HP with super enamelled copper winding wire as per existing size, turns andappropriate gauge including all insulating material i.e Varnish , Cotton tape , insulating paper and soldering etccomplete all as specified and as directed. |
| 41 | Repair of microprocesssor based PLC (programmable logic controller ) of washing machine/drying tumbler with replacemnt of burnt parts such as timers, diode , capacitors and checking of. All electronic circuits with proper instruments and made it functionalcomplete all as specified and as directed. |
| 42 | M&L for repair and servicing of Washing Machine of cap 60 kgs front loading incl replacement of defective parts (if needed)complete all as specified and as directed.Note: Cost for replacement of defective parts has been measured and paid under relevent items. |
| 43 | 3 \" Motor pulley complete all as specified and as directed. |
| 44 | 16\" motor bush pulley complete all as specified and as directed. |
| 45 | Bearing-22210 complete all as specified and as directed. |
| 46 | Bearing slip-22310 complete all as specified and as directed. |
| 47 | Bearing-22215 complete all as specified and as directed. |
| 48 | Bearing slip-22315 complete all as specified and as directed. |
| 49 | Glen dori, oil seal complete all as specified and as directed. |
| 50 | Door gaskit complete all as specified and as directed. |
| 51 | Inner basket repair complete all as specified and as directed. |
| 52 | M&L for repair and servicing ofof hydro 25kgs capacity incl replacement of defective parts (if needed)complete all as specified and as directed.Note: Cost for replacement of defective parts has been measured and paid under relevent items. |
| 53 | Rubber Buffer complete all as specified and as directed. |
| 54 | Hydro spring complete all as specified and as directed. |
| 55 | Limit switch complete all as specified and as directed. |
| 56 | Push botton with NC 0-15 Min timer complete all as specified and as directed. |
| 57 | brake plate complete all as specified and as directed. |
| 58 | 1 KVA transformer complete all as specified and as directed. |
| 59 | delay off timer complete all as specified and as directed. |
| 60 | SS Lock complete all as specified and as directed. |
| 61 | Repair/replacement of air compressor of Motor capacity: 5 HP with auto cut, Motor type: three phase AC 415 Volts, No of cylinder: 02, Tank: 280 Ltrs, CFM: 30.2, Pressure:500 Poundcomplete all as specified and as directed. |
| 62 | M&L for repair and servicing of Sluicing Machine of cap 7 Kgs front loading incl replacement of defective parts (if needed)complete all as specified and as directed. |
| 63 | Repair/replacement of Wet/Dry Linen trolly stainless steel body of size 990mmx600mmx660mm complete with wheelscomplete all as specified and as directed. |
| 64 | Repair/replacement of touch control panel, LED bulbs,convertor of operation theatre lights Model Sims Prima 96Rcomplete all as specified and as directed. |
| 65 | M&L for replacement of defective Indion Resin 220 NA Softner SN COD 3914 of existing water softenning plantcomplete all as specified and as directed. |
| 66 | Supply & Fix MPV 40 NB side mounted (SFT) SN COD 8421 of water softening plantcomplete all as specified and as directed. |
| 67 | Supply only water hardness kit 500BX SN COD 3822 for water softening plantcomplete all as specified and as directed. |
| 68 | M&L for repair of UPS of capacity 10-20 KVA by repair/ replacement of insulated gate bipolar transistor (IGBT), DC capacitor, SCR module, logic board, diaod transisters, protection board or DC converter circuit board 3 phase of suitable ratingcomplete all as specified and as directed. |
| 69 | M&L for repair of UPS of capacity 2-5 KVA by repair/ replacement of insulated gate bipolar transistor (IGBT), DC capacitor, SCR module, logic board, diaod transisters, protection board or DC converter circuit board 3 phase of suitable ratingcomplete all as specified and as directed. |
| 70 | Material and labour for pressure testing of cylinder and refilling of fire extinguisher CO2 type of capacity 6.5 Kgs alongwith replacement of nozzle and hose as existingcomplete all as specified and as directed.Note : Testing certificate must be provided by the OEM. |
| 71 | Material and labour for pressure testing of cylinder and refilling of fire extinguisher CO2 type of capacity 4.5 Kgs alongwith replacement of nozzle and hose as existingcomplete all as specified and as directed. Note : Testing certificate must be provided by the OEM. |
| 72 | Material and labour for pressure testing of cylinder and refilling of fire extinguisher CO2 type of capacity 9 Kgs alongwith replacement of nozzle and hose as existingcomplete all as specified and as directed. Note : Testing certificate must be provided by the OEM. |
| 73 | Material and labour for pressure testing of cylinder and refilling of fire extinguisher ABC type of capacity 5 Kgs alongwith replacement of nozzle and hose as existing complete all as specified and as directed.Note : Testing certificate must be provided by the OEM. |
| 74 | Supply & fix in replacement of pressure release valve of size 25 mm dia for laundary plant as per existingcomplete all as specified and as directed. |
| 75 | S&F in replacement of detectors complying with and type certified to EN-45 addressebale type multisensor detectors with heat and smoke combination photoelectric/optical with base with self built intelligenceas per IS-11360complete all as specified and as directed. |
| 76 | S&F in replacement of fire alarm sounders/ Sirens Electronic type horizontal single stage continious normal opeartion for atleast 50 minutes with sound level 65 DB to 120 DB measured al 1.5 mtr with sound output variation of +5 DB of range 500 mtrcomplete all as specified and as directed. |
| 77 | Comprehensive maintenance including preventive and periodical maintenance of installed lift -06 Nos of capacity 15 passengers (1020 kgs) with speed of 0.40 m/s to 0.5 m/s in reliable, safe, efficient operating condition through authorised OEM or their accredited/ authorised agencies by regularly examining, lubricating and adjusting the eqpt and carrying out planned maintenance in a systematic and controlled manner using technician and expertise and replacement of all unserviceable as per OEM term & condition and schedule of maintenece provided by the OEM including machine and belt. Equipment covered such as Renew all wire ropes and chains (where fitted) as often required an adequate factor of saftey, to equalise the tension on all hoisting ropes, repair or replace conductor cables and hoistway and machine room elevetor wiring, machine, worn gear, thrust bearings, drive sheves, drive sheaves bearing, break contact, lining and components, Motor, motor generator, motor winding, rotating elements, commutator, brushes, brush holders,bearing, coils, resistence for operating motors circuits, magnet frames and other mechanical parts, controller, selector, levelling devices, cams, relays, solid state components e.g, PCB, transducers, resisters, condensors, power amplifiers, transformers, contacts, leads, dashpots, timing devices, steel selector tapes and mechanical and electrical driving equipment, governer,governer sheaves, shaft assembly, bearing, contacts and governers jaws, car and hall mechanical buttonss, car and hall position indicators, hall lanterns, car direction indication and other car landing signal features, deflectors or secondary sheave, bearing, car and counter weight guide rails, automatic power operated to be continued. |
| 78 | Door operator, car door hanger, car door contact, safty shoe, load weighing equipment, car frame, car safety mechanism and plateform, batteryry operated emergency light and alarm system, wiring of all eqipments and accessories, vibration materials, reverse phase relays, over load warning indicator and digital group indicator panel with micro-processer complete and automatic rescue device incl maintenance free battery and cost of material & qualified technician to attend the complaint on requirement basis including sunday and holiday complete all as specified and as directed. |
| 79 | S&F in replacement of addresseble manual call point resetteable type for fire alarm systemcomplete all as specified and as directed. |
| 80 | Material and labour for cutting, dismantling of existing MS steam pipe line with insulation and providing new MS steam pipe line 50 mm bore medium grade for making connections to the machines with cutting, making pieces including neccesary fittings and weldingcomplete all as specified and as directed. |
| 81 | M&L for descaling of steam boiler of cap 600 Kgs by descaling media SRI-S2 Liquid Boiler Descaling Chemical, standard grade or by Liquid Sulfamic Descalantis a liquid chemical substance used to remove limescale from metal surfaces in contact with hot watercomplete all as specified and as directed. |
| 82 | M&L for old painted or treated / untreated Steam Boiler Surface with Heat resistance Aluminium paint films of paint prepared and tested shall show no cracking, blistering, flaking or peelingcomplete all as specified and as directed. |
| 83 | M&L for old painted or treated / untreated iron pipes of size 80/100/150 mm dia of Fire Fighting plant and applying two coats of Oil based paint (of Red in colour and as directed) over a coat of red oxide zinc chrome primercomplete all as specified and as directed. |
| 84 | Supply and fixing stainless steel, globe valves, with side handle, half turn operated, ISI marked screwed both ends for iron pipe of size 50 mm borecomplete all as specified and as directed. |
| 85 | Supply and fixing stainless steel, globe valves, with side handle, half turn operated, ISI marked screwed both ends for iron pipe of size 40 mm borecomplete all as specified and as directed. |
| 86 | Supply installation ,testing and commisioning Automatic rescue device (ARD) part ID 529 system complete for lift of make ECEcomplete all as specified and as directed. |
| 87 | M&L for stainless Steel braided connection pipe of size 20/25mm of length 1.5 mtrcomplete all as specified and as directed. |