| 1 | Providing erecting and commissioning of 33/11 KV 20 MVA capacity substations along with 33 KV incoming UG line and 11 KV UG distribution network with 11/0.433 KV 100 & 200 KVA transformers and LT UG line. |
| 2 | 33 KV SIDE |
| 3 | P/E/C 33 KV Lightning Arrestors (Station type) |
| 4 | P/E/C 33 KV Isolators with EB (800 A) |
| 5 | P/E/C 33 KV Isolators without EB (800 Amp.) |
| 6 | P/E/C 33 KV Post Insulator |
| 7 | P/E/C Gantry Structure / Steel section for 33 KV Bus as per Sheet No.1 |
| 8 | P/E/C Disc Insulator 11 KV 70 KN |
| 9 | P/E/C AAAC 232 mm2 |
| 10 | P/E/C Strain Hardware for AAAC232 sq.mm. |
| 11 | P/E/C Earthing complete as per Sheet no.2 |
| 12 | P/E/C Power Transformer 33/11 KV, 10 MVA |
| 13 | P/E/C 33 KV P.T. |
| 14 | P/E/C 33 kV C. T. (400-200/1-1-1) |
| 15 | P/E/C 33 KV VCB complete 1600 Amp (O.D.) |
| 16 | P/E/C C&R panel for 33 KV Transformer with Diff. Protection |
| 17 | Structure for 33 KV CT & PT as per Sheet no.3 |
| 18 | P/E/C G.I.Nut Bolts |
| 19 | Insulators (OH-INS) |
| 20 | Supplying and erecting porcelain pin type insulator with GI pin suitable for 33kV line, complete as per specification no. OH-INS/PN |
| 21 | 11 KV SIDE |
| 22 | P/E/C 11 kv 250 MVA OD Switchgears comprising of 1 Incomer and 3 single feeder with associated OD panels, Islators, C.T. & P.T. etc. |
| 23 | P/E/C Take off structure for 3 outgoing feeder as per Sheet no.4 |
| 24 | P/E/C L.As. 11 KV (Gapless type) with disconector |
| 25 | P/E/C 11 kV Pin Insulators with G.I. Pins |
| 26 | P/E/C Clamps and Connectors as per Sheet no.5 |
| 27 | P/E/C Structure for 11 KV Main Bus as per Sheet no.6 |
| 28 | P/E/C S/S Yard lighting as per Sheet no.7 |
| 29 | P/E/C Battery set 30 Volt, 100 AH with Battery charger |
| 30 | P/E/C 11/0.43 KV x 100 KVA station Transformer as per Sheet no.8 |
| 31 | P/E/C Control cables for S/S as per Sheet no.9 |
| 32 | P/E/C AC Distribution Board \"B\" type |
| 33 | Civil works for 33/11 KV Sub Station. |
| 34 | Land Development of 33/11 substation ( As per table A) |
| 35 | Construction of Control room (As per table B) outdoor |
| 36 | Construction of Store room of size 8.0m X 6.0 m (As per table C) |
| 37 | P/E/C Electrification to 33/11 KB substation building (Lumsum) |
| 38 | Construction of WBM Road (As per table D) |
| 39 | P/E/C Chain link fencing and Bar bed wire fencing (As per table E) |
| 40 | Supplying & Providing Metal Spreading (As per table F) |
| 41 | Equipment Foundations for 1X 5 MVA or 1X10 MVA (1+3 Bay) + Stn Trans. (As table G) Outdoor |
| 42 | Equipment Foundations for additional 1X 5 MVA or 1X10 MVA (1+3 Bay) (As table G1) Outdoor |
| 43 | P/E/C Fire Wall for 2 x 10 MVA Power Transformer (as per table G3) Outdoor |
| 44 | Providing Water Supply arrangement for Control Room and Switch Yard.(As per table H) |
| 45 | Providing Borewell including pumpset and allied accessories. (As per table I) |
| 46 | Construction of cable trench with covers in Substation Yard. (As per table J) |
| 47 | Construction of retaining wall. (As per table K) |
| 48 | P/E/C Rain Water Harvesting (As per Table L) |
| 49 | Construction of Culvert (As per Table N) If required |
| 50 | Civil Works for NFIPS System (For 2 PTF) |
| 51 | Providing Foundation for 33 KV Feeder Bay without Gantyry Structure |
| 52 | Providing Foundation for 11 KV HT feeder Pillar |
| 53 | 33 KV FEEDER BAY without Gantry Structure |
| 54 | P/E/C 33 KV Lightning Arrestors (Station type) |
| 55 | P/E/C 33 KV Isolators with EB (800 A) |
| 56 | P/E/C 33 KV Isolators without EB (800 Amp.) |
| 57 | P/E/C 33 KV VCB complete 1600 Amp (O.D.) |
| 58 | P/E/C CT 200-100/1-1 A , 33 KV |
| 59 | P/E/C C&R panel for 33 KV for feeder breaker |
| 60 | P/E/C structures, Bus-bar material, Control Cables, clamps & painting etc for 11 KV Feeder bay .as per sheet (A+C+D+F) |
| 61 | P/E/C Marshalling Box |
| 62 | P/E/C Earthing work for 11 KV feeder bay as per Sheet (E) |
| 63 | 33 KV 3 X 300 mm2 U/G XLPE Cable |
| 64 | HT Cables (CB-HT) |
| 65 | Supplying , erecting & terminating XLPE insulated, galvanised steel formed wire armoured (strip) cable 33 kV(E), 3 x 300 sq. mm. aluminium conductor laid in provided trench / pipe as per specification no. CB-HT |
| 66 | Cable Enclosures (CB-CE) |
| 67 | Supplying & laying (including excavation) reinforced cement concrete pipe of NP-2 class of 150 mm diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. |
| 68 | Supplying & laying (including excavation) half round reinforced cement concrete pipe of NP-2 class of 150 mm diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. |
| 69 | Cable Joints & End Termination Kits (HT Cables) (CB-JT/HT) |
| 70 | Providing and erecting Heat shrinkable outdoor termination kit for 33 kV ( E )/33 kV (UE) XLPE HT cable 3x300 sq. mm. to 400 sq. mm. with necessary material as per specification no. CB-JT/HT |
| 71 | Providing and erecting Heat shrinkable straight through joint kit for 33 kV ( E )/33 kV (UE) XLPE HT cable 3x300 to 400 sq. mm. with necessary material as per specification no. CB-JT/HT |
| 72 | Supplying & erecting coarse Sand |
| 73 | 33 KV 3 X 300 mm2 XLPE underground cable for road crossing |
| 74 | P/E/C M.S.Channel of size 75 X 40 X 6 mm / 100 X 50 X 6 mm / M.S. Angle 50 X 50 X 6 mm |
| 75 | P/E/C M.S. Flat of size 50 X 6 mm |
| 76 | P/E/C 33 KV Isolators with EB (800 A) |
| 77 | Steel Poles (OH-PL) |
| 78 | Supplying and erecting rolled steel joist (girder) pole 152 x 152 mm (37.1 kg/m) with base plate in provided foundation as per specification no. OH-PL/RSJ |
| 79 | Insulators (OH-INS) |
| 80 | Supplying and erecting polymer pin type insulator with GI pin suitable for 33kV line, complete as per specification no. OH-INS/PN |
| 81 | Supplying and erecting polymer disc type insulator 70KN with necessary hardware suitable for 33kV line complete as per specification no. OH-INS/DI |
| 82 | P/E/C AAAC 100 MM2 |
| 83 | Supplying & erecting coarse Sand |
| 84 | Supplying , erecting & terminating XLPE insulated, galvanised steel formed wire armoured (round) cable 33 kV(E), 3 x 300 sq. mm. aluminium conductor laid in provided trench / pipe as per specification no. CB-HT |
| 85 | Supplying & laying (including excavation) reinforced cement concrete pipe of NP-2 class of 150 mm diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. Supplying & laying (including excavation) reinforced cement concrete pipe of NP-2 class of 150 mm diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. |
| 86 | \"Providing and erecting Heat shrinkable outdoor termination kit for 33 kV ( E )/33 kV (UE) XLPE HT cable 3x300 sq. mm. to 400 sq. mm. with necessary material as per specification no. CB-JT/HT \" |
| 87 | Double Pole Structure (Cut point) of 33 KV Line using 13 Mtr Long RSJ |
| 88 | \"Supplying and erecting rolled steel joist (girder) pole 152 x 152 mm (37.1 kg/m) with base plate in provided foundation as per specification no. OH PL/RSJ \" |
| 89 | P/E/C M.S. Flat of size 50 X 6 mm |
| 90 | P/E/C M.S.Channel of size 75 X 40 X 6 mm / 100 X 50 X 6 mm / M.S. Angle 50 X 50 X 6 mm |
| 91 | Supplying and erecting polymer pin type insulator with GI pin suitable for 33kV line, complete as per specification no. OH-INS/PN |
| 92 | P/E/C Strain Hardware for Dog 0.1 or equ. AAAC |
| 93 | Providing & erecting GI stay set for poles along with CC Foundation, including loop insulators at inaccessible height complete with anchor plate 150 x 150 x 6 mm straining screws GI stay wire 7/8 SWG GI stay rod 20 mm x 1.8 mtr length and pole clamps |
| 94 | Plate, Pipe type Earthing (EA-EP) |
| 95 | Supplying, installing and testing pipe type earthing with 40mm. dia. G.l. pipe or 20 mm dia. G.I. Rod complete with all accessories of GI materials & recording the results as per specification no. EA-EP |
| 96 | Accessories |
| 97 | Supplying and erecting barbed wire two ply with 12 SWG ply and 12 SWG barb with a gap between two bars of 75 mm. firmly fixed on provided angle supports with necessary materials complete. (6.044 meters/kg.). |
| 98 | Sheets (CP-SS) |
| 99 | Supplying, erecting, testing & commisioning GI sheet 1.6mm (16 SWG) caution board of size 250 x 200 mm duly painted with red oxide and enamel paint in marathi and hindi erected at position for HV/EHV (11000 Volts) erecting with compliance to IS 2551-1982. as per specification no. CP/SH/CR |
| 100 | C.C. Foundation |
| 101 | Making Cement concrete foundation including excavation (60 x 60)cm x deep 1/6 of pole length in 1:3:6 cement concrete 20 x 25 mm stone metal, 45cm x 45cm x 45cm/ 45cm dia. x 45cm height plinth duly plastered, with necessary curing and finishing complete. (for above 9m poles) |
| 102 | 11 KV 3 X 300 mm2 U/G XLPE Cable |
| 103 | Supplying , erecting & terminating XLPE insulated, galvanised steel formed wire armoured (round) cable 11 kV(E), 3 x 300 sq. mm. aluminium conductor laid in provided trench / pipe as per specification no. CB-HT |
| 104 | Supplying & laying (including excavation) reinforced cement concrete pipe of NP-2 class of 150 mm diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. |
| 105 | Supplying & laying (including excavation) half round reinforced cement concrete pipe of NP-2 class of 150 mm diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete |
| 106 | \"Providing and erecting Heat shrinkable straight through joint kit for 11 KV (E) XLPE HT cable 3x240 to 400 sq. mm. with necessary material as per specification no. CB-JT/HT \" |
| 107 | \"Providing and erecting Heat shrinkable outdoor termination kit for 11 KV (E) XLPE HT cable 3x240 to 300 sq. mm. with necessary material as per specification no. CB-JT/HT \" |
| 108 | Supplying & erecting coarse Sand |
| 109 | 11 KV 3 X 300 mm2 XLPE underground cable for road crossing |
| 110 | \"Supplying and erecting rolled steel joist (girder) pole 152 x 152 mm (37.1 kg/m) with base plate in provided foundation as per specification no. OH PL/RSJ \" |
| 111 | P/E/C M.S.Channel of size 75 X 40 X 6 mm / 100 X 50 X 6 mm / M.S. Angle 50 X 50 X 6 mm |
| 112 | P/E/C M.S. Flat of size 50 X 6 mm |
| 113 | P/E/C 11 KV Isolators with EB (400 A) |
| 114 | P/E/C 11 kV Pin Insulators with G.I. Pins |
| 115 | P/E/C AAAC 100 MM2 |
| 116 | Supplying , erecting & terminating XLPE insulated, galvanised steel formed wire armoured (round) cable 11 kV(E), 3 x 300 sq. mm. aluminium conductor laid in provided trench / pipe as per specification no. CB-HT |
| 117 | Supplying & laying (including excavation) reinforced cement concrete pipe of NP-2 class of 150 mm diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. |
| 118 | \"Providing and erecting Heat shrinkable outdoor termination kit for 11 KV (E) XLPE HT cable 3x240 to 300 sq. mm. with necessary material as per specification no. CB-JT/HT \" |
| 119 | Supplying & erecting coarse Sand |
| 120 | Double Pole Structure (Cut point) of 11 KV Line using 11 Mtr Long RSJ |
| 121 | \"Supplying and erecting rolled steel joist (girder) pole 100 x 116 mm (23 kg/m) with base plate in provided foundation as per specification no. OH-PL/RSJ \" |
| 122 | P/E/C M.S. Flat of size 50 X 10 mm |
| 123 | P/E/C M.S.Channel of size 75 X 40 X 6 mm / 100 X 50 X 6 mm / M.S. Angle 50 X 50 X 6 mm |
| 124 | P/E/C Strain Hardware for Dog 0.1 or equ. AAAC |
| 125 | \"Supplying and erecting polymer disc type insulator 45KN with necessary hardware suitable for 11kV line, complete as per specification no. OH-INS/DI \" |
| 126 | Providing & erecting GI stay set for poles along with CC Foundation, including loop insulators at inaccessible height complete with anchor plate 150 x 150 x 6 mm straining screws GI stay wire 7/8 SWG GI stay rod 20 mm x 1.8 mtr length and pole clamps |
| 127 | Supplying, installing and testing pipe type earthing with 40mm. dia. G.l. pipe or 20 mm dia. G.I. Rod complete with all accessories of GI materials & recording the results as per specification no. EA-EP |
| 128 | \"Supplying and erecting barbed wire two ply with 12 SWG ply and 12 SWG barb with a gap between two bars of 75 mm. firmly fixed on provided angle supports with necessary materials complete. (6.044 meters/kg.). \" |
| 129 | Making Cement concrete foundation including excavation (60 x 60)cm x deep 1/6 of pole length in 1:3:6 cement concrete 20 x 25 mm stone metal, 45cm x 45cm x 45cm/ 45cm dia. x 45cm height plinth duly plastered, with necessary curing and finishing complete. (for above 9m poles) |
| 130 | \"Supplying, erecting, testing & commisioning GI sheet 1.6mm (16 SWG) caution board of size 250 x 200 mm duly painted with red oxide and enamel paint in marathi and hindi erected at position for HV/EHV erecting with compliance to IS 2551-1982. as per specification no. CP/SH/CR \" |
| 131 | Single Pole Cut point structure of 11 KV Line using 11 Mtr Long RSJ |
| 132 | \"Supplying and erecting rolled steel joist (girder) pole 152 x 152 mm (37.1 kg/m) with base plate in provided foundation as per specification no. OH PL/RSJ \" |
| 133 | P/E/C M.S.Channel of size 75 X 40 X 6 mm / 100 X 50 X 6 mm / M.S. Angle 50 X 50 X 6 mm |
| 134 | P/E/C Strain Hardware for Dog 0.1 or equ. AAAC |
| 135 | \"Supplying and erecting polymer disc type insulator 45KN with necessary hardware suitable for 11kV line, complete as per specification no. OH-INS/DI \" |
| 136 | Providing & erecting GI stay set for poles along with CC Foundation, including loop insulators at inaccessible height complete with anchor plate 150 x 150 x 6 mm straining screws GI stay wire 7/8 SWG GI stay rod 20 mm x 1.8 mtr length and pole clamps |
| 137 | Supplying, installing and testing pipe type earthing with 40mm. dia. G.l. pipe or 20 mm dia. G.I. Rod complete with all accessories of GI materials & recording the results as per specification no. EA-EP |
| 138 | \"Supplying and erecting barbed wire two ply with 12 SWG ply and 12 SWG barb with a gap between two bars of 75 mm. firmly fixed on provided angle supports with necessary materials complete. (6.044 meters/kg.). \" |
| 139 | \"Supplying, erecting, testing & commisioning GI sheet 1.6mm (16 SWG) caution board of size 250 x 200 mm duly painted with red oxide and enamel paint in marathi and hindi erected at position for HV/EHV erecting with compliance to IS 2551-1982. as per specification no. CP/SH/CR \" |
| 140 | Making Cement concrete foundation including excavation (60 x 60)cm x deep 1/6 of pole length in 1:3:6 cement concrete 20 x 25 mm stone metal, 45cm x 45cm x 45cm/ 45cm dia. x 45cm height plinth duly plastered, with necessary curing and finishing complete. (for above 9m poles) |
| 141 | 11 KV HT Feeder Pillar |
| 142 | P/E/C 11 KV HT Feeder Pillar 4 Way |
| 143 | 200 KVA 11/0.433 KV Pole Mounted Distribution Transformer |
| 144 | Supplying & erecting inline D. P. Structure for 11/0.415 kV, 200 kVA Transformer with R.S.J. Pole 2 Nos. of size 100 x 116 mm x 11 Mtr. Long with suitable Distribution Box of C.R.C.A. Sheet 16 SWG with 4 Pole MCCB 300 Amps as incomer & 6 Nos. 100 Amps Kitkat / MCCB for out going circuits. Transformer D.P. Structure includes the A. B. Switch 400 Amps, D.O. fuse Set & L.A. Set. 2 Nos of Top channel of size 100 mmx 50 mm for erection of A.B. Switch & 2 Nos. Base channel of size 100 mm x 50 mm for erecting Transformer Channel of size 75 x40 mm for erecting D.O. Fuse Set, L.A., A.B. Switch handle etc. Angle of size 50 x 50 x6 mm for erecting Distribution Box , Transformer Belt etc.as per drawing (min. 124 Kg. iron work ) with necessary clamps, Nut-bolts. V cross arm, top clip, insulators etc. complete with caution board & barbed wire. D.P. Structure shall be erected in c.c. foundation complete. |
| 145 | Supplying, installing, testing & commissioning 3 phase, 11/0.433 kV, 50 Hz., 200 kVA, Mineral oil immersed and naturally cooled outdoor type, aluminium wound Non-sealed transformer, delta/star connected with additional neutral brought out on load side, temperature rise should not exceed 45? by thermometer in oil and 50 ? by the resistance method in winding at full load rating, using type A winding insulation (kraft paper) with HV tapping (with off load tap changer)off load +2.5 to -5 in steps of 2.5%, having 4 number of tap positions, with standard accessories complete with test ertificate with losses below 780 Watts at 50% load, 2300 Watts at 100% load as per IS:1180 (part 1) : 2014 , with necessary permissions of Electrical Inspector, as per specification no SS- TR-NSL. |
| 146 | Supplying, installing and testing pipe type earthing with 40mm. dia. G.l. pipe or 20 mm dia. G.I. Rod complete with all accessories of GI materials & recording the results as per specification no. EA-EP |
| 147 | Providing & erecting GI stay set for poles along with CC Foundation, including loop insulators at inaccessible height complete with anchor plate 150 x 150 x 6 mm straining screws GI stay wire 7/8 SWG GI stay rod 20 mm x 1.8 mtr length and pole clamps |
| 148 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 185 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 149 | Making Cement concrete foundation including excavation (60 x 60)cm x deep 1/6 of pole length in 1:3:6 cement concrete 20 x 25 mm stone metal, 45cm x 45cm x 45cm/ 45cm dia. x 45cm height plinth duly plastered, with necessary curing and finishing complete. (for above 9m poles) |
| 150 | Providing Erecting & commissioning DTC metering With Box single Core LT XLPE Cable as required for 200 KVA DP |
| 151 | 100 KVA 11/0.433 KV Pole Mounted Distribution Transformer |
| 152 | Supplying & erecting inline D. P. Structure for 11/0.415 kV, 100 kVA Transformer with R.S.J. Pole 2 Nos. of size 100 x 116 mm x 11 Mtr. Long with suitable Distribution Box of C.R.C.A. Sheet 16 SWG with 4 Pole MCCB 200 Amps as incomer & 6 Nos. 100 Amps Kitkat / MCCB for out going circuits. Transformer D.P. Structure includes the A. B. Switch 200 Amps, D.O. fuse Set & L.A. Set. 2 Nos. of Top channel of size 100 mmx 50 mm for erection of A.B. Switch & 2 Nos. Base channel of size 100 mm x 50 mm for erecting Transformer Channel of size 75 x40 mm for erecting D.O. Fuse Set, L.A., A.B. Switch handle etc. Angle of size 50 x 50 x6 mm for erecting Distribution Box , Transformer Belt etc.as per drawing (min. 124 Kg. iron work ) with necessary clamps, Nut-bolts. V cross arm, top clip, insulators etc. complete with caution board & barbed wire, D.P. Structure shall be erected in c.c. foundation complete |
| 153 | Supplying, installing, testing & commissioning of 3 phase, 11/0.433 kV, 50 Hz., 100 kVA, Mineral oil immersed and naturally cooled outdoor type, aluminium wound Non-sealed transformer, delta/star connected with additional neutral brought out on load side, temperature rise should not exceed 40? by thermometer in oil and 45? by the resistance method in winding at full load rating, using type A winding insulation (kraft paper) , with standard accessories complete with test certificate with losses below 475 Watts at 50% load, 1650 Watts at 100% load as per IS:1180 (part 1) : 2014, with necessary permissions of Electrical Inspector, as per specification no SS- TR-NSL. |
| 154 | Supplying, installing and testing pipe type earthing with 40mm. dia. G.l. pipe or 20 mm dia. G.I. Rod complete with all accessories of GI materials & recording the results as per specification no. EA-EP |
| 155 | Providing & erecting GI stay set for poles along with CC Foundation, including loop insulators at inaccessible height complete with anchor plate 150 x 150 x 6 mm straining screws GI stay wire 7/8 SWG GI stay rod 20 mm x 1.8 mtr length and pole clamps |
| 156 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 120 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 157 | Making Cement concrete foundation including excavation (60 x 60)cm x deep 1/6 of pole length in 1:3:6 cement concrete 20 x 25 mm stone metal, 45cm x 45cm x 45cm/ 45cm dia. x 45cm height plinth duly plastered, with necessary curing and finishing complete. (for above 9m poles) |
| 158 | Providing Erecting & commissioning DTC metering With Box single Core LT XLPE Cable as required for 100 KVA DP |
| 159 | LT Cables (Aluminum) (CB-LT/AL) |
| 160 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable, 1100 V 3½ core 120 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL |
| 161 | Mini Feeder Pillar (SW-MFP)/ Street Light Control Panel (SW-STCP) |
| 162 | Supplying and erecting mini feeder pillar with 415V, 315-320A FPMCCB as incomer and 3 outgoing circuits with HRC fuse base and cartridge of 100A aluminium bus bar erected in 14 SWG CRCA sheet box with supporting angles, self locks, gasket and enclosure must be dust proof, rust proof, vermin and water resistant, having slanting top and erected on angle iron/ GI frame in provided C.C. foundation complete as per specification no. SW-MFP. |
| 163 | Horizontal boring by push through method for laying 33 kV U/G cable / 11 KV U/G Cable |
| 164 | Providing structural steel work in single stanchions composed of R.S.J. Channel etc. with caps, bases, mild steel plated, angle brackets, cleats, gusset plates, anchor bolts etc. as per detailed designs and drawings or as directed including cutting, fabrication, hoisting, erecting fixing in position, making riveted/ bolted/ welded connection and one coat of anticorrosive paint and over it two. coats of oil painting approved quality and shade etc. complete. |