Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 29-10-2025 | Corrigendum | Date | 06-11-2025 |
| Sl. No. | Item Description |
| 1 | Excavation in foundations in Ordinary Soil (Loam Clay or sand) including lift upto 1.5m. (5 fts.) and lead upto 30 m. (100 fts.) & including filling, watering and ramming of excavated Earth into the trenches or into the Space between the building and sides of foundation trenches or into the space between the building and the sides of foundation trenches or into the plinth and removal and disposal of surplus earth as directed by the engineer-incharges upto a distance of 30m. (100fts.) from the foundation trenches. |
| 2 | Same as in item No. 251 above but excavation in soil mixed with Moorum,, shingle kanker etc, requiring the use of special T&P such as pickaxes : sabbals etc. |
| 3 | Add to item 251 for every additional 30m. (100 fts.) lead or part of 30m. (100 fts.) or for every additional 1.5 m. (5fts.) lift or part of 1.5m. (5fts.). |
| 4 | Providing and laying Cement concrete with 4cm gauge approved stone ballast, approved coarse sand and cement in the proportion of 1:4:8 (1 cement ; 4 Coarse sand : 8 graded Stone Ballast 40mm. Nominal size.) including supply of all materials, labour and T & P etc. required for proper completion of the work. |
| 5 | Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footings, bases of columns, etc. for mass concrete |
| 6 | Centering and shuttering including strutting, propping etc. and removal of form for : Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. |
| 7 | Centering and shuttering including strutting, propping etc. and removal of form for : Suspended floors, roofs, landings, balconies and access platform |
| 8 | Centering and shuttering including strutting, propping etc. and removal of form for : Lintels, beams, plinth beams, girders, bressumers and cantilevers |
| 9 | Centering and shuttering including strutting, propping etc. and removal of form for : Columns, Pillars, Piers, Abutments, Posts and Struts |
| 10 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level and above plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more |
| 11 | Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge. (Note :- Cement content considered in this item is @ 330 kg/cum. Excess/ less cement used as per design mix is payable/recoverable separately). All works upto plinth level |
| 12 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. |
| 13 | Providing and laying Ceramic glazed floor tiles 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in all colours, shades, except White, Ivory, Grey, Fume Red Brown laid on 20mm thick bed of Cement Mortar 1:4 (1 Cement : 4 Coarse sand) including pointing the joints with white cement and matching pigments etc., complete. |
| 14 | Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : 25 mm thick |
| 15 | 12 mm cement plaster of mix : 1:4 (1 cement: 3 Coarse sand) |
| 16 | 6 mm cement plaster of mix : 1:3 (1 cement : 3 fine sand) |
| 17 | Disternpeng (first coat) with oil bound distemper of approved brand and manufacture and the required shade on undecorated wall surface to give an even shade over and including a priming coatwith cement primer of approved brand manufacture such as Berger, .J&N, Shalimar, Asian Paint after thoroughly brushing the surface free from mortar dropping and other foreign rnatters and also lncluctillg the surface even with plaster of Paris or approved synthetic materials and sand papered smooth including supply of all materials, labour, Tools & plants etc. required for proper completion of the work, |
| 18 | Granular Sub-Base with Close Graded Material (Table :- 400-1) (B) By Mix in Place Method, Construction of granular sub-base by providing close graded material, spreading in uniform layers with motor grader on prepared surface, mixing by mix in place method with front end loader at OMC, and compacting with vibratory roller to achieve the desired density, complet as per clause 401 |
| 19 | Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels /subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same fromnnegative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of selfhealing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product performance shall carry guarantee for 10 years against any leakage. For vertical surface two coats @0.70 kg per sqm |
| 20 | Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels /subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of selfhealing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product performance shall carry guarantee for 10 years against any leakage. For horizontal surface one coat @1.10 kg per sqm |
| 21 | ACP Cladding Designing, fabricating, testing, installing and fixing in position Curtain Wall with Aluminium Composite Panel Cladding, with open grooves for linear as well as curvilinear portions of the building , for all heights andall levels etc. including: (a) Structural analysis & design and preparation of shop drawings for pressure equalisation or rain screen principle as required, proper drainage of water to make it watertight including checking of all the structural and functional design.(b) Providing, fabricating and supplying and fixing panels of aluminium composite panel cladding in pan shape in metalic colour of approved shades made out of 4mm thick aluminium composite panel material consisting of 3mm thick FR grade mineral core sandwiched between two Aluminium sheets (each 0.5mm thick). The aluminium composite panel cladding sheet shall be coil coated, with Kynar 500 based PVDF/ Lumiflon based fluoropolymer resin coating of approved colour and shade on face # 1 and polymer (Service) coating on face # 2 as specified using stainless steel screws, nuts, bolts, washers, cleats, weather silicone sealant, backer rods etc. |
| 22 | (c) The fastening brackets of Aluminium alloy 6005 T5 / MS with Hot Dip Galvanised with serrations and serrated washers to arrest the wind load movement, fasteners, SS 316 Pins and anchor bolts of approved make in SS 316, Nylon separators to prevent bi-metallic contacts all complete required to perform as per specification and drawing The item includes cost of all material & labour component, the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working curtain wall with aluminium composite panel cladding, cleaning and protection of the curtain wall with aluminium composite panel cladding till the handing over of the building for occupation. Base frame work for ACP cladding is payable under the relevant aluminium item.s The Contractor shall provide curtain wall with aluminium composite panel cladding, having all the performance characteristics all complete , as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer-in-Charge. However, for the purpose of payment, only the actual area on the external face of the curtain wall with Aluminum Composite Panel Cladding (including width of groove) shall be measured in sqm. up to two decimal places. |
| 23 | Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+ 0.05 %) total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. |
| 24 | Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. Hot finished welded type tubes |
| 25 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. . .DSR 2018 1.1.3 |
| 26 | Group C |
| 27 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. .DSR 2018 1.3.3 |
| 28 | Group C |
| 29 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. DSR 2018 1.7 |
| 30 | 2x1.5sq mm + 1x1.5 sq mm earth wire |
| 31 | 2x2.5sq mm + 1x2.5 sq mm earth wire |
| 32 | 2x6 sq mm + 1x6 sq mm earth wire |
| 33 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. DSR 2018 1.17.3 |
| 34 | 3 x 1.5 sq. mm |
| 35 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. DSR 2018 1.31 |
| 36 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. DSR 2018 1.32 |
| 37 | SUB HEAD - II : MV DISTRIBUTION BOARDS Providing and fixing following rating and breaking capacity and 4 pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panels board including drilling holes in cubicle panel , marking connections etc as required. DSR 2018 |
| 38 | 125A, 36KA FPMCCB DSR 2018 1623 |
| 39 | 250A, 50KA,FPMCCB DSR 2018 1626 |
| 40 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) DSR 2018 2.4 |
| 41 | 6 way (4 + 18), Double door |
| 42 | 8 way (4 + 24), Double door |
| 43 | Supplying and finishing 5 amps to 32 amps rating, 240 volts \"C\"series, miniature circuit breaker suitable for inductive and other loads of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.DSR 2018 2.10 |
| 44 | Single pole |
| 45 | Triple pole |
| 46 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. DSR 2018 2.15 |
| 47 | 40 A |
| 48 | Supplying and fixing single pole blanking plate in the existingMCB DB complete etc. as required. DSR 2018 2.11 |
| 49 | SUB HEAD - III : CABLES & CABLE TRAYS Supplying and making outdoor end termination with cast resin compound including aluminium lugs and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. DSR 2018 9.2 |
| 50 | 3½ C x 300 Sqmm |
| 51 | 3½ C x 240 Sqmm |
| 52 | 3½ C x 150 Sqmm |
| 53 | 3½ C x 70 Sqmm |
| 54 | 3½ C X 50 sq.mm |
| 55 | 3½ C X 25 sq.mm |
| 56 | 3CX 16 sq. mm |
| 57 | 2C X 16 sq. mm |
| 58 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. DSR 2018 7.1 |
| 59 | Above 185 sq. mm and upto 400 sq. mm |
| 60 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.DSR 2018 |
| 61 | Upto 35 sq. mm (clamped with 1mm thick saddle) DSR 2018 7.7.1 |
| 62 | Above35 sq. mm and up to 150 sq.mm (clamped with 25x3 mm MS Flat clamp)DSR 20187.7.2 |
| 63 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed/ XLPE aluminium conductor cable of 1.1 kV grade as required. DSR 2018 9.1 |
| 64 | 3½ C x 300 Sqmm |
| 65 | 3½ C x 240 Sqmm |
| 66 | 3½ C x 150 Sqmm |
| 67 | 3½ C x 70 Sqmm |
| 68 | 3½ C X 50 sq.mm |
| 69 | 3½ C X 25 sq.mm |
| 70 | 3CX 16 sq. mm |
| 71 | 2C X 6 sq. mm |
| 72 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays Cross Member with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. . DSR 2018 4.4 |
| 73 | 150 mm width x 50 mm depth x 1.6 mm thickness |
| 74 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 75 | SUB HEAD - IV : MV PANELSDesign, manufacture, supply, installation, testing and commissioning of following Utility panels suitable for 415 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 2mm thick CRCA sheet steel for Load bearing members and 1.6 mm thick for non-load bearing members, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber (form-3b Construction). The panel shall be complete with name plate, earthing, numbering, danger plate etc. as required and as per specifications and drawings. The panel shall withstand the fault level of as indicated elsewhere or shown in Single Line Diagrams. |
| 76 | Important Notes: Common for all Switchboard: |
| 77 | The BOQ shall be read inconjunction with general notes, specification and Single Line Diagram (attached for Ref.). Incase of any discrepancy between specification, BOQ and SLD, the same shall be brought to the notice of Client/Consultant before quoting the rates, otherwise stringent condition shall be deemed to have been considered. |
| 78 | Fault current wherever mentioned shall be Ics value. (Ics = 100% Icu). |
| 79 | All MCCB shall be provided with door interlocked rotary handle with ON/TRIP/OFF position indicator, continious variable thermal magnetic O/C and S/C releases. The MCCB above 250A rating shall be provided with microprocessor based releases. |
| 80 | Incoming MCCBs shall be provided with O/C, selective S/C, Instentaneous short circuit protection releases. |
| 81 | Outgoing MCCBs shall be provided with O/C, and selective short circuit protection. |
| 82 | All feeder doors shall have pad locking arrangement. |
| 83 | All TP feeders shall have solid isolable neutral link. |
| 84 | All MCCB used in starter feeder shall be suitable for motor duty application. |
| 85 | All power contactors including NIC shall be of AC3 duty. |
| 86 | Panel shall be powder coated of approved shade with minimum 60 micron thickness. |
| 87 | Size of Voltmeter / Ammeter for incomer also, 96mm x 96mm flush mounted with shrouded terminal shall be used in the panel. |
| 88 | Bus bar chamber shall be kept at top of the all panels. |
| 89 | All bus bar shall be insulated with coloured PVC Sleeve i.e.RYB, BK as per colour code. |
| 90 | Internal wiring of panel shall be with size 2.5sqmm Flexible Copper Conductor for CT circuit and control wiring with 1.5 sqmm. |
| 91 | All indicating light shall be LED type . |
| 92 | Each vertical section of floor mounted panel shall have independent base frame (75mm x 40mm) size made out of3 mm sheet steel (LT Panel & DG Panel). |
| 93 | All the makes shall be as per approved make list only. |
| 94 | Wherever only voltmeter & ammeter are required, the same may be provided in combined meter suitable for both parameter. |
| 95 | Space heater shall be provided in each cable alley. |
| 96 | All links/drops for ACB/MCCB shall be designed for full rated current of ACB/MCCB rating at same current density of Main Bus Bar. |
| 97 | All switchgear used in starter feeder shall be type-2co-ordinated. Vendor is required to submit manufacturer\"s type-2 co-ordination chart for the make used. |
| 98 | Arch flase Protection shall be in Cable allay & busbar Chember. |
| 99 | Fault rating of RCCB shall be equal to the fault rating of MCBs. |
| 100 | Necessary Co-ordination shall be done by the Panel Manufacturer / Vendor with the vendor of \"Gas flooding system\" for fire protection, for making suitable provisions in the panels, at the Design stage, Manufacturing stage, stage of testing at works & stage of commissioning at site. |
| 101 | Main Panel:- |
| 102 | Location : ELECTRICAL ROOM |
| 103 | Incomer 1: From Transformer (100kVA) |
| 104 | 1No. 160A ,50kA, 4P EDO/ motorised typewith inbuilt Micro Processor based releases, with 3 Nos. Class-1 Cast resin metering CT\"s of suitable ratio & burden, ON/OFF/Trip LED indications (110V AC) MCCB |
| 105 | Protection: |
| 106 | In built micro processor based releases (O/C, S/C & E/F). |
| 107 | Incomer 2: From DG (100kVA) |
| 108 | 1No. 160A ,36kA, 4P EDO/ motorised typewith inbuilt Micro Processor based releases, with 3 Nos. Class-1 Cast resin metering CT\"s of suitable ratio & burden, ON/OFF/Trip LED indications (110V AC) MCCB |
| 109 | Protection: |
| 110 | In built micro processor based releases (O/C, S/C & E/F). |
| 111 | Metering & Indications |
| 112 | R, Y, B LED indications (110V) |
| 113 | ON, OFF, TRIP LED indications (110V AC) |
| 114 | Trip circuit healthy indications (110V AC) |
| 115 | 3 Nos. cast resin class 1 metering CT\"s of adequate burden & ratio. |
| 116 | Multi functional meter(110V AC) |
| 117 | Microprocessor Based 6 Window annunciator with in built test, accept, reset push buttons. |
| 118 | Bus Bars: |
| 119 | 200A, 4P, Aluminium bus bars of electrolytic grade with Heat shrinkable sleeves 35kA. |
| 120 | Bus Coupler: |
| 121 | 200A 4P MCCB motorised type with Inbuit prot.O/C,S/C,E/F 20kA |
| 122 | Out goings: |
| 123 | 1No. 100A 25kA, 4P MCCB withthermal magnetic based releases, with 3 Nos. Class-1 Cast resin metering CT\"s of suitable ratio & burden, ON/OFF/Trip LED indications (110V AC) with Capacitor bank30 kVAR Capacitor Bank. |
| 124 | 1Nos. 100A 35kA, 4P MCCB withthermal magnetic based releases, with 3 Nos. Class-1 Cast resin metering CT\"s of suitable ratio & burden, ON/OFF/Trip LED indications (110V AC). FEEDER PILLAR |
| 125 | 4No. 63A 18kA, 4P MCCB withthermal magnetic based releases, with 3 Nos. Class-1 Cast resin metering CT\"s of suitable ratio & burden, ON/OFF/Trip LED indications (110V AC) |
| 126 | 1No. 63A 10kA, 4P MCB withthermal magnetic based releases, with 3 Nos. Class-1 Cast resin metering CT\"s of suitable ratio & burden, ON/OFF/Trip LED indications (110V AC) |
| 127 | 3No. 32A 10kA, 4P MCB withthermal magnetic based releases, with 3 Nos. Class-1 Cast resin metering CT\"s of suitable ratio & burden, ON/OFF/Trip LED indications (110V AC) |
| 128 | 1No. 50A 10kA, 4P MCB withthermal magnetic based releases, with 3 Nos. Class-1 Cast resin metering CT\"s of suitable ratio & burden, ON/OFF/Trip LED indications (110V AC) |
| 129 | 2No. 25A 10kA, DP MCB withthermal magnetic based releases, with 2 Nos. Class-1 Cast resin metering CT\"s of suitable ratio & burden, ON/OFF/Trip LED indications (110V AC) |
| 130 | With digital ammeter with inbuilt selector switch with in all feeders |
| 131 | Main LT panel |
| 132 | UPS PANELDesign, manufacture, supply, installation, testing and commissioning of cubicle type panel fabricated out ofCRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ completewith aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid. |
| 133 | INCOMER:1 Nos 63 AMP FP MCB (Thru Bypass Switch 5 kva/10 kva UPS) |
| 134 | BUS BAR :100 AMP,415 Volts, 3 phase 50 HZ4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 06 sq mm / amp. |
| 135 | The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient temperature. |
| 136 | OUT GOINGS: |
| 137 | 1 No 40 AMP DP MCB |
| 138 | 1 No 40 AMP DP MCB |
| 139 | 1 No 40 AMP DP MCB |
| 140 | 1 No 40 AMP DP MCB |
| 141 | 2 No 40 AMP DP MCB |
| 142 | 2 No 40 AMP DP MCB |
| 143 | complete panel as above and complete |
| 144 | AMF PANEL (OUTDOOR TYPE)Supply Installation, testing and commissioning of AMF Panel fabricated out of 14 gauge CRCA sheet steel in cubicle compartmentised free standing floor mounted. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 Hz supply system. Lifting hooks shall also be provided in all panels. |
| 145 | Compatibility to BMS shall be provided. |
| 146 | Auto Start Panel for 100 KVA DG Set : |
| 147 | DG AMF panel for 100 KVA DG Set as described above. |
| 148 | SUB HEAD -V: LIGHTING FIXTURE & FAN Supply and fixing ofLED Tube Light with batten suitable for up to 1 X 22 watt LED tube light fittingincluding tube on Surface complete in all respect. PS No-1413CAT- AAA |
| 149 | Supply & Fixing of 40 Watt LED Surface Mountingweather proofLuminaire with PC Housing and opal finish cover confirming to IP 65 Complete in all respect. PS.No.1418(A)CAT-AAA |
| 150 | Supply & Fixing of 20 Watt LED Surface Mountingweather proof Luminaire with PC Housing and opal finish cover confirming to IP 65 Complete in all respect. PS.No.1418 |
| 151 | Supply and fixing ofLED Street light Fittinghaving die cast aluminium body and diffuser with driver set suitable for 52 watt to 72 Watt. Confirming to IP66Protection complete in all respect. PS.NO.1422CAT- AAA |
| 152 | Fabrication,supply & erection of following size flange mounted hot dip galvanized octagonal pole made of HT steel plate window with flash cover with full vertical window cover at appropriate height from the base plate on existing cement concrete padestal as required including supplying and fixing the window mounted sheet inside the window including providing and welding 3 nos GI strips 4mm thick of suitable length and having suitable for 25 sqmm conductor 4 nos & shorting link on DIN chanel icpdg and fixing DIN channel of suitable length, 6 amp SPMCB-C characteristic earth stud, cable support clamp suitable for upto 4x25 sqmm cable logo/Name of the manufacturer shall be embossed on the pole. Galvanization as per IS. 3 MTR height 3mm Thick, bottom dia of 130mm & top dia 70mm base plate of size 225x225x12 mm thick. |
| 153 | 6 mtr heigh |
| 154 | Fabrication supplying and fixing class B galvanized single overhang arm bracket made out of 250mm long galvanized top tube with cap & 250 mm long 32 mm dia galvanized pipe with tightening bolts complete as required. |
| 155 | Providing an dlaying in position M25 grade reinforced cement concrete foundation of size 450mm (L)x 450mm (W) and 1000 mm deep including excavation of earth, providing cutting, bending and placing in position, reinforcement of cold twisted bars of 12 mm dia 960 mm long ( Approx) - 8 nos and reinforcement of cold twisted bars of 8 mm dia 1400 mm ( approx)-6 nos ( with 150mm spacing) as required with supply and positioning of 4 nos of foundation bolts 16mm dia, 600 mm long J type including two numbers of template anchor plates of size 225mmx225mmx3mm and providing DWC HDPE for cable entry and exit as required for the pole |
| 156 | Supply of following sizes of ceiling fan without regulator complete with double ball bearing, motor,3 nos blades, 30 cm long downrod, canopy, shackle kit, safety rope, copper winding,Power factor not less than 0.9, Service Value (CMM/W) minimum 6.85 ,Air delivery minimum 215 CFM, 350 rpm ( tolerrance as per IS : 374;2019) THD not less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pinetc complete in all respect as required. |
| 157 | 1200 mm Sweep. |
| 158 | Supply of following sizes of fresh air Exhaust fan suitable for operation on single phase 230 Volt AC 50 Hz supply, ideal for mounting on glass & window / wood panels made of high quality engineering plastic complete with all fixing accessories as required. |
| 159 | 200 mm dia (1280 RPM) |
| 160 | SUB HEAD -VI: CCTV SYSTEMSupplying, installing, testing and commissioningof UL Listed ONVIF Compliant 16 channel Network Video Recorder with 2 SATA HDD Slots with storage of 8 TB storage , Recording Bandwidth up to 320 Mbps , Recording Resolution 8MP(4K) , 5MP ,3MP,2MP,1.3MP,1MP, Alram I/O 16 Ch Alarm in , 1Ch Alarm out , Ethernet RJ-45 (1000 Mbps) Make : IMPACT HONEYWEL / MATRIX / IMPULSE /CP PLUS |
| 161 | Supply, installation, testing and commissioning of 5 MP (2502 x 1944) Bulletcamera ,ONVIF profile S , G& T ,UL , CE , FCC Certified ,1/2.7” Progressive Scan CMOS ,2.7 mm to 13.5 mm motorized varifocal lens , Quad stream with each stream support H.265 compression simultaneously ,min illumination : Color 0.01lux @ F1.2(AGC ON) ; B/W 0 lux @ IR ON , Shutter speed :1 / 5s ~ 1 / 100,000 s ,WDR , Compression : H.265/H.265+/H.264/H.264+ .SD card supportupto 256GB, Cloud Storage , Alarm trigger - 1 input / 1 output, frame rate : Main stream should support 25 &30 fps@5MP, Net HDD, ROI Min. 8 Region, Two Way Audio, Hardware reset, Edge analytics : Face Detection, Customer Flow staistics, Heat Map, Human & Vehicle Detection, Pedestrian Intrusion Detection & Line cross Detection. Queue length detection, Regional population statistics, SOD-Stationaary Object Detection, Tempering detection, Rare Sound Detection, Defog, Motion Detection, License plate detection. Protocol:- TCP/IP, HTTP, DHCP,DNS, DDNS, RTP, RTSP,SMTP, NTP, UPnP, SNMP, HTTPS,FTP PPPOE, NFS/SMB/CIFS, P2P , In built IR LED , IR Distance upto 45 meters , IP 67,IK10,POE/12V DC. (5 years warranty) |
| 162 | Supply, installation, testing and commissioning of 5 megapixels resolution Network Dome Camera for ture HD quality images,2.7 mm to 13.5 mm varifocallens, True Day/Night (TDN) functionality for true color image, Motion Detection , Multi-Level Sensitivity Privacy Zones 4 Zones, Snapshot Support JPEG format Password Protection Support Charatcer Display Support (Channel/ date ) ONVIFYes, IR Illumination 45 M IR illuminations for clear image in low light conditions Wide Dynamic Range :120dB, In built Analytics, 3D noise reduction for sharper images and lower bandwidth use in low light, Certifications:FCC,CE,UL.IP66-rated enclosure to protect against dust and water damage ,ONVIF compliant complete in all respect.(5 years warranty) |
| 163 | Supply,installation, testing and commissioning of 6 TB AV HDD (HARDDISK) (5 years warranty) MAKE: SEGATE / WD / TOSIBA |
| 164 | Supply,installation, testing and commissioning of Client Machine with Intel Core i5, 8GB DDr3 PC 1333 Memory, 320GB HDD, Independent Nvidia/ATI Graphic Controller with 1GB Dedicated VRAM, Dual display, Gigabit Ethernet, DVD Drive, Windows Pro.(5 years warranty) MAKE: HP / DELL / LENOVO |
| 165 | Supply,installation, testing and commissioning of 42\" LED Screen with wiring & all accessories.(5 years warranty) MAKE: LG/ SAMSUNG/ SONY/ CROMA |
| 166 | Supply and drawing of UTP 4 pair 23 AWG CAT 6 LAN Cable in the existing surface/recessed steel/PVC conduit as required. 4 pair CAT6 Unshielded, Twisted Pair (U/UTP) Cable 305 mtr per Box. Blue/Orange/White/Green in colour conforming to the following standards like ANSI/TIA 568 C.2, EN50173, IEC 11801 2nd ED, frequency tested upto 700Mhz.. (5 years warranty). MAKE : D-LINK / BELDEN / AMP /COMMSCOPE |
| 167 | Supply and Fixing of following size of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 20mm dia (DSR 2018/1.21.1/P-5) MAKE : AKG / SHETAL / TMT |
| 168 | Supplying, installing, testing and commissioning of 24 port Cat 6 patch panels available with block of four equipped with tool less IO, Rack Mountable. 19\" Modular Patch Panel, loaded CAT6 U/UTP 24port LCS2 rack mountable to be compatible in 4nos of 6 X RJ 45 Tool less connector U/UTP unit in a block. (5 years warranty) MAKE : NETGEAR / D-LINK / AMP |
| 169 | SITC of 4 Feet: CAT6 UTP 23 AWG Patch Cord- 1 mtr- Factory crimped LCS2 Patch cord in Blue colour. (5 years warranty)`MAKE : NETGEAR / D-LINK / AMP |
| 170 | Supply, Installation, Testing & Commissioning of LC-Style Connectors/Pigtail. (5 years warranty) MAKE : NETGEAR / D-LINK / AMP |
| 171 | Supply, Installation, Testing & Commissioning of MM Patch Cord- LC/LC Duplex Cords- 1 mtrs (5 years warranty) MAKE : NETGEAR / D-LINK / AMP |
| 172 | Supply, Installation, Testing & Commissioning of 16 Ports 10/100/1000 Mbps PoE + 4 SFP Managed SmartPro L2 + Switch. (5 years warranty) MAKE : NETGEAR / D-LINK / ALCATEL |
| 173 | Supply, Installation, Testing & Commissioning of 1GBASE- SR SFP + Transceiver on MMF. (5 years warranty) |
| 174 | 12U Rack including all accessories as complete as required. |
| 175 | SUB HEAD -VII: LIGHTINING PROTECTION & EARTHINGProviding and fixing of lightning conductor finial, made of 25mm dia 300mm, long copper tube, having single prong at top, with 85mm dia 3mm thick copper base plate including holes etc. complete as required. |
| 176 | Providing and fixing G.I. tape 20mm x 3mm thick on parapet or surface of wall for lightning conductor as required. (For vertical run.) |
| 177 | Providing and fixing testing joint, made of 20mm x 3mm thick G.I. strip, 125mm long with 4 Nos. of G.I. bolts, nuts, check nuts and spring washers etc. complete as required. |
| 178 | Providing and laying G.I. tape, 32mm x 6mm thick, from earth electrode directly in ground as required. |
| 179 | EARTHINGSupply and burying of 600mm x 600mm x 6mm G.I. plate vertically for earthing with its top at least 3 metres below ground level complete with 20mm dia G.I. pipe and funnel for watering and one earthing lead of one no. 8to 10 SWG GI wire in 15mm dia G.I. pipe up to switch board (from appron to switch board the cost of G.I. pipe and G.I. wire will be extra) 30cm square C.I. frame with hinged cover masonry housing alternate layers of charcoal/coke and salt at least 150mm thick alround etc. as per directions of Engineer-in-charge complete in all respects as per drawing (This will apply for earthing of poles also). PsNo.-702 |
| 180 | Supply and burying of 600mm x 600mm x 3mm copper plate vertically for earthing with its top at least 3 metres below ground level complete with 20mm dia G.I. pipe and funnel for watering and one earthing lead of one no. 8 to 10 SWG copper wire in 15mm dia G.I. pipe up to switch board (from appron to switch board the cost ofG.I. pipe and copper wire will be extra) 30cm square C.I. frame with hinged cover masonry housing alternate layers of charcoal/coke and salt at least 150mm thick alround etc. complete in all respect.Ps.No-704 |
| 181 | Supply and fixing of horizontal air termination (roof conductor) of 25mm x 3mm copper strip, on G.I. clamps on surface complete in all respects as approved by Engineer-in-charge. Ps.No-711 |
| 182 | Supply and burring of Safe Earthing Electrode T-19, (Hot Dip Galvanized), Length up to 3000mm, outer Dia 50 mm inner Dia 25 mm, terminal Dia 12mm, outer GI pipe of 16 swg and inner GI pipe of 12 swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity and one earthing lead of 25mm x 3mm G.I. strip, upto switch board (from apron to switch board, the cost of G.I. strip will be extra) along with 30 cm square C.I. frame with hinged cover & masonry housing. Make: As approved in U.P. P.W.D., & C.P.R.I. Certified. Ps.No 725 B |
| 183 | SUB HEAD-VIII: DG SETS & ALLIEDSERVICESProviding, installation, testing & commissioning of silent type Diesel Generating set along with prime power rating of 250KVA, 415 Volts at 1500RPM, 0.8 lagging power factor at 415V suitable for 50Hz, 3 phase system consisting of the followings: |
| 184 | a) Diesel Engine: Diesel engine radiator cooled, electric start of suitable BHP at 1500RPM suitable for above utput of alternator capable of taking 10% overload for one hour after 12 hours of continuous operation. The engine will be fitted complete with all the required accessories. |
| 185 | b) Suitable engine mounted instrument panel |
| 186 | c) Alternator: Synchronous alternator rated at 100KVA, 415V at 1500RPM, 3 phase 50Hz, AC supply with 0.8 lagging power factor. The alternator shall be brushless, continuous duty, self excited & self regulated. |
| 187 | d) base frame |
| 188 | e) Fuel tank: Daily service fuel tank of suitable capacity complete with all standard accessories as required. |
| 189 | f) Suitable exhaust system (as per environmental norms) |
| 190 | g) Electrical starting system |
| 191 | h) Accoustic & weather proof enclouser with arrangement fro fresh air intake for cooling the engine & alternator, extraction, discharging hot air in the atmosphere. |
| 192 | 100 KVA DG Set |
| 193 | Supply, laying of following sizes of MS Piping for Exhaust system as per IS: |
| 194 | 3589 and 1239 (part - I) including providing suitable flanges, reducers at suitable intervals, painting etc. as required as per drawings and specifications. |
| 195 | 125mm (NB) MS ERW pipe 4.85mm thick |
| 196 | Supply, of MS bends of above thickness same as above piping along with necessary hardwares ets.: |
| 197 | 125mm dia 90 deg bend |
| 198 | Supply,of 75mm thick Rockwool LRB mattress insulation (of 150 Kgs. Per cubic meter density) over the exhaust pipes of following diameter including cladding with aluminum sheet of 26 SWG and covering from outside complete as required suitable for DG exhaust pipe temp. upto 450OCetc. as per specifications (for horizontal pipes). |
| 199 | 125mm (NB) |
| 200 | Insulation of silencers for 100 KVA DG Set |
| 201 | Supplyof miscellaneous structural support for horizontal/ vertical exhaust piping including fabrication, hardwares and painting as per specifications. |
| 202 | Supply & Fixing of SS expansion joints for horizontal/ vertical exhaust pipes as required at site: |
| 203 | 125 mm exhaust SS Bellows(200mm long) |
| 204 | Control Cable: |
| 205 | Supplying, laying, installation, testing and commissioning of the following sizes of 1.1 KV grade PVC insulated and PVC sheathed copper conductor armoured stranded control cable conforming latest IS complete as required. |
| 206 | 10 Core x 2.5 Sq.mm Cable |
| 207 | Control Cables termination: |
| 208 | Supplying of all materials and making terminations ofcontrol cable terminations for control cables above item complete with singlebrass compression glands, copper lugs etc. as required. |
| 209 | 10 Core x 2.5 Sq.mm Cable |
| 210 | Enlosure for 630 amp MCCB |
| 211 | SITC OF BOOM BARRIER ENTRY AND EXIT WITH TICKET DISPENSING MACHINE AND KIOSAK MACHINE |
| 212 | SUB HEAD - XI: 10KVA UPSSupply of 10 kVA Online UPS, IGBT UPS(Transformer-less Design). |
| 213 | Supply of SMF Batteries (12Volt VRLA, 26 Ah, 40 Numbers or as per standard Nosto provide 30 Minutes Backup in total for 10 kVA UPS at 0.8PF and ECV=1.7V. |
| 214 | Fully rated Inbuilt static switch at the inverter output and 100% rated Inbuilt static switch at the static bypass line integrated in UPS module. |
| 215 | Supply of Local Accessories (like Cabling Between UPS and the Battery onsidering Cable Routing ,Battery Interlinks ,Battery Rack etc). |
| 216 | Backfeed protection at Mains & Bypass(Inbuilt / External). |
| 217 | Installation and Commissioning of 10 kVA UPS, Battery and Accessories. |
| 218 | Supply , installation , testing and commissioning 63A FP MCB of10kA breaking Capacity in metal sheet enclosure with ON/OFF, TYB Indication lamps for Incoming of UPSComplete in All Respect as Required. |
| 219 | SUB HEAD - XII : SOLARPANELProvide the required materials, equipment\"s, tools, machines and skilled labours for Providing and installing a Photovoltaic Solar Power system, Off grid Complete Set of Production Capacity as belowVoltage Range 230Vac, Overload 200% during 60sec, Protection Class IP20/IP54, Built-in MPPT,Built-in Fuse Box, Monitoring & Data Storage and Operator Panel) consisting from Solar Panels, Solar Racks, Smart Invertors, Regulators, Connection Cables, Plugs & Sockets...etc as Main Power Sources that supply power during the day and night and according to the below item descriptions/specifications. All the provided below materials should be of Western Origin of approved quality by supervisor Engineer (Certificate of Origin and Quality should be provided). The System should always work on solar with stored energy from batteries. |
| 220 | Supply and Install Solar Panel, monoycrystalline PV Solar Modules 320 W(as per requirements), internationally certifiedto ISO, BS and UV standards with required certificates. |
| 221 | Supply and Install Multiplus 12/500 VA Inverter Charger 12 Vdc to 230 Vac |
| 222 | Supply and install SmartSolar MPPT 100/30 & 100/50 |
| 223 | Supply and install 300 ah gel type lead acid maintenance free battery |
| 224 | Solar charge controller |
| 225 | supply and install Secure Battery Storage Rack |
| 226 | Supply and install Combiner box, Solar AC Fuses |
| 227 | Supply and install Solar DC Fuses |
| 228 | Supply and install Cable Channels |
| 229 | supply and install 1.5 mm square 3core cable |
| 230 | supply and install socket outlet |
| 231 | Supply and install Steel Structure/Tower, Module Support Structure and steel foundation for Solar Panels of required high (according to the site requirements and supervisor Engineer instructions) for mounting the solar panels required to power the community and designed to BS5950. The structure will be made of square hollow galvanized steel with vandal proofing. The structure steel for the support of the PV module will be made of galvanized medium gauge square hollow sections and angle iron anchored to the roof |
| 232 | Supply and Install all required types & sizes of Electrical Cables with all connections between Solar Panels, Inverter, and batteries.Terminal Electrical Boxes. 4, 2 cores DC, Copper Earth Cables with all required accessories |
| 233 | Supply and Install AC protection panel & AC Cables from system cupboard to main panel |
| 234 | Installation, Test, Commissioning of the solar system.The work includes training of the a local electrician on the operation and maintenance of the solar system for 2 days minimum. |
| 235 | SUB HEAD-XV: SUBSTATION & HT PANELS Supply & installation of 100kVA continuous duty cycle, 11KV/0.433kv, 3 phase, 50Hz, oil type , Dyn-11 vector group, step down, outdoor type, copper wound, ONAN type transformer complete with Off Load Tap changer . Tap changing range shall be ±2.5%, ±5%, ±7.5% in steps of 2.5%.Transformer shall have cable box for 11kV XPLE cable on HT side and Cable box on medium voltage side. with G.O.D.O. swith with foundation as per requirements |
| 236 | 11KV HT PANEL |
| 237 | Supply, installation, testing & commissioning of HT PANEL |
| 238 | IP Rating : IP 42 |
| 239 | 1No. 200A .350MVA,18.5KA VCBwith HT & LT fuse as per requirements , ON/OFF/Trip LED indications (110V AC).and MFM with R-Y-B indicators |
| 240 | Protection: |
| 241 | In built micro processor based releases (O/C, S/C & E/F). |
| 242 | Metering & Indications |
| 243 | R, Y, B LED indications (110V) |
| 244 | ON, OFF, TRIP LED indications(110V AC). |
| 245 | 11 / √3 / 110V/ √3,50VAPT\"s, Cast Resin type, 3 Phase for metering & indications, suitable rated 6A, TP MPCB of the fault withstand capacity as of the panel on the primary side of PT & suitable rated 6A, TP MCB on the secondary side of PT. |
| 246 | HT Cable Termination Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : DSR 2018 10.5 |
| 247 | 120 sq. mm |
| 248 | Supplying,installation,testingandcommissioningof Electric driven Main Fire Pump suitablefor automatic operationandconsistingoffollowing,completeinall respects, as required : |
| 249 | Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. |
| 250 | Suitable HP Squirrel cage induction motor, TEFC, synchronousspeed1500RPM,suitableforoperation on415volts,3phase50Hz,ACsupplywithIP55 protectionforenclosure,horizontalfootmountedtype with Class-\"F\" insulation, conforming to IS-325. |
| 251 | M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. |
| 252 | Suitablecementconcretefoundationdulyplastered with anti vibration pads. |
| 253 | 2280 lpm at 70 m Head (For Hydrant & Sprinkler Pump) |
| 254 | Note: *The head of the pump is selected in a manner so as to give a minimum 3.5kgf/cm2 pressure at the highest/farthest point. |
| 255 | Supplying,installation,testingandcommissioningof diesel engine driven main fire pump suitable for automatic operation and consistingof following, completeinallrespects,asrequired:(DieselDrivenPump) |
| 256 | Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft,mechanical seal conforming to IS 1520. |
| 257 | SuitableHP,1500RPMwatercooledwithradiator, diesel engine conforming to relevant IS standard completewithautostartingmechanism,12/24volts electricstartingequipment,dieseltank,exhaustpipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. |
| 258 | M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. |
| 259 | Suitablecementconcretefoundationdulyplastered and with anti vibration pads. |
| 260 | 2280 lpm at 70 m Head |
| 261 | Note: *The head of the pump is selected in a manner so as to give a minimum 3.5kgf/cm2 pressure at the highest/farthest point. |
| 262 | Supplying,installation,testingandcommissioningof electricdrivenpressurisationpumpsuitablefor automaticoperationandconsistingoffollowing, complete in all respects, as required : (Jockey Pump) |
| 263 | Horizontaltype,multistage,centrifugalpumpofcast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520. |
| 264 | SuitableHPsquirellcageinductionmotorTEFCtype suitableforoperationon415volts,3phase50Hz AC supply with IP 55 class of protection for enclosure, horizontalfootmountedtypewithClass-\"F\"insulation,conforming to IS : 325. |
| 265 | M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. |
| 266 | Suitablecementconcretefoundationdulyplastered and with anti vibration pads. |
| 267 | 180 lpm at 70 m Head |
| 268 | Supplying,installation,testingandcommissioningof electric driven terrace pump suitable forautomatic operationandconsistingoffollowing,completeinall |
| 269 | respects, as required: (Terrace Pump) |
| 270 | (a)Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 |
| 271 | b)SuitableHPsquirellcageinductionmotorTEFCtype suitable for operation on 415 volts, 3 phase, 50 Hz, AC supplywithIP55classofprotectionforenclosure, horiziontalfootmountedtypewithClass-\"F\"insulation,conforming to IS-325. |
| 272 | (c)M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. |
| 273 | (d)Suitablecementconcretefoundationdulyplastered and with anti vibration pads. |
| 274 | 900 lpm at 35 m Head |
| 275 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. |
| 276 | Supplyingandfixingsingleheadedinternalhydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheelISI marked conformingtoIS5290(Type-A)withblank Gunmetal/Stainless Steel cap and chain as required : |
| 277 | Single headed Stainless steel |
| 278 | Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/StainlessSteel couplingand cast iron wheel, ISImarked,conformingtoIS5290(typeA)withblank Gunmetal/Stainless Steel cap and chain as required : |
| 279 | Single headed Stainless steel |
| 280 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter sizenozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : |
| 281 | Stainless Steel (Grade 304) |
| 282 | Providing & fixing of MS Hose cabinet outdoor type of size 0.90 Mx 0.60 Mx 0.50 M made of 2mm thick MS sheet with 6mm thick glazed glass doors i/c necessary locking arrangement suitable to accomodate 2nos 15m long hoses, one no branch pipe, etc. and mounted on wall or with raised brick platform. The cabinet shall be painted with redcolour shade No. 536 of IS: 5 externally & white internally complete in all respects for external hydrant and as per enclosed specification. |
| 283 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipewith63mmdiamaleandfemalecouplingsduly boundwithGIwire,rivetsetc.conformingtoIS636 (type-A) as required : |
| 284 | Stainless Steel (Grade 304) |
| 285 | Supplying andfixing first-aidHoseReelwithMS constructionspraypaintedinpostofficered, conformingtoIS884completewiththefollowingas required. |
| 286 | 20mmnominalinternaldiawaterhosethermoplastic (Textile reinforced) type -2 as per IS: 12585 |
| 287 | 20mmnominalinternaldiagunmetalglobevalve& nozzle. |
| 288 | Drum and brackets for fixing the equipmets on wall. |
| 289 | Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. |
| 290 | 40 m |
| 291 | Providing and fixing angle iron (40mmx40mmx5mm) door frame and S.S. sheet (2mm thick) cum glass shutter of size 2.1mtrx0.9mtr(N.S.) with 25mmx25mmx3mm angle frame all around and stiffened in between i/c hinges, handle, locking arrangement, painting with approved synthetic enamel paint i/c sign writing on glass at internal hydrant including providing & fixing S.S. sheet 2mm thick on remaining portion above door to close opening i/c painting etc. as required. Glass shall be 6 mm thick. |
| 292 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. |
| 293 | Constructing masonry Chamber 90x90x100 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design :With common burnt clay F.P.S.(non modular) bricks of class designation 7.00 |
| 294 | Supplyingandfixingoffirebrigadeconnectionof cast iron body with gun metal male instantaneous inlet couplingscompletewithcapandchainasreqd.for suitabledia MS pipe connectionconforming to IS 904 as required :4 way-150 mm dia M.S. Pipe |
| 295 | Providing and fixing fire brigade suction hose coupling (draw out connection) with nut for female coupling as per IS-902 complete with 150mm dia. Suction pipe and foot valve (to be connected to static tank) complete as required andas per enclosed specification. |
| 296 | Supplyingandfixingoffirebrigadeconnectionof cast iron body with gun metal male instantaneous inlet couplingscompletewithcapandchainasreqd.for suitabledia MS pipe connectionconforming to IS 904 as required : 2 way-100 mm dia M.S. Pipe |
| 297 | PIPES & VALVESProvidinglaying,testing&commissioningof\"C\"class heavydutyMSPipeconformingtoIS1239/3589i/c fittingslikeelbows,tees,flanges,tapers,nutsbolts, gasketsetc.ingroundincludingwelding,excavation& providingcementconcreteblocksassupports, anticorrosivetreatmentwithcoaltar/asphalttapeasper IS10221,refillingthetrenchetc.offollowingsizes complete as required. |
| 298 | 150mm dia. (for External) |
| 299 | 80mm dia. (for External) |
| 300 | Providing,laying,testing&commissioningof \"C\"class heavydutyMSpipeconformingtoIS3589/IS1239 includingWelding,fittingslikeelbows,tees,flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
| 301 | 250 mm dia (wall thickness 6.3 mm) |
| 302 | 200 mm dia (wall thickness 6.3 mm) |
| 303 | 150 mm dia. |
| 304 | 100 mm dia. |
| 305 | 80 mm dia. |
| 306 | 65 mm dia. |
| 307 | 50mmdia. |
| 308 | 40 mm dia. |
| 309 | 32 mm dia. |
| 310 | 25 mm dia. |
| 311 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI markedcompletewithnuts,bolts,washers,gaskets conforming to IS 13095 of following sizes as required : |
| 312 | 200mm dia. |
| 313 | 150mm dia. |
| 314 | 100mm dia. |
| 315 | 80mm dia. |
| 316 | 65mm dia. |
| 317 | Providing,installation,testingandcommissioningof non-returnvalveoffollowingsizesconfirmingtoIS: 5312 complete with rubber gasket, GI bolts, nuts,washers etc.as required : |
| 318 | 200 mm dia. |
| 319 | 150 mm dia. |
| 320 | 100 mm dia. |
| 321 | 80 mm dia. |
| 322 | Supplying,fixing,testing&commissioningofdouble flangedsluicevalveofratingPN1.6withnonrising spindle,bronze/gunmetalseat,ISImarkedcomplete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required : |
| 323 | 150mm dia. |
| 324 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) : |
| 325 | 25 mm nominal bore |
| 326 | Providing & fixing of 25mm dia. gunmetal air release valve with all fittings and forged ball valve on header complete as required and as per enclosed specification. |
| 327 | Providing,installation,testingandcommissioningof stainlesssteelY-strainerfabricatedoutof1.6mm thickstainlesssteel,Grade304,sheetwith3mmdia holes with stainless steel flange. |
| 328 | 150mm dia. |
| 329 | 80 mm dia. |
| 330 | Providing and fixing following size Pressure gauge (0-15 Kg/Cm2) complete with shut off valve duly calibrated before installation complete as required & as per enclosed specification.150mm dia. |
| 331 | Providing, fixing, testing & commissioning of MS air cushion tank on top of each riser fabricated from 6mm thick MS plate, 200 mm in diameter and 1.2 m in height with dished ends fabricated from 8mm thick MSplate with Air release valve with stop cock, flanged inlet connection and drain arrangement with 25mm dia valve, pressure gauge with gun metal stop cock complete with all accessories as required and conforming to IS 4736-1968. |
| 332 | Providing, fixing, testing & commissioning of installationcontrolvalveofcastironbody, brass/bronzeworking partscomprisingofwater motor alarm,bronzeseatclapper,clapperarmand hydraulicallydrivenmechanicalgongbelltosound continuousalarmwhenthewetriser/sprinklersystem activates,pressuregauges,emergencyreleases, strainer,pressureswitch,cockvalvecompletewith drainvalveandbypass,testcontrolbox,ballvalves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes asrequired : |
| 333 | 150mm dia. |
| 334 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valveontopandflangedconnectiontoriser,drain arrangementwith25mmdiagunmetalwheelvalve withrequiredaccessories,pressuregaugeand paintingwith synthetic enamel paint of approved shade as required. |
| 335 | Providing and fixing reinforced neoprene rubber vibration eliminators/expansion joints (to provide relief from stresses at pipe flanges) suitable for upto 20 kg/cm2 pressure, complete as perspecification. |
| 336 | 150mm dia. |
| 337 | 100mm dia. |
| 338 | 80mm dia. |
| 339 | AUTOMATIC SPRINKLER SYSTEMProviding, fixing, testing & commissioning of 15mm dia quartzoidbulbtypesprinklersofrating68degree centigrade with required accessories : |
| 340 | Pendent Sprinkler |
| 341 | Horizontal side wall sprinkler |
| 342 | Providing & fixing flow switch in following sizes M.S.pipe including connection etc as required. |
| 343 | 80 mm Dia |
| 344 | 65 mm Dia |
| 345 | Providing and fixing 25mm dia inspecting & testing assembly with S.S. isolation valve, S.S. sight glass byepass valve & connected to line drain complete in all respect as per standard practice of code including pressure gauges of approved make. |
| 346 | FIRE EXTINGUISHERSupply, installation, testing and commissioning ISI marked (IS:15683) Fire Extinguisher, Carbon-di-oxide type capacity 4.5 Kg. Flat base including valve, discharge hose of not less than 10 mm dia, 1M long and complete in all respects including initial fill with CO2 gas conforming to IS:307-1966 and wall suspension braket as required as per specifications. |
| 347 | Supply, installation, testing and commissioning ISI marked (IS:15683) portable fire extinguisher, water (gas pressure) type capacity 9 kg with gun metal cap and nozzle and complete in allrespectsincluding initial fill and wall suspension brackets as required as per specifications. |
| 348 | Supply, installation, testing and commissioning of 6kg ABC (Powder Type) Fire Extinguisher. Mild Steel Cylinders ISI marked fitted with pressure indicating gauge, internal tube, squeeze lever type valve fully charged with ABC 90 powder (Mono Ammonium Phosphate) pressured by Nitrogen complete in all respects including wall suspension bracket and conforming to IS:15683 as required as per specifications. |
| 349 | Mechanical Foam type Fire Extinguisher. In HP Mild Steel Cylinders ISI marked / approved fitted with pressure indicating gauge, internal tube, squeeze lever type valve fully charged complete in all respects including wall suspension bracket / trolley mounted and confoming to IS:910 50 Litres (trolley mounted) |
| 350 | CONTROL PANELSFabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet,compartmentalisedwithhingedlockabledoors, dustandverminproof,powdercoatedofapproved shade after 7 tank treatment process, cable alley, inter-connectionwithsuitablesizecopperconductor cable/solidcopper strip, havingswitchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitableformainfirepump,pressurisationpump& dieselpumpsetcompleteasperCPWDspecification withfollowingincomingandOutgoings,suitablefor operationon415V,3phase,50HzAcSupplywith enclosure protection class IP 42 as required : |
| 351 | Incomings |
| 352 | 300A, 50kA4 Pole MCCB, Ics=100% Icu Rating |
| 353 | Digital Voltmeter 0-500V with selector switch |
| 354 | Ammeter (0-800 A) with selector swtich & CTs etc. |
| 355 | LEDtypeRYBphaseindicatinglamps,ON,OFF,trip indicating lamps |
| 356 | Set of CopperBus Bar 400Amps |
| 357 | Outgoings |
| 358 | (Note:Alloutgoingfeedersforpumpsshouldhave digital Ammeter with selector switches,and LED typeON, OFF, trip indicating lamps) |
| 359 | Main Fire Pump |
| 360 | 120Amp,50kATPNMCCB,Ics=100%Icu,withfully automaticStar/Deltastartersuitablefor100hppump withoverloadprotection,currentsensingtypesingle phasepreventorcompletewithallacceessoriesand internalwiringrequiredforautomaticoperation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets |
| 361 | Jockey Pump 63 Amp, 50kA TPN MCCB, Ics=100% Icu, with Suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventorcompletewithallacceessoriesandinternal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation.- 2 sets |
| 362 | DIESEL ENGINE CONTROLControl for diesel engine comprising - |
| 363 | Automatic/Manualselctorswitch&3attemptsstarting device,timersandrelaysasrequired,pushbuttons,start/stop in manual mode |
| 364 | Indicatinglampforhigh/LowLub.Oilpressure,High Water Temp and Engine on indication |
| 365 | Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter |
| 366 | All standard relays and accessories for automatic operation of diesel engine |
| 367 | System Controller |
| 368 | Designing,Supply,Installation,Testingand commissioning of system controllertocontrol operation ofmainelectricfirepump,dieselpump,Pressurization pump,Terracepumpinsequenceasperspecification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification |
| 369 | Providing, fixing, testing and commissioning of control panel for Terrace Booster pumps .Incoming: MCCB 35A 1 set of Phase indicating lamps, 1 set of 35A Al bus bars, 1No Ammeter, 1No Voltmeter with phase selector switch Feeder for Booster Pumps - 1 No. 1 No. 32A TP MCCB without releases. DOL starter with over load relay, single phase preventor and indicating lamps with ON/OFF push buttons. 1 No. Automanual selector switch. Suitable for booster pumps |
| 370 | Planning, Design,Manufacturing, Supply, Installation, Testing and Commissioning of Multi Level 4 Level Over- Ground Puzzle type Car Parking System with ElectroMechanical Technology accommodating approx. 100 Nos. of Cars including 1 Year Defect Liability Period with suitable steel structure frame work as per technicalspecifications, scope of work and as per direction of E-I-C, with Car Carrying Capacity of atleast 2000 kg each and Car Dimension of 5000 mm length x 2000 mm width x 2000 mm height (SUV) in ground floor, 5000 mm length x 2000 mm width x 1800 mm height in 1st floor to top floor with average retrieval/parking time not more than 180 seconds. The Lifting speed shall be @ 3 Meter/Minutes (minimum) with lateral movement speed of 5 Mtr/Minutes (minimum) and having safety features as outlined in specifications. |
| 371 | Annual operation and Routine maintenance of complete multi level over- ground puzzle type Car Parking System having capacity of 100 Nos. Car Spaces after physical completion of MLCP work as per the scope of the work and specifications given in the tender documents. The Item includes cost of deployment of required no. of experienced manpower given in the Tender Document. Note 1. If there is any variation in no. of car spaces provided above & that as per actual execution of work at site, payment shall be made on pro rata basis. |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail