Tender For General Electrical Works At Jnisac-vv2 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm 3 Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.1.00 sq.mm 2 Run 4 Supply ,installation, testing and commissioning of 36W/40W LED square (2ft X 2ft) recessed fitting made of crca sheet of thickness 0.5mm, having efficacy not less than 110l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram lumilled/Nichea (UGR less than 19) 5 Supply ,installation, testing and commissioning of 15W/18W round/ square(1X1) recessed fitting made of diecast aluminium, having efficacy not less than 110l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram/lumilled/Nichea 6 Supplying, fixing, testing and commissioning of 1200 mm, 20 W LED tube light fitting of reputed make with the following minimum specifications: 1200 mm length, 20 W nominal system wattage ;Lumen output: not less than 2000 lumens (minimum efficacy 100lm/W);Input voltage: 220–240 V AC, 50 Hz ;Power factor (PF): 0.90 ;Total Harmonic Distortion (THD): 20% ;Color temperature (CCT): 3000 K / 4000 K / 5700 K (as specified):Color rendering index (CRI): 80 ; Driver: Electronic LED driver, high efficiency, inbuilt protection against surge, short circuit, and thermal overload 7 Supplying and fixing following piano type switch / socket on the existing switch box/ cover including connections etc. as required.5/6 amps switch 8 Supplying and fixing following piano type switch / socket on the existing switch box/ cover including connections etc. as required.3 pin 5/6 amp socket outlet 9 Supply, installation, testing and commissioning of 250 mm sweep Light Duty Exhaust fan in plastic body with self opening lowers working on 230V single phase A/C 10 Flood Lights 11 Supply Conveyance, installation, testing and commissioning of 200W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) 12 Dismantling the existing LED lights including Lowering down the Highmast lighting system of the of the highmast after dismantling the electrical connection and servicing of motor for lowering down mechanism. Dismantled LED lights should be moved to departmental store as per the instruction of Site Engineer. 13 SFU,HRC Fuses 14 Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.63 Amp TP & N 15 Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.125 Amp TP & N 16 Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, C curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole Isolator-63 A 17 Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, C curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole and netural 18 Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, C curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole 19 Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, C curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole and neutral 20 Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps 21 Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts C curve DP MCB complete with connections, testing and commissioning etc. as required. 22 Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32amps 415 volts C curve TP MCB complete with connections, testing and commissioning etc. as required.