| Sl. No. | Item Description |
| 1 | Supply, installation, testing and commissioning of power distribution panels as per the detailed specification. (Refer Sec. V Part A) |
| 2 | 415V Class - IV power distribution panel-1- HIRAM as per dwg no.IGC/T-1648/01 |
| 3 | 415V Class - IV power distribution panel-2- HIRAM as per dwg no.IGC/T-1648/02 |
| 4 | 63A 4P MCCB with enclosure & shunt trip, “ON,OFF,TRIP Indication |
| 5 | Supply, Installation, testing and commissioning of Cast-Resin Isolation Transformer with enclosure as per detailed specification. |
| 6 | Supply, Installation, testing and commissioning of 30 kVA, 433V/433V, AN isolation Transformer as per technical specification. (Refer Sec V Part E) |
| 7 | Supply, open installation, testing and commissioning of the following sizes of VTPN DBs with MCCB & MCB on MS frame work (MS frame will be measured separately) as per the scope of work. (Refer Sec VI, Clause No.15.1). |
| 8 | DB VTPN8 Way (8 Plus 24) IP 43 - IK 09 with 1No. 125A, 4 Pole DPX3 MCCB (for Incomer) and 8 Nos. 63A,3P MCB (for outgoing),Cat No:507747 or equivalent. The scope includes suply of 1 No. spare MCCB of same make and rating as per section V Part A) |
| 9 | Supply and Embedment of following sizes of flush mountingPOWDER COATEDTPN/SPN DB Enclosures with Double Doorand per Phase isolation DBs consisting of Phase, Neutral and Earth Bus and interconnecting wires etc. at suitable depth in brick work as per the detailed specification and as directed by the Engineer-in-charge.(Refer Sec VI, Clause No.15.2). |
| 10 | 12 WAY Cat No:DETPI012DD (Vertical) or equivalent make TPN TIER Per Phase Isolation (PPI) DB |
| 11 | Supply and Embedment of following sizes Cable end termination box at suitable depth in brick work as per the detailed specification and as directed by the Engineer-in-charge.(Refer Sec VI, Clause No.15.2.2). |
| 12 | TPN,12 way Cable end box, Cat No:DBTPI012CB or equivalent suitable for TPN, 12 way TPN TIER Per Phase Isolation Distribution Board Cat No:DBTPI012DD (Vertical) |
| 13 | Supply and Embedment of following sizes of flush mounting POWDER COATED TPN/SPN DB Enclosures with Double Door consisting of Phase, Neutral and Earth Bus and interconnecting wires etc. at suitable depth in brick work as per the detailed specification and as directed by the Engineer-in-charge .(Refer Sec VI, Clause No.15.2). |
| 14 | SPN, 12 Way Distribution Board with all accessories, cat No:507612 |
| 15 | Supply Installation testing and commissioning of the following MCB on Distribution Boards as per the detailed specification. (Refer Sec VI, Clause No.14.2). |
| 16 | 6-32 Amps SP MCB (Type-C) |
| 17 | 40-63Amps, FP MCB (TYPE-C) |
| 18 | 6-32 Amps DP MCB (TYPE-C) |
| 19 | Supply fixing testing and commissioning of the following RCBOs on Distribution Boards as per the detailed specification. (Refer Sec VI, Clause No.14.2). |
| 20 | RCBO DP 25A sensitivity 30mA TYPE AC, 2Module |
| 21 | RCBO DP 32A sensitivity 30mA TYPE AC, 2Module |
| 22 | Assembling, installation, testing and commissioning of MCB DB enclosure already embedded in the wall including supply of Engraved Circuit Identification Plate and Danger Board as per the detailed specification for the following size of MCB DBs. (Refer Sec VI, Clause No.15.3). |
| 23 | TPN, 12 Way Distribution Board |
| 24 | Wiring for lights / fans /sensors/ Timer /Power point with 1100V grade FRLS insulated copper conductor wires in existing concealed/ ExposedPVC / ERW / Flo-coated Metal conduitsas per the detailed scope of work, includingsupply of Wires, switches/ sockets, termination of copper wires at either end by crimping including supply of PVC Sleeves/Ferrules, Copper Crimping Lugs and connecting the wires to various switches, sockets, etc. including testing and commissioning as per the detailed specification.(Refer Sec VI, Clause No.18) |
| 25 | Wiring for Light/Sensor/Fan Points with 2 Runs of 1.5 Sq.mm copper wires for Phase & Neutral and 1 Run of 2.5 Sq.mm copper wire for Earth from MCB Distribution Board to Primary light/sensor/fan point through Control Switch Box including 6Amps modular switch. |
| 26 | Wiring for Power point with 3 Runs of 2.5 Sq.mm Copper wires for Phase & Neutral and Earth from MCB Distribution Board to Power point through Control Switch Box including 16A modular switch, 6/16 Amps combined shuttered type Socket and 6A modular switch & 3 pin, 6A shuttered type Socket, Modular Plate. |
| 27 | Wiring for Exhaust fan point up to 3Mtr height with 2 Runs of 1.5 Sq.mm Copper wires for Phase & Neutral and 1 Run of 2.5 Sq.mm Copper wire for Earth from MCB Distribution Board to Power point through Control Switch Box including supply of 3 pin 6A shuttered type Socket, 2Nos. 2 Modular plate and 1 No 6A modular switch. |
| 28 | Wiring for Power point with 3 Runs of 2.5 Sq.mm Copper wires for Phase & Neutral and Earth from MCB Distribution Board to Power point through Control Switch Box including supply of 16A modular switch, 6/16 Amps combined shuttered type Socket, 3Modular plate 1No. |
| 29 | Wiring for Power Points with 4 Runs of 6.0 Sq.mmCopper wires for Phase, Neutral and 2 Runs of 2.5 Sq.mm Copper wires for Earth from MCB Distribution Board to Three Phase Metal Clad Socket. |
| 30 | Wiring for Power Points with 2 Runs of 4.0 Sq.mm Copper wires for Phase, Neutral and 1 Run of 2.5 Sq.mm Copper wires for Earth from MCB Distribution Board to Single Phase Metal Clad Socket. |
| 31 | Wiring for Power point with 3 Runs of 2.5 Sq.mm Copper wires for Phase & Neutral and Earth from MCB Distribution Board to Power point through Control Switch Box |
| 32 | Wiring for lights / fans /sensors/ Power pointwith1100V grade FRLS insulated copper conductor wires in existing concealed/ ExposedPVC / ERW/Flo-coated Metal conduitsas per the detailed scope of work, includingsupply of Wires, switches/ sockets, termination of copper wires at either end by crimping including supply of PVC Sleeves/Ferrules, Copper Crimping Lugs and connecting the wires to various switches, sockets, etc. including testing and commissioning as per the detailed specification.(Refer Sec VI, Clause No.18) |
| 33 | Wiring for Light point with 2 Runs of 1.5 Sq.mm Copper wires for Phase & Neutral and 1 Run of 2.5Sq.mm Copper wire for Earth from Switch boxto switch box and further to Light point including 1 No 6A modular switch |
| 34 | Wiring for Light point with 2 Runs of 1.5 Sq.mm Copper wires for Phase & Neutral and 1 Run of 2.5 Sq.mm Copper wire for Earth from Light point toLight point /sensor/contactor |
| 35 | Wiring for Power point with 3 Runs of 2.5 Sq.mm Copper wires for Phase & Neutral andEarth fromControl Switch Box to control switch boxincluding 6A modular switch & 3 pin 6A, shuttered type Socket and 16A modular switch &6/16A combined shuttered type Socket, Modular plate |
| 36 | Wiring for Power point with 3 Runs of 2.5 Sq.mm Copper wires for Phase & Neutral and Earth from Control Switch Box to control switch box including supply of 16A modular switch, 3 pin 6/16 A combined shuttered type Socket, Modular plate. |
| 37 | Wiring with 1 Run of 1.5 Sq.mm Copper wire |
| 38 | Wiring with 1 Run of 2.5 Sq.mm Copper wire |
| 39 | Wiring with 1 Run of 4 Sq.mm Copper wire |
| 40 | Wiring for Power point with 3 Runs of 2.5 Sq.mm Copper wires for Phase & Neutral andEarth fromControl Switch Box to control switch box |
| 41 | Supply and fixing following Modular front cover plate on existing modular metal/plastic boxes etc. as required. (Refer Sec VI, Clause No.15.7). |
| 42 | One/Two module |
| 43 | 3Module |
| 44 | 4 Module |
| 45 | 6 Module |
| 46 | 1 Modular dummy plate |
| 47 | Supply and Installation of following sizes of Surface Mounting Plastic Boxes as per the detailed specification. (Refer Sec VI, Clause No.15.6). |
| 48 | Surface Mounting Plastic Boxes 1/2 Module |
| 49 | Surface Mounting Plastic Boxes 3 Module |
| 50 | Surface Mounting Plastic Boxes 6 Module |
| 51 | Supply,installation, testing and commissioning of 6A modular switch (cat no.573400)& 3 pin 6A, shuttered type Socket (cat no.573424)and 16A modular switch (cat no.573410) &6/16A combined shuttered type Socket (cat no.573471), 6 Modular plate (cat No.010996) the above switch sockes to be installed in existing DLP Trunking box with all fixing accessories as required as per site condition. Termination for switch and sockets by using wires is in the scope of work. Wiring for power point to be measured in seperate item.(Refer section V Part -A) |
| 52 | Supply, transportation, installation, testing and Commissioning of the following type of plastic trunking of size 105 x 80 mm (cat no.010422), 85mm PVC flexible cover (cat no.010522), joint for 85mm width cover(cat no.010802), base joint (cat no.010691), internal angle(cat no. 010602), external angle (cat no.010622) and flat angle (cat no.010785), end cap (cat no.010702) as required as per site condition.(Refer section V Part A) |
| 53 | Supply and Installation of following Wiring Accessories as per the detailed specification(Refer Sec VI (MNC), Clause No.5). |
| 54 | 1 No 6A Switch on modular plate and termination of wires to the switches |
| 55 | 1 No16A Switch on modular plate and termination of wires to the switches |
| 56 | 1 No 6A 3 Pin shuttered type Socket on modular plate and termination of wires to the switches |
| 57 | 1 No 6/16A 3 Pin combined shuttered type Socket on modular plate and termination of wires to the switches |
| 58 | Supply, transportation, installation, testing and commissioning of the following type of Recess mounted luminaires. (Refer Sec VI, Clause No.16.1).- Catalogue No : Spoon Zen Cat.No. SP 1772,36W, 6000k or equivalent and Lamp TypeLED |
| 59 | Supply, transportation, installation, testing and Commissioning of the following type of Surface mounted luminaires. (Refer Sec VI, Clause No.16.1).- Catalogue No : WAND K 9W 5700K Code- SLWKB00957NDWEP0002C01-2Feet Batten PRIMEor equivalent and Lamp Type LED |
| 60 | Supply, transportation, installation, testing and Commissioning of the following type of Surface mounted luminaires. (Refer Sec VI, Clause No.16.1).- Catalogue No : Moon V2 STD 18W 5700K Item code SLMOSO1857NDWEP or Equivalent and Lamp Type LED |
| 61 | Supply, transportation, installation, testing and Commissioning of the following types of Suspended luminaires. (Refer Sec VI, Clause No.16.1). - Catalogue No : CANE STD LINEAR PENDANT 40W, 5700K-4FTItem code LPC0104057NDWEP0DL4C01 with downrod replacement fixing accessories or Equivalent and Lamp Type LED |
| 62 | Supply, transportation, installation, testing and Commissioning of the following type of Surface mounted luminaires. (Refer Sec VI, Clause No.16.1).- Catalogue No : WAND K 30W 5700Kcode SLWKY03057NDWEP04C22 -SURFACE LIGHTS NONDIM WITH CUSTOMIZED CLAMP OF 30 DEG. TILT WHITE (PC) 4FEET- PRIME or equivalent and Lamp Type LED |
| 63 | Supply and external installation of following sizes ofHeavy Duty, Hot Dip Galvanised MS ERW Conduitsfor Electrical & Communication System with all the required accessories like round JBs, Solid Long Bends, Check Nuts, Nipples, Couplings, Reducers, Copper Clips, Copper Conductor, GI Wire etc. as per the detailed specification. .(Refer Sec VI, Clause No.27). |
| 64 | 25mm dia 1.8mm wall thickness Heavy Duty, Hot Dip Galvanised/ ERW Conduits with 50mm deep junction boxes. |
| 65 | 32mm dia 1.8mm wall thickness Heavy Duty, Hot Dip Galvanised/ ERW Conduits with 50mm deep junction boxes. |
| 66 | 25mm GI Flexible Hose |
| 67 | Supply and providing GI conduit downrod for installation of luminaries, fans etc as per the detailed specification.(Refer Sec VI, Clause No.16.5). |
| 68 | 20mm dia GI conduit |
| 69 | Supply and Installation of following sizes of PVC trunking (casing & capping) on walls/Ceiling for routing of Power, Lighting and Telephone wires including all the required accessories like JBs, Coupling, External & Internal Bends, Elbows and end cap as per the detailed specification.(Refer Sec VI, Clause No.29) |
| 70 | 20 X 12 mm size of PVC Mini trunking |
| 71 | 25 X 12 mm size of PVC Mini trunking |
| 72 | 32 X 12mm size of PVC Mini trunking |
| 73 | Supply and Installation of MS Brackets, Supports, Frame work, Clamps, Base Channels, etc. fabricated out of angle / Channel / Rods etc. The rate quoted shall include the cost of fabrication / welding, cleaning and painting/ galvanising as follows including supply of required, fasteners, nuts, washers, etc.(Refer Sec VI, Clause No.11). |
| 74 | MS fabrication 1 coat primer & 2 coats synthetic enamel paint |
| 75 | Supply Embedment Assembling testing and commissioning of following type Metra plug and socket DB and RCBO in sheet steel enclosure including chipping and finishing as per the detailed specification. (Refer Sec VI, Clause No.15.4). |
| 76 | 16A 2P+E-DP Metra plug and socket DB and 16A DP 30mA sensistivity RCBO |
| 77 | 32A 3P+N+E-FP Metra plug and socket DB and 32A FP 30mA sensistivityRCBO |
| 78 | Supply, installation, testing and commissioning of the following SDFU with factory made enclosure with 3Nos Fuse links on MS frame work as per the scope of work. (MS item will be measured separately).(Refer Sec VI, Clause No.14). |
| 79 | SDFU TPN 63A, DIN FUSES with 3Nos 63A HRC fuse links, Sheet steel enclosure FN Cat No:SK90484 |
| 80 | Supply, installation, testing and commissioning of the following SDFU with factory made enclosure with 3Nos Fuse links on MS frame work as per the scope of work. (MS item will be measured separately). (Refer Sec VI, Clause No.14.1). |
| 81 | SDFU TPN 125A, DIN FUSES with 3Nos 125A HRC fuse links, Open Execution FN Sheet steel enclosure FN Cat No:SK90486 |
| 82 | Loading, Transportation, Unloading at site, installation, Testing and Commissioning of1100 Volts Grade PVC/HRPVC/XLPE insulated, Stranded Aluminium/copper conductor cables of following sizes in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the detailed specification (Note: Cable will be issued free of cost by the department).(Refer Sec VI, Clause No.3) |
| 83 | 3/3.5/4core X Upto 25 sqmm |
| 84 | 3/3.5/4Core X above 25 & up to 120 sqmm |
| 85 | 3/3.5/4Core X above 120 & up to 240 sqmm |
| 86 | 3/3.5/4Core X above 240 & up to 400 sqmm |
| 87 | Supply, Loading, Transportation, Unloading at site, installation, Testing and Commissioning of 1100 Volts Grade following sizes of cables in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the detailed specification.(Refer Sec VI, Clause No.3) |
| 88 | 4C X 16 sqmm 1.1kV grade Copper conductor XLPE insulation flat wire armour FRLSH PVC outersheath |
| 89 | End Termination of the following sizes of Aluminium Conductor PVC Insulated and sheathed armoured UG Cable usingSingle Compression, Heavy Duty, Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Comet or equivalent make Aluminium crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland. (Refer Sec VI, Clause No.10.1). |
| 90 | 4 Core X 16 Sqmm |
| 91 | 3.5/4 C x 25 sq.mm |
| 92 | 3.5/4 C x 35 sq.mm |
| 93 | 3.5/4C x 50/70 sq.mm |
| 94 | 3.5 x 185 sq.mm |
| 95 | 3.5 x 400 sq.mm |
| 96 | End Termination of the following sizeCopper Conductor PVC/XLPE Insulated and FRLS sheathed armoured UG Cable usingSingle Compression, Heavy Duty,Siemens type Brass Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Copper crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland. (Refer Sec VI, Clause No.10.1). |
| 97 | 4C x 10 Sq.mm including cable gland earthing |
| 98 | 4C x 16 Sq.mm including cable gland earthing |
| 99 | Supply, installation, testing and commissioning of the following Raychem make Heat Shrinkable CableStraight Through Jointing Kits (Crimping type) for 3.5 Core Aluminium Conductor, 1.1 kV (E), PVC/XLPE insulated cables of following sizes as specified. Excavation will be measured separately (Refer Sec VI, Clause No.10.6). |
| 100 | Straight Through Joint (Crimping type)for 3.5 Core, 25- 50 Sq. mm |
| 101 | Straight Through Joint (Crimping type)for 3.5 Core, 70-95 Sq. mm |
| 102 | Straight Through Joint (Crimping type)for 3.5 Core 120- 185 Sq. mm |
| 103 | Straight Through Joint (Crimping type)for 3.5 Core x 400 Sq. mm |
| 104 | Retrieval of the existingone number PVC/HRPVC/XLPE insulated and PVC sheathed power cable of 1.1 KV grade of following sizes laid direct in ground includingRemoval of end termination, excavation of trenches, retrieving of bricks and back filling as per the detailed specification.(Refer Sec VI, Clause No.5) |
| 105 | 3/3.5/4 CoreAbove 240sqmm & upto 400 sqmm |
| 106 | Retrieval of the already laidone number1100 Volts Grade XLPE/HRPVC insulated, Stranded Aluminium conductor cables of following sizes in built-in trenches, on walls, poles and from embedded pipes including removal of end termination GI spacer, clamps etcas per the detailed specification. (Refer Sec VI, Clause No.5) |
| 107 | 3/3.5/4 Core upto 25 Sqmm |
| 108 | 3/3.5/4 Core Above 25 & Upto 120 Sqmm |
| 109 | 3/3.5/4 Core Above 240 & Upto 400 Sqmm |
| 110 | Relaying of one number 1100 Volts Grade PVC/HRPVC/XLPE insulated, Stranded Aluminium/copper conductor cables of following sizes in built-in trenches on walls, poles and through embedded pipes using the retrieved spacer & clamps as per the detailed specification. (Note: Cable will be supplied by department as free issue item) (Refer Sec VI, Clause No.6) |
| 111 | 3/3.5/4C X Upto25sqmm |
| 112 | 3/3.5/4 Core Above 25 & Upto 120 Sqmm |
| 113 | 3/3.5/4 Core Above 120 & Upto 240 Sqmm |
| 114 | Supply and fixing of powder coated MS Danger / warning Boards of different voltage levels as per the detailed specification. |
| 115 | Rod Earthing |
| 116 | Supply installation and testing of Maintenance free earthing system TRIPOLAR (3x10feetx5/8inch copper bonded steel rod, 55 kg Ground Enhancing Material (GEM) ) as per IS: 3043 including RCC Chamber and RCC cover as per Drawing No.IGC/ESD/5060/1008/1 enclosed . (Refer Sec VI, Clause No.12.12). |
| 117 | Supply, fabrication and installation of the following size of Copper Flats in Built in trenches on walls, poles, RCC Concrete and through embedded pipes as per the detailed specification. (Refer Sec VI, Clause No.12.7). |
| 118 | 25X3 mm Copper flat |
| 119 | Supply, fabrication and installation of the following size of Copper Flats including excavation and refilling as per the detailed specification. (Refer Sec VI, Clause No.12.7). |
| 120 | 25X3 mm Copper flat |
| 121 | Supply and installation of the following sizes of copper wires in built in trench as per the detailed specification.(Refer Sec VI, Clause No.12.8) |
| 122 | 8SWG copper wire |
| 123 | 14 SWG Copper Wire |
| 124 | Supply and installation of Following Sizes of Unsheathed flexible cables in Walls, Floors, Built in Trenches including supply of GI spacer and clamps, fixing fasteners etc as per detailed specification.(Refer Sec VI, Clause No.12.5). |
| 125 | 1100V Unsheathed Flexible Copper Conductor PVC cable size 1 Core x 35.00 Sq.mm |
| 126 | Supply and installation of Following Sizes of Unsheathed flexible cables indirect in ground including excavationrefilling the trench etc as per detailed specification.(Refer Sec VI, Clause No.12.5). |
| 127 | 1100V Unsheathed Flexible Copper Conductor PVC cable size 1 Core x 35.00 Sq.mm |
| 128 | End Termination of insulated Unsheathed flexible single core cables of the following sizes using copper crimping lugs. The rate shall include the cost of supply of copper crimping Lugs. (Refer Sec VI, Clause No.12.6). |
| 129 | 1100V grade 1C X 35 Sq.mm FRLS PVC unsheathed cable |
| 130 | Supply and Installation of Clean earth point. (Refer Sec VI, Clause No.12.11). |
| 131 | Supply and Installation of clean earth point with DMC insulator support and 200mm long 25X3mm Tinned copper flat as per the detailed specification. |
| 132 | Supply and open installation of following Sizes of MS boxes as per the detailed specification. (Refer Sec VI, Clause No.15.10). |
| 133 | 150(W)X150(H)X80(D)mm, 1.6mm thick sheet MS Box |
| 134 | 300(W)X300(H)X120(D)mm,1.8mm thick sheet MS Box |
| 135 | Supply and Installation of laminated Hylam sheet of 3mm thickness over the boxes and as per the detailed specification. |
| 136 | Plain Cement Concrete.(Refer Sec VI, Clause No.26) |
| 137 | 1:2:4 Plain Cement Concrete |
| 138 | Removal of the following from 415Volts switch boards (Refer Sec VI (MNC), Clause No.19). |
| 139 | 63A/100A/125A, 500V, TP/TPN/SFU/ Combination SFU or 4/6/8/12 Way SPN DB or 4/8 WAY TPN DBs |
| 140 | Removal, transportation and unloadingof 415V industrial type / Cubiclepanel from HIRAM building to storage yard including removal of Power cables connected with the panel. (Refer Sec V Part A) |
| 141 | Removal of 1.5 or 2.5 or 4 sq.mm aluminium wire from concealed/ ExposedPVC / ERW / Flo-coated Metal conduits on roof or wall conduitsas per the detailed scope of work.(Refer Sec V Part A) |
| 142 | Removal of light fixtures (Refer Sec VI (MNC), Clause No.21). |
| 143 | Removal of light fixtures in labs .(Refer Sec V Part A) |
| 144 | Removal of light fixtures,proper cleaning and Re-installation of the same light fixtures at the same location in labs and low bay area as directed by Engineer-in-charge.(Refer Sec V Part A) |
| 145 | Removal of MS box / switch box from the wall (Refer Sec VI (MNC), Clause No.19). |
| 146 | Removal of various sizes of GI/ PVC Conduit from wall/column/Beam and removed conduit transported to stores (Refer Sec VI (MNC), Clause No.19). |
| 147 | Supply, transportation, installation, Configuration, testing and commissioning of the following Sensors as directed by the Engineer-in-Charge. (Refer Sec VI, Clause No.16 and Section-V). |
| 148 | Surface/Recess mountable type Occupancy & day light PIR SWITCH CORRIDOR sensorsuitable for lighting load coverage 2mtr wide and 12mtr length on both sides. This scope also includes suply of 1 No. remote along with charger to operate the sensors(Refer Sec VI, Clause No.16.3). Make : Legrand, Model No. 488 17 |
| 149 | Maintenance of Earth Pits including supply of Sodium Bentonite, and measurement of Earth Pit Resistance as per the specification.(Refer Sec VI (MNC), Clause No.2). |
| 150 | Supply and replacing following earth pit chamber parts after removing and disposing off old/damaged part as per drawing No. IGC/ESD/5060/1008/1. |
| 151 | RCC ring with cover |
| 152 | Excavation in hard soil including refilling with excavated earth and disposing surplus earth at places as directed with in a lead of 10 Mtrs. and initial lift upto 1.5 Mtrs. including neat banking as per detailed specification. (Refer Sec VI, Clause No.2) |
| 153 | Supply, cleaning the floor, proper pasting and installation of following insulating mat as per specification. (Refer Sec VI, Clause No.25). |
| 154 | 2.0 mm thickness, Max useable voltage 3.3kV, AC Proof voltage 10kVfor 3 minutes, AC dielectric strength 30kVRMS Insulating Mat confirming to IS:15652 |
| 155 | Clearing light jungle area, bulb weeds, grass including removal all unwanted plants, branches, twigs, wild growth etc.complete, and disposing the same 100 meters away manually or burning them without disturbing other areas etc., complete all as directed by the Engineer-in-Charge. Contractor must inform the Engineer-in-charge and prior permission shall be obtained from him for burning the wild growth.(Refer Sec VI (MNC), Clause No.7.3). |
| 156 | Temporary installation of class IV panel as directed by Engineer-in-charge.(Refer Sec V Part A) |
| 157 | Temporary installation ofDB as directed by Engineer-in-charge.(Refer Sec V Part A) |
| 158 | Shifting of Electrical equipment of various sizes including loading and unloading/Shifting of electrical items from IGCAR and hand over to service centres (upto chennai limit) or vice versa.(Refer Sec VI (MNC), Clause No.31). |
| 159 | Equipment weighing more than 100 kgs and upto 1000 kgwithin a distance of 5km. Dismantaling and segregation is also included in the scope |
| 160 | Supply and Fixing of Powder coated MS Danger / Warning Boards of different Voltage levels as per the detailed specification. Make: Thadhani or equivalent. ( (Refer Sec V Part A ). |
| 161 | Supply and pasting of water proof stickers of 250 x 50 mm size with messages as directed by Engineer in charge as per the detailed specification. ( (Refer Sec V Part A ) |
| 162 | Civil Related work:-Removal of existing False ceiling including disposing, cleaning and depositing the debris with in a distance of 50 metres etc. as directed by Engineer.-in-charge. |
| 163 | Refixing of existing False ceiling including necessary fixtures such as bolt and nuts etc. for the completion of the work and as directed by the Engineer-in charge |
| 164 | Providing and applying painting One coat on at all levels withAcrylic emulsion paint (ACE or Equivalent approved brand, colour and manufacturer) to give an even shade including preparation of the surfaces, applying putty (putty for touch up to fill up crevices, mild depression etc.), scaffolding complete all as per specifications and as directed by the Engineer-in-Charge. |
| 165 | Providing and Fixing in position Suspended false ceiling system using 600 x 600mm Mineral Fibre Reinforced Factory applied Vinyl painted \"ARMSTRONG\" Ceiling tilesor approved equivalent make & pattern (as per Sec V Part C) |
| 166 | Providing and fixing Gypsum False ceiling Tiles, 600x600x9mm of Armstrong or approved equivalent make, pattern(as per Sec V Part C) |
| 167 | Providing and fixing false ceiling with 12.5mm thicktapered edge gypsum moisture resistant board at allheight including providing and fixing of frame work made of special sections, power pressed from M.S. sheets andgalvanized with zinc coating of 120gms/sqm (both side inclusive) (as per Sec V Part C) |
| 168 | Conveying the surplus excavated earth & debris, boulders and spoil by mechanical means and depositing at places inside DAE installation identified as Dumping yard as per requirement with a lead specified(as per Sec V Part C). |
| 169 | Lead charges for lead Exceeding 3 kilometre but not exceeding 4 kilometre |
| 170 | Telephone relatedwork: Loading, Transportation, Unloading at site, installation, Testing and Commissioning of one number of armoured PIJF 0.63mm dia Telephone cable of following sizes in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the detailed specification.(Note: Cable will be issued free of cost by the department). (Refer Sec VI, Clause No.3) |
| 171 | 20 Pairs 0.63mm PIJF telephone cable. |
| 172 | 50 Pairs 0.63mm PIJF telephone cable. |
| 173 | Supply, wiring and termination for Telephone point with 1 Run 0.6mm, twin twisted, 2 pair PVC telephone wires, tinned copper wire from Telephone Junction Box to Telephone points in concealed conduit/ PVC Trunking as instructed by EIC. (Ref. Sec V) |
| 174 | Supply and installation of two modular box with two modular plates suitable for fixing telephone socket of rebuted brand. (Section VI, Clause No.15.6 & 15.7) |
| 175 | Supply and Installation of RJ-11 socket 1 Gang with shutter for information outlet and termination of 1 Run of data Cable. (Ref. Sec V) |
| 176 | Supply & installation (Embedment in concealed) of wall mountable powder coated MS telephone distribution boxes of different sizes with SS KRONE Base module, Cable entry, lock and key provision. (Ref. Sec V). |
| 177 | 400(W)x300(H)x100(D), 2 mm thick sheet MS Box - (50L+50R =100 pair) |
| 178 | 500(W)x400(H)x150(D), 2 mm thick sheet MS Box-(100L+100R =200 pair) |
| 179 | Retrieval of the already laid one number Telephone cables of following sizes in built-in trenches, on walls, poles and from embedded pipes including removal of end termination, GI spacer, clamps etc as per the detailed specification. (Refer Sec VI, Clause No.5) |
| 180 | Upto 20 Pair |
| 181 | Above 20 Pair & upto 50 Pair |
| 182 | Supply and open installation of following Sizes of MS boxes as per the detailed specification. (Refer Sec VI, Clause No.15.10). |
| 183 | 150(W)X150(H)X80(D)mm, 1.6mm thick sheet MS Box. |
| 184 | Supply, installation, testing and commissioing of following Heat shrinkable cable jointing kit with UY connector for telephone cables of following sizes including excavation of soil, backfilling etc as specified (Refer sec VI, Caluse No.10.6) |
| 185 | 20 PAIR 0.63mm Heat shrinkable jointing kits for PIJF cable. |
| 186 | 50 PAIR 0.63mm Heat shrinkable jointing kits for PIJF cable. |
| 187 | Supply and installation of KroneLSA PLUS disconnection Modules 2/10 (10 pair each) as per specification. (Refer Sec V). |
| 188 | Supply and installation of the following telephone accessories: (Ref Sec V). |
| 189 | Push button analog telephone instruments with line cord, spring cord and rosettee box. |
| 190 | CLIP telephone instruments with line cord spring cord and rosettee box. |
| 191 | Jumper wire 0.5mm dia. (colour: Red/white & Blue/white) for telephone connection. |