| 1 | Design, Fabrication, Supplying, Installation, Testing & Commissioning of dust and vermin proof OutdoorFeeder panel (with canopy system) of size (1400*1000*400)mmsuitable for 415 V, 3 Phase, 4 Wire 50 Hz AC supply system fabricated in compartmentalized system made out of CRCA sheet steel of 2 mm thick and painted with powder coating in approved shade and comprising of Incoming & Outgoing switchgears, Aluminium Bus bars of adequate capacity for phases and neutral (minimum of 300 A, with Color Coded Sleeve(30*10)mm), CT Coil, suitable MS angle base frame, interconnections, including incoming and outgoing cables connections etc. as required at the site of work and as directed by the engineer in-charge. (switchgear as follows with appropriate links, plates, connections etc.:Incoming1. 4 Pole MCCB, 200A, 36kA - 1 nos. (Adjustable Thermal & Adjustable Magnetic)Outgoing1. 4 Pole MCCB, 125A, 35kA - 1 nos. (Adjustable Thermal & Adjustable Magnetic)2. 4 Pole MCCB, 100A, 35kA - 1 nos. (Adjustable Thermal & Adjustable Magnetic)3. 4 Pole MCCB, 63A, 35kA - 2 nos. (Adjustable Thermal & Adjustable Magnetic)Metering1. RYB Indication Lamp2. VAF Meter |
| 2 | Design, Fabrication, Supplying, Installation, Testing & Commissioning of dust and vermin proof OutdoorFeeder panel (with canopy system) of size (1600*1000*400)mmsuitable for 415 V, 3 Phase, 4 Wire 50 Hz AC supply system fabricated in compartmentalized system made out of CRCA sheet steel of 2 mm thick and painted with powder coating in approved shade and comprising of Incoming & Outgoing switchgears, Aluminium Bus bars of adequate capacity for phases and neutral (minimum of 300 A, with Color Coded Sleeve(30*10)mm), CT Coil, suitable MS angle base frame, interconnections, including incoming and outgoing cables connections etc. as required at the site of work and as directed by the engineer in-charge. (switchgear as follows with appropriate links, plates, connections etc.:Incoming1.4 Pole MCCB, 200A, 36kA - 1 nos. (Adjustable Thermal & Adjustable Magnetic)Outgoing1. 4 Pole MCCB, 125A, 35kA - 1 nos. (Adjustable Thermal & Adjustable Magnetic)2. 4 Pole MCCB, 100A, 35kA - 6 nos.(Adjustable Thermal & Adjustable Magnetic)Metering1. RYB Indication Lamp 2. VAF Meter |
| 3 | Design, Fabrication, Supplying, Installation, Testing & Commissioning of dust and vermin proof OutdoorFeeder panel (with canopy system) of size (1400*1000*400)mmsuitable for 415 V, 3 Phase, 4 Wire 50 Hz AC supply system fabricated in compartmentalized system made out of CRCA sheet steel of 2 mm thick and painted with powder coating in approved shade and comprising of Incoming & Outgoing switchgears, Aluminium Bus bars of adequate capacity for phases and neutral (minimum of 300 A, with Color Coded Sleeve(30*10)mm), CT Coil, suitable MS angle base frame, interconnections, including incoming and outgoing cables connections etc. as required at the site of work and as directed by the engineer in-charge. (switchgear as follows with appropriate links, plates, connections etc.:Incoming1. 4 Pole MCCB, 125A, 35kA - 1 nos. (Adjustable Thermal & Adjustable Magnetic)Outgoing1. 4 Pole MCCB, 100A, 35kA - 4 nos.(Adjustable Thermal & Adjustable Magnetic)Metering1. RYB Indication Lamp2. VAF Meter |
| 4 | Design, Fabrication, Supplying, Installation, Testing & Commissioning of dust and vermin proof OutdoorFeeder panel (with canopy system) of size (1400*1000*400)mmsuitable for 415 V, 3 Phase, 4 Wire 50 Hz AC supply system fabricated in compartmentalized system made out of CRCA sheet steel of 2 mm thick and painted with powder coating in approved shade and comprising of Incoming & Outgoing switchgears, Aluminium Bus bars of adequate capacity for phases and neutral (minimum of 300 A, with Color Coded Sleeve(30*10)mm), CT Coil, suitable MS angle base frame, interconnections, including incoming and outgoing cables connections etc. as required at the site of work and as directed by the engineer in-charge. (switchgear as follows with appropriate links, plates, connections etc.:Incoming1. 4 Pole MCCB, 125A, 35kA - 1 nos. (Adjustable Thermal & Adjustable Magnetic)Outgoing1. 4 Pole MCCB, 100A, 35kA - 3 nos.(Adjustable Thermal & Adjustable Magnetic)Metering1. RYB Indication Lamp2. VAF Meter |
| 5 | Design, Fabrication, Supplying, Installation, Testing & Commissioning of dust and vermin proof OutdoorFeeder panel (with canopy system) of size (1600*1000*400)mmsuitable for 415 V, 3 Phase, 4 Wire 50 Hz AC supply system fabricated in compartmentalized system made out of CRCA sheet steel of 2 mm thick and painted with powder coating in approved shade and comprising of Incoming & Outgoing switchgears, Aluminium Bus bars of adequate capacity for phases and neutral (minimum of 300 A, with Color Coded Sleeve(30*10)mm), CT Coil, suitable MS angle base frame, interconnections, including incoming and outgoing cables connections etc. as required at the site of work and as directed by the engineer in-charge. (switchgear as follows with appropriate links, plates, connections etc.:Incoming1.4 Pole MCCB, 125A, 35kA - 1 nos. (Adjustable Thermal & Adjustable Magnetic)Outgoing1. 4 Pole MCCB, 100A, 35kA - 5 nos.(Adjustable Thermal & Adjustable Magnetic)Metering1. RYB Indication Lamp 2. VAF Meter |
| 6 | Supply and Installation of 100A MCCB in available space in Cable Alley of Feeder Pillar 1, including all accessories like Busbar, Trunkings, Links, spreaders etc. |
| 7 | Relocation and Re-Installation of Feeder Pillar including foundation work |
| 8 | Supplying ofXLPE Armoured cable with aluminium conductor of 1.1 KV grade confirming to IS:7098 (Part- I) 1988 with up to date ammendments of the following sizeas required.(a) 3.5 x 50 sq.mm |
| 9 | (b) 3.5 x 35 sq.mm |
| 10 | (c) 3.5 x 25 sq.mm |
| 11 | (d) 4 x 16 sq.mm |
| 12 | (e) 3 x 6 sq.mm |
| 13 | Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required(a) 100 mm dia |
| 14 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.(a) Above 35 sq. mm and upto 95 sq. mm |
| 15 | (b) Upto 35 sq. mm |
| 16 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.(a) Above 35 sq. mm and upto 95 sq. mm |
| 17 | (b) Upto 35 sq. mm |
| 18 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.(a) Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 19 | (b) Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 20 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.(a) Upto 35 sq. mm |
| 21 | Supplying and fixing of light class G.I. pipe of 100 mm dia. (nominal) 3 metres length along the pole for protection of under ground cable as required. |
| 22 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.(a) 3½ X 50 sq. mm (35mm) |
| 23 | (b) 3½ X 35 sq. mm (32mm) |
| 24 | (c) 3½ X 25 sq. mm (28mm) |
| 25 | (d) 4 X 16 sq. mm (28mm) |
| 26 | (e) 2 X 10 sq. mm (19mm) |
| 27 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (a) Single Pole & Neutral |
| 28 | (b) Single pole |
| 29 | (d) Triple pole & Neutral |
| 30 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 31 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 32 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 33 | Supply of 20W LED T8 tube with extruded Al body, PC diffuser and inbuilt driver with efficacy min of 100 lumens/W along with Highly robust Industrial Box type luminaire suitable for single T8 LED Tube etc.at the site of work. |
| 34 | Supply of 20W LED T8 tube with extruded Al body, PC diffuser and inbuilt driver with efficacy min of 100 lumens/W along with Surface/Suspended waterproof industrial luminaire with polycarbonate housing and diffuser suitable for single 4 ft T8 tube etc.at the site of work. |
| 35 | Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 36 | Supplying, installation, Testing and commissioning of70W LED Street light fitting made up of pressure die cast alluminium housing with IP 66,IK 08, System efficacy of≥110 lm/W,colour temp 6500 K,THD( %)≤ 10 and fixing on wall/truss/pole with suitable clamps and nut bolts including giving connection etc., at site of work as required. |
| 37 | Supplying and fixing of 32 mm dia X 1.00 metres long G.I. pipe (medium class) bracket for mounting of all type of street light fitting on pole / wall / structure including bending the pipe to the required shape, 2 nos 40 mm X 3 mm flat iron clamps with nuts, bolts and washer, painting the flat iron with primer and finish paint as required. |
| 38 | Supplying and fixing of Hot pressed moulded SMC Junction box of size 230mm x 170mm x 105mm with 6A SP MCB, 2/4 way strip connector etc. as required at the site of work. |
| 39 | Supplying of70 watt LED typeWell Glass luminaires in pressure die-cast aluminium housing with IP 66, System efficacy of≥110 lm/W,colour temp 5700 K,THD( %)≤ 10, Polycarbonate diffuser in opal finish. |
| 40 | Supplying and fixing of 3 phase (RYBN), 100 A, 4 way, wall mounted aluminium BusBar chamber in sheet steel enclosureetc, at site of work as required. |
| 41 | Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge.(a) Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix) |
| 42 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :(a) 1:3:6 (1 Cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 43 | (including MF = 1.0633 as per CPWD to account for 18% GST) |