| 1 | Excavation in trenches not exc 1.5 M wide and not exc 1.5 M indepth for pipe line, etcgetting out in soft/ loose soil and levelling of bottom surface to required level complete all as specified and as directed. |
| 2 | Returning filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 CM thick complete all as specified and as directed. |
| 3 | Removal of surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point completeall as specified and directed by Engineer-in-charge. |
| 4 | Supply, laying and spreading of dry (Ganga) sand, free from organic impurities for cushioningas in trenches 8cm depth below cable and 15cm above cable andpunned to 10cm depthcomplete all as specified & directed. Note :- Punned thickness shall be considered for measurement purpose. |
| 5 | M&L brick, sub class \"B\" bricks laid dry, flat, length equal to width of brick over sand cusioning in trenches for cable protection complete all as specified and directed |
| 6 | Labour only for reuse of serviceable bricks obtained from taking out of existing cable,equal to width of brick over sand cusioning in trenches for cable protection complete all as specified and directed. |
| 7 | Material & labour for cutting /boringto plinth protection/ hard standing / road etc in suitable depth to across the GI pipe size upto 80 mm dia of bore for drawn through XLPE under ground cable forgivingmechanical protection to cable complete all as specified and directed. Note : Quoted rate shall be included the cost of required material for repairing to disturbed surface complete all as per existing site and all as directed by Engineer-in-charge. |
| 8 | M&L in replacement to GI tubing light grade 80 mm dia of bore with all fitting laid in trenches across the road or fixed with pole/ surface of wall etc as site with required fixing accessories complete all as specified and directed. (Make: Tata or Jindal or Swastic) |
| 9 | Supply and fixing galvainesd water tubing light grade 50 mm dai of borewith fix with pole/ surface of wall / laid in trench etc assite with required fixing accessories complete all as specified and directed. (Make: Tata or Jindal or Swastic) |
| 10 | Supply, laying, jointing, connecting and testing XLPE insulated PVC sheathed cable 1100V grade, conforming to IS-7098 (Part-I) of 1988, screened PVC bedded, armoured electric power cable, heavy duty multi-stranded aluminium conductor grade cross section area 3.5 core 95 Sqmm (earthed) complete all as specified, laid in trenches / fixed on walls/poles, passing through pipes, etc. including connecting up to DBs, etc. with required lugs, end terminal / cable glands complete all as specified and as directed. |
| 11 | Supply, laying, jointing, connecting and testing XLPE insulated PVC sheathed cable 1100V grade, conforming to IS-7098 (Part-I) of 1988, screened PVC bedded, armoured electric power cable, heavy duty multi-stranded aluminium conductor grade cross section area 3.5 core 70 Sqmm (earthed) complete all as specified, laid in trenches / fixed on walls/poles, passing through pipes, etc. including connecting up to DBs, etc. with required lugs, end terminal / cable glandsdisposing off complete all as specified and as directed. |
| 12 | Supply, laying, jointing, connecting and testing XLPE insulated PVC sheathed cable 1100V grade, conforming to IS-7098 (Part-I) of 1988, screened PVC bedded, armoured electric power cable, heavy duty multi-stranded aluminium conductor grade cross section area 3.5 core 50 Sqmm (earthed) complete all as specified, laid in trenches / fixed on walls/poles, passing through pipes, etc. including connecting up to DBs, etc. with required lugs, end terminal / cable glands complete all as specified and as directed. |
| 13 | Supply, laying, jointing, connecting and testing XLPE insulated PVC sheathed cable 1100V grade, conforming to IS-7098 (Part-I) of 1988, screened PVC bedded, armoured electric power cable, heavy duty multi-stranded aluminium conductor grade cross section area 4 core 25 Sqmm (earthed) complete all as specified, laid in trenches / fixed on walls/poles, passing through pipes, etc. including connecting up to DBs, etc. with required lugs, end terminal / cable glands complete all as specified and as directed. |
| 14 | Supply, laying, jointing, connecting and testing XLPE insulated PVC sheathed cable 1100V grade, conforming to IS-7098 (Part-I) of 1988, screened PVC bedded, armoured electric power cable, heavy duty multi-stranded aluminium conductor grade cross section area 4.00 core 16 Sqmm (earthed) complete all as specified, laid in trenches / fixed on walls/poles, passing through pipes, etc. including connecting up to DBs, etc. with required lugs, end terminal / cable glands complete all as specified and as directed. |
| 15 | Supply, laying, jointing, connecting and testing XLPE insulated PVC sheathed cable 1100V grade, conforming to IS-7098 (Part-I) of 1988, screened PVC bedded, armoured electric power cable, heavy duty multi-stranded aluminium conductor grade cross section area 2.00 core 10 Sqmm (earthed) complete all as specified, laid in trenches / fixed on walls/poles, passing through pipes, etc. including connecting up to DBs, etc. with required lugs, end terminal / cable glands complete all as specified and as directed of the following sizes: |
| 16 | Labour for re-laying, connecting, jointing, thembling using in suitable size and cramping etc to serviceable XLPE insulate LT cablein all specification (95/70/50/25/16 sqmm)incl brick (re-use) and sand (Provided fresh) etc all as per existing complete with other site required works complete all as specified and directed.Note : Excavation and Sand cushioning punned dept shall be measured and paid separately under respective items. |
| 17 | Material and labour for PCC 1:4:8 type D2 (using 40 mm graded stone aggregates) as in foundation bed and above ground including necessary form work and finishing the exposed surface even and smooth without using extra cement complete all as specified and directed. |
| 18 | M&L for tree trimming cut away dead or excess branches from trees or shrubs to maintain clearance along with over head power lines using climbing equipment and collecting the debris for disposal and removing broken limbs from electric wires by using hooked extension poles complete all as specified and as directed.Notes:-Span is taken as distance between two adjacent poles. |
| 19 | Supply ,installing,commissioning and testing CPRI approved factory made,floor mounted LT panel board outdoor typewith doubledoor 3 phase 4 wire having seperate busbar chamber and compartment for control switch gear fabricated with3.15mm thick CRCA sheet, dust, vermin and water prooffor outside and 2 mm thick inner sheetduly powder coated painting mounted on angle iron stand of suitable size fabricated with50X50x6 mm angle iron frame,with suitable size 4 no of legs at each corner including grouting in PCC1:3:6 upto 30 cmhaving locking arrangementand opening arrangement from front and rear both duly fitted with compression cable glands for entry and exit of cables, powder coated with two coats and having minimum clearance of 450 mm above ground level complete. Panel shall be suitable size to accomodate with and including following accessories:-(a) Panel mounteddigital volt meterflush mounting of size 96x96mmto read line & phase voltage with selector switch auxiliary supply 230 volt AC -01 No. (b) Panel mountedAmpere meterflush mounting of size 96x96mmto read line & phase current including CTs with selector switch auxiliary supply 230 volt AC -01 No.(c ) Tinned copper bus bar. for3 phase and neutral of capacity 200 Amp, duly taped in color coded FRP sleeves.d) Indicating lamps Red, Yellow and Blue in color, LED type complete with lamp holders, 220 volts AC- 01 set of 3.(e) Panel wiring with suitable size copper cable.(a) INCOMING-(i) MCCB 4 pole, 160Amps rating and 25KA rupturing capacity with adjustable thermal magnetic release type complete - 01 No (b) Outgoing(ii)MCCB 4 pole, 100Amps rating and 16KA rupturing capacity with adjustable thermal magnetic release type complete - 02 No (iii)MCCB 4 pole, 63Amps rating and 16KA rupturing capacity with adjustable thermal magnetic release type complete - 01 No |
| 20 | Supply ,installing,commissioning and testing CPRI approved factory made,floor mounted LT panel board outdoor typewith doubledoor 3 phase 4 wire having seperate busbar chamber and compartment for control switch gear fabricated with3.15mm thick CRCA sheet, dust, vermin and water prooffor outside and 2 mm thick inner sheetduly powder coated painting mounted on angle iron stand of suitable size fabricated with50X50x6 mm angle iron frame,with suitable size 4 no of legs at each corner including grouting in PCC1:3:6 upto 30 cmhaving locking arrangementand opening arrangement from front and rear both duly fitted with compression cable glands for entry and exit of cables, powder coated with two coats and having minimum clearance of 450 mm above ground level complete. Panel shall be suitable size to accomodate with and including following accessories:-(a) Panel mounteddigital volt meterflush mounting of size 96x96mmto read line & phase voltage with selector switch auxiliary supply 230 volt AC -01 No. (b) Panel mountedAmpere meterflush mounting of size 96x96mmto read line & phase current including CTs with selector switch auxiliary supply 230 volt AC -01 No.(c ) Tinned copper bus bar. for3 phase and neutral of capacity 200 Amp, duly taped in color coded FRP sleeves.d) Indicating lamps Red, Yellow and Blue in color, LED type complete with lamp holders, 220 volts AC- 01 set of 3.(e) Panel wiring with suitable size copper cable.(a) INCOMING-(i) MCCB 4 pole, 160Amps rating and 25KA rupturing capacity with adjustable thermal magnetic release type complete - 01 No (b) Outgoing(ii)MCCB 4 pole, 100Amps rating and 16KA rupturing capacity with adjustable thermal magnetic release type complete - 01 No (iii)MCCB 4 pole, 63Amps rating and 16KA rupturing capacity with adjustable thermal magnetic release type complete - 03 No |
| 21 | Taking down old unsv DB and supply and fixing Busbar chamber TPN current capacity 100 Amp 04 way horizental type, total enclosed with porcelain Insulator and colour coated tinned copper bus bar with suitable size of legs including PCC work fixing on ground or on wall/pole with suitable size of clamp, Nut, bolts, suitable size of thimbles for connectionetc. complete all as dirceted by Engr-in-Charge.Make - Havells/L&T/Standard/ABB/Indoasian |
| 22 | Taking down old unserviceable DB and supply and fixing Busbar chamber TPN current capacity 200 Amp 04 way horizental type, total enclosed with porcelain Insulator and colour coated tinned copper bus bar with suitable size of legs including PCC work fixing on ground or on wall/pole with suitable size of clamp, Nut, bolts, suitable size of thimbles for connectionetc. complete all as dirceted by Engr-in-Charge.Make - Havells/L&T/Standard/ABB/Indoasian |
| 23 | Supply, jointing, commissioning and testing in replacement heat shrinkable straight through jointing kit suitable for 1100 volt grade (Earthed) cable for outdoor type complete with jointing material and required accessories suitable for underground XLPE cable of size 4 Core 120 to 185Sqmm (earthed)complete all as specified and directed.Make:Dension/3M/Rahycam or make as mentioned in Appx \"B\" of PS. |
| 24 | Supply, jointing, commissioning and testing in replacement heat shrinkable straight through jointing kit suitable for 1100 volt grade (Earthed) cable for outdoor type complete with jointing material and required accessories suitable for underground XLPE cable of size 4 Core 120 to 185Sqmm (earthed)complete all as specified and directed. Make:Dension/3M/Rahycam or make as mentioned in Appx \"B\" of PS. |
| 25 | S&F Off load change over switch 4 pole ,415 V ,capacity 200amps with sheet metal encloser fixed on wall complete all as specified and directed Make ; L&T / Schneider or Equivalent |
| 26 | Supply and fixing Adjustable thermal and adjustable magnetic setting based MCCB 4 Pole 250 Amps, rated Ultimate Shortcircuit Breaking Capacity 35 KAIcu at 415 V (kA rms thermal & magnetic adjustable type, 415 volts with extended copper terminals including taking out existing Userviceable/ burnt MCCB from site complete all as specified and directed by Engineer-in-charge. |
| 27 | Supply and fixing Adjustable thermal and adjustable magnetic setting based MCCB 4 Pole 160 Amps, rated Ultimate Shortcircuit Breaking Capacity 25 KAIcu at 415 V (kA rms thermal & magnetic adjustable type, 415 volts with extended copper terminals including taking out existing Userviceable / burnt MCCB from site complete all as specified and directed by Engineer-in-charge. |
| 28 | Supply and fixing Adjustable thermal and adjustable magnetic setting based MCCB 4 Pole 100 Amps, rated Ultimate Shortcircuit Breaking Capacity 16 KAIcu at 415 V (kA rms thermal & magnetic adjustable type, 415 volts with extended copper terminals including taking out existing Userviceable / burnt MCCB from site complete all as specified and directed by Engineer-in-charge. |
| 29 | Supply and fixing Adjustable thermal and adjustable magnetic setting based MCCB 4 Pole 63 Amps, rated Ultimate Shortcircuit Breaking Capacity 16 KAIcu at 415 V (kA rms thermal & magnetic adjustable type, 415 volts with extended copper terminals including taking out existing Userviceable / burnt MCCB from site complete all as specified and directed by Engineer-in-charge. |
| 30 | Supply and fixing in repair new generation energy saving & environmental friendly long life LED flood light 100 watt 230 V AC outdoor type with high pressure die cast aluminum housing with toughened glass and heat resistant and indvidual high power LED\"s with secondary optical lances, high efficiency >120 lm/W with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp including making electric connection with three core copper cable with all accessories completeall as specified and directed. |
| 31 | Note :- (i) Credit shown in credit schedule of tender document shall be considered by the tenderer while quoting the rates of various items. The same shall be recovered from various payment to contractor before handing over old material. The contract amount shall be arrived at after deduction of Schedule of Credit from the total quoted amount in BOQ.(ii) Make of material shall be as per mentioned in Particular specifications or Appendix \"B\" to Particular specifications as approved by AGE (I) AF manauri |