Tender For Provision Of Auditorium At Nasirabad Mil Station.; 1 Note:-Please refer schedule A notesbefore quoting the tender. 2 Sch A Part - I (Building Works) 3 Construction of block ofAuditorium (600 capacity) complete all as shown on drawings and as specified & directed.Note :- Wooden flooring wherever shown in the drawings shall be measured and paid separately. 4 Construction of block of AC plant room complete all as shown on drawings and as specified & directed. 5 Construction of block of AHU room complete all as shown on drawings and as specified & directed. 6 Construction of block of Sub Station and pump house Bldg complete all as shown on drawings and as specified & directed. 7 Construction of UG Sump of 115000 Ltrs complete all as shown on drawings and as specified & directed. 8 Construction ofSentry Post complete all as shown on drawings and as specified & directed. 9 GENERAL SUMMARY 10 Lump sum price worked out by the contractor for INTERNAL WATER SUPPLY WORKS as listed in Schedule ‘A’Part- II (Ref prepriced schedule attached seperately) 11 Lump sum price worked out by the contractor for INTERNAL ELECTRIFICATION WORKS as listed in Schedule ‘A’Part- III (Ref prepriced schedule attached seperately) 12 Lump sum price worked out by the contractor for EXTERNAL WATER SUPPLY WORKS as listed in Schedule ‘A’Part- IV (Ref prepriced schedule attached seperately) 13 Lump sum price worked out by the contractor for EXTERNAL ELETRIC SUPPLY WORKS as listed in Schedule ‘A’Part- V (Ref prepriced schedule attached seperately) 14 Lump sum price worked out by the contractor for ROAD, PATH AND CULVERT WORKS as listed in Schedule ‘A’Part- VI (Ref prepriced schedule attached seperately) 15 Lump sum price worked out by the contractor for SEWAGE DISPOSAL WORKS as listed in Schedule ‘A’Part- VII(Ref prepriced schedule attached seperately) 16 Lump sum price worked out by the contractor for AREA DRAINAGE WORKS as listed in Schedule ‘A’Part-VIII(Ref prepriced schedule attached seperately) 17 Lump sum price worked out by the contractor for COMPOUND WALL AND FENCING WORKS as listed in Schedule ‘A’Part-IX (Ref prepriced schedule attached seperately) 18 Lump sum price worked out by the contractor for LIGHTENING PROTECTION WORKS as listed in Schedule ‘A’Part- X (Ref prepriced schedule attached seperately) 19 Lump sum price worked out by the contractor for FIRE FIGHTING SYSTEM WORKS as listed in Schedule ‘A’Part- XI (Ref prepriced schedule attached seperately) 20 Lump sum price worked out by the contractor for DG SET WORKS as listed in Schedule ‘A’Part- XII (Ref prepriced schedule attached seperately) 21 Lump sum price worked out by the contractor for CENTRAL AC WORKS as listed in Schedule ‘A’Part- XIII (Ref prepriced schedule attached seperately) 22 Lump sum price worked out by the contractor for RAIN WATER HARVESTING WORKS as listed in Schedule ‘A’Part-XIV(Ref prepriced schedule attached seperately) 23 Lump sum price worked out by the contractor for ROOF TOP SOLAR WORKS as listed in Schedule ‘A’Part-XV (Ref prepriced schedule attached seperately) 24 Lump sum price worked out by the contractor forCEILING AND WALL PANELING, CARPETING WORKS as listed in Schedule ‘A’Part-XVI (Ref prepriced schedule attached seperately) 25 Lump sum price worked out by the contractor for EXCAVATION, EARTH WORK AND SITE DEVELOPMENT WORKSas listed in Schedule ‘A’ Part-XVII (Ref prepriced schedule attached seperately) 26 SCH A Pt - XVIII (MISCELLANEOUS ITEMS) 27 INTERNAL WATER SUPPLY WORKSNOTE:- For items of INTERNAL WATER SUPPLY WORKS notes given at the beginning of Sch ‘A’ Part-II (INTERNAL WATER SUPPLY WORKS) shall also be applicable. 28 S&F for two way bib tap 15mm bore CP fancy type complete all as specified and directed 29 INTERNAL ELETRIFICATION WORKS NOTE:- For items of INTERNAL ELETRIFICATION WORKS notes given at the beginning of Sch ‘A’ Part-III (INTERNAL ELETRIFICATION WORKS) shall also be applicable. 30 Material and labour for point wiring with two runs of single core FRLSH 1.5 Sq.mm. (Nominal area) PVC insulated unsheathed multistranded copper conductor cable confirming to IS. the wiring shall be drawn through and including not less than 20 mm nominal dia& 1.4 mm thick PVC concealed conduit complete with all accessories including Modular PVC Flush Box for fixing modular type switches, sockets, regulators etc. including provision of multistranded 1.5 Sq.mm. copper conductor as earth wire connected to common earth dolly and earth in distribution board including modular cover plate complete all as directed all as specified. (For Item no 6.02 to 6.05) 31 One light point controlled by one way 6A modular switch. 32 One fan/wall fan point controlled by one way6A modular switch. 33 One Exhaust fan point controlled by one 6 Amps one-way modular switch 34 One Socket Outlet contolled by 6 Amps modular switch on Independent board 35 All as per Sl item No. 6.01 above, but with cable 2.5 sqmm for phase and neutral & 2.5 sqmm for earth continuity complete for 16 Amps socket outlet point 36 M & L for submain wiring using 1.1 kV grade single core FR-LSH flexible cable conforming to IS 694: 2010, having multi-drawn thin strands of electrolytic copper conductors of size 35.0 sqmm for phase, neutral and earth continuity conductor connecting to earth dolly, drawn in medium grade suitable size PVC surface/recessed conduit conforming to IS 9537 (Part 3): 1983, colour coded as per IS 11353: 1983, including making good of disturbed surfaces of wall / ceiling / floor all complete as specified in IS 732: 2019 and directed. (4 X 35 sqmm + 1 X 25 sqmm earth wire)NOTE: Phase & neutral conductors (04 runs), earth continuity conductor (01 run) and surface / recessed conduit (01 run) shall be measured combined as one unit. 37 S&F LED tube light fitting. 2x20 W, 230v , efficacy not less than 120 Lumens per watt, colour temprature 6000 to 6500 K (Cool White), power factor PF> 0.95, aluminium body , CRI> 80, IP rating> 20, THD<10% complete with all accessories internally pre-wired and including connecting up with flexible copper conductor cable suitable size from ceiling rosecomplete all as specified and directed. 38 Supply and fixingrecess mounted 1 x 1LED luminarie 20 watt, cool day/warm white light with white powder coated CRCA housing with LED driver, efficacy not less than 100 Lumens per wattcomplete all as specified and directed. 39 S & F of 30 W recessed mounted downlight made of extruded aluminium housing and high power LED as a light source with clear diffuser includingelectronic driver complete with electrical connection through PVC insulated copper conductor unarmoured cable of suitable size all as specified and directed. 40 S & F of 30 W recessed mounted dimable downlight made of extruded aluminium housing and high power LED as a light source with clear diffuser includingdimable electronic driver complete with electrical connection through PVC insulated copper conductor unarmoured cable of suitable size all as specified and directed. 41 S&F Wall mounted air circulator copper wound, double ball bearing of size 600 mm, 220-240 volts, air delivery not less than 250 CMM & power consumption not more than 200 watt, metal body painted with metallic powder coated anti corrosion paint alongwith necessary fixing arrangement and connecting cable from ceiling rose complete all as specified and directed. 42 Supply, installation, testing and commissioning of LT Panel Made out of CRCA sheet 2 mm thick sheet steel, indoor type, factory made by CPRI approved manufacturer, totally enclosed, dust and vermin proof (protection Class IP 54), (front opening) with locking arrangement, double door duly compartmentalized with extended canopy at the top, the panel shall duly powder coated with colour shade RAL 7035 Siemens grey Pure Polyester adopting 8 tank pretreatment of fabricated job before powder coating, the panel shall consist of the following switchgear:-Incomer-MCCB 4P 250 A 36kA-1 Nos, Out going- MCCB 4P 125A 25kA -1 Nos ,MCCB 4P 100A 25kA -2 Nos , Protection MCB 6 A, SP, all inter connections to outgoing feeders shall be made with TPN aluminum bus bar of rating not less than the current carrying capacity of the respective feeder, all bus bars shall be covered with colour coded heat shrinkable sleeve, the complete panel shall be mounted on ISMC of 75x40mm duly painted with black paint.Digital Ammeter (0-300) with ASS-1No, Current transformer of rating 300/5A-3No, Digital Voltmeter with VSS(0-500)V-1No, RYB LED set-1,including suitable size of cable lugs, danger platecomplete all as specified and directed. 43 Supply and fix decorative LED light fitting 1x6/9 Watt with Lamp holder PVC/Polycarbonate type with back plate and LED valve including all accessories complete all as specified and directed. 44 EXTERNAL WATER SUPPLY WORKSNOTE:- For items of EXTERNAL WATER SUPPLY WORKS notes given at the beginning of Sch ‘A’ Part-IV (EXTERNAL WATER SUPPLY WORKS) shall also be applicable. 45 Supplying, laying, connecting, jointing and testing in trenches 80 mm nominal dia ductile iron pressure pipe for water mains, centrifugally cast, spigot and socket ends (for push on joints), class K9 in any length with external protection of Metallic zinc with finishing layer of bituminous paint and internal linings of Portland cement (with or without additives) mortar with seal coat, all as per IS 8329: 2000 and including materials and jointing with rubber gasket for WA type of application and hardness class 50 for bulb and hardness class 80 for heel all as per IS 5382: 2018 and IS 12820: 2004 complete all as specified and as directed. Note : DI fitting shall be measured and paid separtely 46 M&L for cutting of existing road/hard standing for crossing of MS/DI/CI/GI Pipes for laying of pipe upto 200 mm dia borePipes including necessary excavation and earth work including repairing the same as per existing road/hard standing by providing PCC (1:2:4)type B1 to match with existing surface complete all as specified and directed. 47 Supply and fix star rated monoblock pump with cast ironimpeller, motor body and delivery casing and carbon steel shaft suitable for 415 V ,3 phase system having discharge 27 LPS + 5% at 20 meter head of capacity 10HP/7.5KW, Suction and delivery 100 mm Pipe complete all as specified and directed. 48 M&L for drilling and tapping in GI/CI/DI water main of any size in position for branch connectionof 200/80 mm bore of pipe complete with clamp, nut bolt, washer etc complete all as specified and directed. 49 Supplying, laying, connecting, jointing and testing in trenches ductile iron fittings (special castings) (class K12 as per IS 9523: 2000) for ductile iron pressure pipe for water mains upto 200 mm nominal dia (spigot and socket and flange ends (for push on joints and flanged joints) with external coatings of Metallic zinc with finishing layer of bituminous paint and internal linings of Portland cement (with or without additives) mortar with seal coat, all as per IS 9523: 2000 and including materials and jointing with rubber gasket for WA type of application and hardness class 50 for bulb and hardness class 80 for heel all as per IS 5382: 2018 and IS 12820: 2004 for push on joints and rubber gasket as per IS 638: 1979 for flanged joints complete all as specified and as directed. 50 Supply, installation, testing and commissioning of LT Panel Made out of CRCA sheet 2 mm thick sheet steel, indoor type, factory made by CPRI approved manufacturer, totally enclosed, dust and vermin proof (protection Class IP 54), (front opening) with locking arrangement, double door duly compartmentalized with extended canopy at the top, the panel shall duly powder coated with colour shade RAL 7035 Siemens grey Pure Polyester adopting 8 tank pretreatment of fabricated job before powder coating, the panel shall consist of the following switchgear:-Incomer- MCCB 4P 63 A 10kA-1No, Out going- MCCB 4P 32A 10kA-2No,MCCB DP 10 Amp 10kA-1No, DOL Starter for 2 HP -02 Nos, Copper Cable 4 Sqmm 3 Core- 20 RM . main aluminum bus bar shall be of 100Aall bus bars shall be covered with colour coded heat shrinkable sleeve, the complete panel shall be mounted on ISMC of 75x40mm duly painted with black paint.Ammeter meter (0-30 Amp) with ASS-1No, Digital Voltmeter with VSS(0-500)V-1No, RYB LED set-1, including suitable size of cable lugs and PCC foundation complete all as specified and directed 51 M&L for Construction of valve chambers of size 0.9 x0.9 x 0.9 internal dimentions with 150 mm thick PCC foundation 1:4:8 type D2 using 40 mm graded trap stone aggregate, 230 mm thick brick masonary wall with sub class B bricks builts in cement mortar 1:4 10 mm thick plastering to brick masonary in cement mortar internally and externally upto 15 cm below ground level, 50 mm thick coping with PCC 1:2:4 type B1 using 20 mm graded crushed trap stone aggregate valve chamber having coller frame size0.9 x0.9 x 0.9made of mild steel angles of size 50mm x 50mm x 6mm and cover made of 2.5 mm thick mild steel sheet framed by 40 x 40 x 5 mm MS angle having 02 nos cross X supprt fixed with coller frame by mild steel hinges - 02 Nos, locking arrangements with provision of locks and painting the steel surfaces with two coats of alluminium enameled paint over a coat of zinc chromate primer including neccessary earth work, excavation, all as specified and directed by Engineer-in-Charge . 52 EXTERNAL ELECTRICAL SUPPLY WORKS NOTE:- For items of EXTERNAL ELECTRICAL SUPPLY WORKS notes given at the beginning of Sch ‘A’ Part-V (EXTERNAL ELECTRICAL SUPPLY WORKS) shall also be applicable. 53 S&F expulsion type fuse (DO Fuse) single pole, 11 kV complete with all fittings,complete all as specified and as directed. 54 M&L for HT cable route indicator factory castmade from of size 800mm x 230mm x 100 including excavation PCC for foundation embossed writing as 11 KV CABLEincl painting preparation of surfaces both sides all as specified and directed. 55 M&L for GI tubing brackets 40mm bore light grade with new GI tubing bracket 40mm bore light grade 1.20 metre length including MS clamp with nuts, bolts and washers etc including taking down old unsv complete, all as specified and directed 56 Supply and connecting 1100 volts grade heavy duty cable with PVC insulated solid copper conductor served with an inner sheathing of PVC tape and overall PVC sheathed of size 1.5 sqmm 3 core for pole box to street light fitting complete all as specified and directed. 57 M&L for junction box made out of 2 mm thick sheet of size 130 x 70H with 4 Nos aluminium busbar of size 20 x 3 mm thick mounted on porcelain insulators with and including MCB, C curve, SP, 06 Amp - 01 No. including incoming and out going connections with necessary welding work, clamps and mounting on poles etc complete all as specefied and as directed. . 58 LT panel incoming from transformer and DG set.Supply, installation, testing and commissioning of LT Panel Made out of CRCA sheet 2 mm thick sheet steel, indoor type, factory made by CPRI approved manufacturer, totally enclosed, dust and vermin proof (protection Class IP 54), (front opening) with locking arrangement, double door duly compartmentalized with extended canopy at the top, the panel shall duly powder coated with colour shade RAL 7035 Siemens grey Pure Polyester adopting 8 tank pretreatment of fabricated job before powder coating, the panel shall consist of the following switchgear:-Incomer- ACB 4P 500 A 36kA-2No(01 for transformer and 01 for DG set), Out going- MCCB 4P 400A 36kA-1No(for AC Plant),MCCB 4P 200A 25kA-1No (for Fire fighting and pump house), MCCB 4P 160A 25kA -01 Nos(01 for Auditorium Bldg Panel ), On Load Changeover Switch 500Amp - 01 No, MCB TPN 63 A, 10 KA-01 No, Timer switch for security light -01 No. main aluminum bus bar shall be of 750A TPN, all inter connections to outgoing feeders shall be made with TPN aluminum bus bar of rating not less than the current carrying capacity of the respective feeder, all bus bars shall be covered with colour coded heat shrinkable sleeve, the complete panel shall be mounted on ISMC of 75x40mm duly painted with black paint. Microprocessor based threephase phase electronictemper proof energy meter of rating 1accuracy class 0.5 voltage 3x240 v,-/5A, conformingto IS: 13779.01 No.Digital Ammeter (0-500) with ASS-1No, Current transformer of rating 500/5A-3No, Digital Voltmeter with VSS(0-500)V-1No, RYB LED set-1,Interlocking logic electrically &mechanicallybetween two incomers and one bus coupler to avoid parallel operation of DG & mains including suitable size of cable lugs and PCC foundation complete all as specified and directed. 59 For Auditorium BldgSupply, installation, testing and commissioning of LT Panel Made out of CRCA sheet 2 mm thick sheet steel, indoor type, factory made by CPRI approved manufacturer, totally enclosed, dust and vermin proof (protection Class IP 54), (front opening) with locking arrangement, double door duly compartmentalized with extended canopy at the top, the panel shall duly powder coated with colour shade RAL 7035 Siemens grey Pure Polyester adopting 8 tank pretreatment of fabricated job before powder coating, the panel shall consist of the following switchgear:-Incomer-MCCB 4P 250 A 36kA-1 Nos, Out going- MCCB 4P 125A 25kA -1 Nos ,MCCB 4P 100A 25kA -2 Nos , Protection MCB 6 A, SP, main aluminum bus bar shall be of 240A TPN, all inter connections to outgoing feeders shall be made with TPN aluminum bus bar of rating not less than the current carrying capacity of the respective feeder, all bus bars shall be covered with colour coded heat shrinkable sleeve, the complete panel shall be mounted on ISMC of 75x40mm duly painted with black paint.Digital Ammeter (0-300) with ASS-1No, Current transformer of rating 300/5A-3No, Digital Voltmeter with VSS(0-500)V-1No, RYB LED set-1, including suitable size of cable lugs, danger platecomplete all as specified and directed. 60 Supply, installing, testing and commissioning of Automatic power factor improvement capacitor ( APFC )having aggregate capacity : 125 KVARin 8 stages with micro processor based, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system. Shall be dust and vermin proof, protection class (IP-54) and made of 3.15 mm thick CRCA Sheet having bus bar of aluminium 300 Amps capacity , three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeve with suitable frame work/ support made out of 50 x 50 x 6 mm, front opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FR cable of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey RAL- 7035 shade. The scope of work also comprising of the following:- 61 (01)Incoming MCCB 250 Amps 36 KA 4 Pole Adjustable thermal & fixed magnetic setting Ics=100% of Icu - 01 No(02) Microprocessor based Power factor corrector relay 8 stage -01 No.(03) Capacitor duty contactor for 25 KVAR, - 02 Nos(04) Capacitor duty contactor for 20 KVAR,- 02 Nos. (05) Capacitor duty contactor for 15 KVAR, - 01 No.(06) Capacitor duty contactor for 10 KVAR, - 01 No. (07) Capacitor duty contactor for 05 KVAR, - 02 Nos (08) Power Capacitor 5 KVAR heavy duty fixed with bus bar with MCB 16 A TP -1 No. (09) MCB 63 A,10 KA TP C Curve -02 Nos.(10) MCB 40 A,10 KA TP C Curve- 02 Nos.(11) MCB 32 A,10 KA TP C Curve - 01 No.(12) MCB 25 A,10 KA TP C Curve - 01 No.(13) MCB 16 A,10 KA TP C Curve- 02 Nos.(14) Auto Manual Selector Switch, 6A 1 Pole - 01 No. (15) ON/OFF Push Button, with Elements - 8 Sets (16) Indicating light ON-OFF, 220 V AC -8 Sets. 62 (17) Aux contactor 2 NO + 2 NC with Aux. Block 2 NO+2 NC, 220 V AC -02 Nos. (18) Power capacitor 25 KVAR heavy duty dry type having tolerance 0% -10% with discharge device resistor, 02 Nos.(19) Power capacitor 20 KVAR heavy duty dry type having tolerance 0% -10% with discharge device resistor, 02 Nos.(20) Power capacitor 15 KVAR heavy duty dry type having tolerance 0% -10% with discharge device resistor, 01 No.(21) Power capacitor 10 KVAR heavy duty dry type having tolerance 0% -10% with discharge device resistor, 01 No.(22) Power capacitor 5 KVAR heavy duty dry type having tolerance 0% -10% with discharge device resistor, 02 Nos. (23) Digital Voltmeter 0-500 V 96x96 mm-01 set.(24) Digital Ammeter 0-250 Amps 96x96 mm- 01 set.(25) Volt Meter Selector Switch 6 A , - 01 No.(26) Amps Meter Selector Switch 6 A , - 01 No.(27) C.T. of ratio 250/5 amps 5 VA Class-1.0 -03 Nos (28) Red, Yellow, Green Phase indicating Lights LED type 220 V AC- 1 Set. (Set of three). (29) Protection MCB 6 Amps SP - 05 Nos.(30) Sensing CT 200/5 A or as per site load condition shall be provided alongwith APFC Panel. 63 SEWAGE DISPOSAL WORKS NOTE:- For items of SEWAGE DISPOSAL WORKS notes given at the beginning of Sch ‘A’ Part-VII (SEWAGE DISPOSAL WORKS) shall also be applicable. 64 Supply & laying RCC septic tank (150 Users) designed to carry sewage and sullage water, excavation in any type of of soil, PCC 1:4:8 below foundation ,RCC M-30 Design Mix in walls, Base slab , Baffle walls and Roof Slab includind beam etc with vent shaft, manhole openings with cover connection etc,complete with effective depth of 1.5 metre and overall depth of 3 m for 150 user capacity complete all specified and directed . 65 M & L for soakage wells including excavation in any type of soil, foundation in PCC (1:4:8), walls of honey combed fly ash brick masonry with top ring of RCC 1:1.5:3 type A-1 concrete including intercepting chamber and screen chamber made of fly ash brick masonry in CM (1:6), RCC cover slab in1:1.5:3 type A-1 & SFRC MH cover, interconnecting pipes of RCC/DWC complete filled with brick bats of size 2.4m dia & 4.50m effective depth complete all as specified and directed. 66 FIRE FIGHTING SYSTEM WORKSNOTE:- For items of FIRE FIGHTING SYSTEM WORKS notes given at the beginning of Sch ‘A’ Part-XI (FIRE FIGHTING SYSTEM WORKS) shall also be applicable. 67 Providing, Fixing, testing and commissioning 150 mm dia C.I. double flanged control valve assembly with alarm Gong, consisting of installation stop valve, alarm valve drain 50 mm dia and 15mm dia test valve, pressure gauges on inlet and outlet with alarm motor and gong, alarm valve clack with padlock and stop drain plug, alarm stop valve and strainer including making inlet/outlet connections by providing necessary nuts, bolts, gaskets ( 6mm thick) all complete all as specified & directed. 68 Providing and fixing bronze orifice with12mm thick disc with tag on plate mentioning dia of orifice for Sprinkler system to control the pressure including rubber gasket packing, bolts, nuts, washers, complete all as specified & directed. 69 Material and labour for fire points made out from MS angle iron 40 x 40 x 6 cutting welding etc,including rain protection canopy made out of 2.0mm thick CRCA Sheet , painting with two coats of red postoffice colourall as directed for keeping various accessories i.e. bucket, hook, beator etc complete all as specified and directed. 70 Supply and fixing standard firemans axe with heavy rubber handle complete all as specified and directed. 71 Supply, laying and testingISI Marked 2 core x 1.5 mm2, Multistrand Copper, FRLS Armoured cable (red in Colour), laid on surface with GI saddle-spacers every 0.3 meters. Complete with GI Junction Box, lugs, cable compression glands, cable tags and Ferruling complete all as spedified and directed. 72 GI slotted type cable trays of the following sizes using MS angle, channels, flats etc.. All MS supports used shall be given one coat of red oxide primer & 2 coats of synthetic enamel paint of approved colour of size 100 x 50 mm x 2mm complete all as specified & directed. 73 S&F fire extinguisher dry chemical powder (ABC) type 9 Kg complete all as specified & directed. 74 S&F fire extinguisher CO2 type 4.5 Kg complete all as specified & directed. 75 S&F fire extinguisher CO2 type 3 Kg complete all as specified & directed. 76 S&F fire extinguisher mechanical foam type 09 ltrs complete all as specified & directed. 77 S&F fire extinguisher wheeled mechanical foam type 45 ltrs complete all as specified & directed. 78 Supply, install, testing and commissioning LT panel, indoor type cubical panel board, made out of 2mm thick CRCA sheet, duly powder coated, compartmental design with locking arrangements, weather and vermin proof with proper ventilation slots, IP 52 free standing floor mounted with Aluminium busbar of suitable size for phase and neutral mounted on hygroscopic insulators comprising of the following:-(a) MCCB 4 pole 400A, incomer, 415V, 50Hz,35 kA - 01 No.(b) MCCB 4 pole 200A, outgoing, 415V, 50Hz, 10 kA - 02 No.(c) MCB TPN32 A, 415V- 1 No. (d) MCB SP6-32A, 10kA - 4 Nos.(e) FASD starter 125 HP-2 Nos.(f)DOL starter 7.5 HP - 1 No.(e) 400 A rated Aluminium bus bar with colour coded heat shrinkable sleeve(f)Digital ammeter with suitable CTs - 02 Nos.(g) Digital voltmeter (0 - 500 V) - 01 No.(h) R-Y-B phase indicating lamp- 01 set(j) Pressure switch operated relays for auto start of pumps - 2 Nos.(k)Internal wiring with suitable size of PVC insulated stranded copper conductor duly crimped with copper lugs ferruled complete wiring of panel & Installation complete all as specified & directed. 79 Providing and Fixing suitable C.I. air release single valve of 20mm dia including necessary support and painting with two coats of enamel paint over a coat of primer etc. complete,for wet riser termination complete all as specified & directed. 80 Supplying and fixing in position drain / test valve assembly comprised of2 nos. 80mm diabrass tested heavy duty ball valves with screwed ends confiming to IS 554 with ISI mark , including necessary G.I. C class pipes, union(1 no)& site glass fitting etc. complete all as specified & directed. 81 S&F air vessel made suitable for 200 mm dia pipe, 8 mm thick MS sheet, 1000 mm in height with air release valve on top and flanged connection to riser, drain aggangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and painting with synthetic enamel paint of approved shade as requires complete all as specified & directed. 82 ENTRY AND EXIT WORKS 83 Supply and installationsingle sided LED Signage (EXIT/ENTRY/GENTS TOILET/LADIES TOILET/No Smoking/Fire)with3W LED of red/Green colour including built in battery backup for 2 hrs complete all as specified and directed . 84 Supply and installation LED step light with4/5 W LEDmade out of white powder coated aluinium body with IP-54 protection complete all as specified and directed . 85 DG SET WORKSNOTE:- For items of DG SET WORKS notes given at the beginning of Sch ‘A’ Part-XII (DG SET WORKS) shall also be applicable. 86 Supply, erection, testing and commissioning complete of manufacture of OEM manufactured, static silent (sound proof enclosure) diesel Engine Driven generating set CPCB IV +capable of delivering 320 KVA, water cooled, 415 volts (AC three phase, 4 wire system of supply) 50 HZ at power factor 0.8 minimum.The DG set shall consists of diesel engine coupled to a matching alternator, through flexible coupling and mounted on common base frame and complete with control panel standardized by manufacture, fuel tank with mounting arrangements and inlet outlet return inlet oil arrangement exhaust pipe complete and suitable for conditions prevalent at Nasirabad (capacity of Engine, alternators shall be worked out taking all derarting factors into consideration) including foundation (of suitable size leaving at least 0.5 M all around for easy of movement and 0.5 M height) anti vibration pads, including all features to complete with latest CPCB guidelines and comprising of following :-(i) ENGINE (Prime Mover) : Diesel Engine 1500 RPM, direct injection, type four stroke, confirming to ISO 3046 / BS 5514, water cooled, naturally turbo charged, capable of giving adequate BHP to drive alternator capable of delivering 320 KVA at outdoor atmospheric conditions at Nasirabad ), ( Taking all derating factor into consideration), 24 Volt (as per manufacturer recommendations) electric battery start, complete with all standard fittings / fixtures as per manufacturer and including suitable panel with tachometer, lub oil, temperature, pressure guage and frequency meters and also including self starter system, dynamo, fuel electric control panel with electronic governor (ECPG) and enging protection system (shut down, High water temperature, low lub oil, oil pressure, over speed etc) fuel tank and first fill of lub oil and other consumables etc. 87 ITEM NO 1 CONTD/- (II) ALTERNATOR :Brushless AC alternator, 3 phase, 415 volt, 4 wire, rated for output of 320 KVA, Minimum power factor 0.8, 1500 RPM, IP 23 protection class enclosure, insulation class “H” sailent pole, revolving field single bearing automatic voltage regulator coupled through flexible coupling with and to match the above engine. (III) BASE PLATE :- Made out of structural steel as per manufactures recommended design / specifications.(IV) AMF CONTROL PANEL :-Factory made cubical type floor mounted LT panel board, indoor type made out of MS angle not less than 25x25x5 mm, and 1.6 mm thick MS CRCA sheet, front opening type, protection class IP-54, duly powder coated after seven tank process, with electrolytic grade copper bus bar of 500 Amps capacity for four poles, with all standard switchgear and protection, internal wiring of adequate size PVC insulated multistranded copper conductor cable etc and also consisting of following :-(a)ACB 415 Volts, 400 Amp, rating 4 pole 50 KA rupturing capacity,Microprocessor based release, draw out type, specially fixed for incoming supply with over load, short circuit and earth fault protection – 01 No with suitable rating HRC back up fuses.(b)AMF logic panel including wiring, power contactor with MCCB/ACB suitable capacity for DG Set of main supply, single phase preventor, digital multifunction meter (showing Amps, Volts, Hz, KWH etc), Emergency stop Button, DG over load, High water temp, Low lub oil pressure, Auto charging unit and failure to start, Phase indication lamp LED type RYB includig all relays, circuit and protection required for automatic operation of DG Set. Contactor, AC1 duty, AC coil with aux contact 500A, 4Pole - 2 Nos 88 CONTD .........(V) ACCOUSTIC ENCLOSURE :-Sheet metal fabricated cope type silent enclosure manufactured on CNC machines as per CPCB norms and powder coated after seven tank process, the enclosure shall be designed for reducing the sound level to 75 DB (A) at a distance of 1 M at 75% load under field condition and OX, 70 DB at 3 M from Gen set when DG set is working at full load alongwith testing conformance, lebelling certification etc as laid down in GSR No 371 (E) dt 17 May 2002.(VI)Foundation / Plinth / Base :Shall be provided as per manufactures recommendations, however minimum 0.5 M space should be available all around the set and height of plinth shall not be less than 0.5 M.(VII) Diesel storage tank of cap adequate for storage of diesel for 12 hrs operation of Gen Set.(VIII) MISC : Tool kit, operation and maintenance catalogue spare part list, overhauling manuals, guarantee card etc shall be provided as per manufacture standard practices. 89 FURNITURE WORKS 90 SUPPLY AND FIXING OF AUDITORIUM CHAIR PUSH BACK - AUTO TIP UP.SEAT: The seat rest assembly is 1.5±0.1 cm thick flat plywood and in-situ moulded with polyurethane foam & upholstered with polyester fabric and enclosed by an injection moulded cover. The Seat should be an auto-tip up feature making it stay in upright position when not in use enabling clear row passage. The seat profile should have a large waterfall edge to help the users get necessary comfort in popliteal region.The Seat size shall be : 45.0 cm. (W) x 50.5 cm (D) x 13.8 cm (T) Approx. BACK: Back shall be ergonomically designed with protruding headrest. The backrest assembly should made up of 1.2±0.1cm thick flat plywood measured as per QA method described in OCP-QLTA-P14-18 upholstered with polyester fabric and enclosed by an injection moulded back cover. The back foam should be designed with contoured back support for extra comfort. The back size shall be HIGH BACK SIZE: 48.7 cm. (W) x 76.9 cm (H) x 12.5 cm (T) Approx. The HR polyurethane foam for Seat and Back should be moulded with Density = 45 +/- 2kgs/m3. LEG FRAME: The leg frame assly should be fabricated from M.S. tube 6.0±0.03cm x 4.0±0.03cm x 0.2±0.016cm thick welded with grouting member. It should be black powder coated ( DFT 40-60 microns ) & grouted to floor using anchors. Contd........... 91 ASSEMBLY: The armrest should be made up of black integral skin polyurethane with 65+/-10 Shore A hardness and reinforced with M.S. insert fixed with leg frame. The armrests shall be scratch and weather resistant. The armrest cladding shall made up of 0.9±0.1 cm thk Plywood & upholstered with polyester fabric. All steel components shall be Epoxy Polyester Powder Coated (DFT 40-60 microns) after 7 tank anti-rust treatment. The auditorium chair shall be designed to get mounted/ grouted on floors with flooring specification as mentioned in flooring pre-requisite. Overall Dimensions shall be Seat Height - 44.5 cm, Height - 103.5cm, armrest c/c - 54.6 cm, Width & Depth as measured from pedestal - Width-64.0cm and Depth-71.5 cm.OEM shall have ISO 9001:2015, IS0 45001:2018 and ISO 50001 :2018 certificate. Chair shade/ colour shall be as approved by GE. OEM shall furnish one year warranty for chairs. 92 S&F of Wooden Floor complete all as shown on drawings and as specified & directed. 93 CENTRAL AC WORKSNOTE:- For items of CENTRAL AC WORKS notes given at the beginning of Sch ‘A’ Part-XIII (CENTRAL AC WORKS) shall also be applicable. 94 (a) Design, Supply, Installation, Testing &Commissioning of Central Air Conditioning plant including AHUs, Water pump sets, Cooling Towers, ducting and electrical connections suitable for 3 phase AC supply chilled water system of suitable capacity (60 TR X 3 units. total capacity 180 TR) including all provisions for earthing, floor mountedLT Panel board, all civil and electrical works as per IS specification and best practices for Provision of auditorium at Nasirabad Mil Stn complete all as specified and directed.Note : -(i)The capacity mentioned for AC Plant is tentative. Actual capacity should be work out by the contractor based on inside & outside enviroment condition.(ii) Compressor, Chiller & Pump, etc should be equally divided based on the total AC plant capacity as designed vetted from IIT/NIT and approved by GE. 95 (Contd/-) (b)Design of energy efficient central air conditioning plant based on inside/outside conditions. Inside conditions to be obtained from GE on given data sheet attached as per format given in Appendix of particular specifications. The design shall meet relevant code requirements and should be as per latest IS practices. It should include the followings:-(i) Data based heat load calculations for AHU as per site plan. (ii)Double line duct drawing showing different sizes of ducts air flow details.(iii)Chiller water pipingdrawing including condenser pipes and fitting with details of dia. (iv)Layout schematic line diagram of LT control panel suitable for the plant showing all the details such as main incoming, outgoing and their type, capacities, Qty, alongwith connected measuring instrument/meters, indication lamp, starters, MCB, MCCB isolator etc. (v) Specification/description of equipment and other materials/items with technical literature of various components of reputed makes.(vi)Recommendation of type of plantwith detailed justifcation depending upon heat load to meet the desired condition specified in data sheet to be obtained from GE in consultation with user as per format attached asAppendixs of particular specifications. (vii)Line plan of plant AHU showing various eqpts/items with dimensions of various eqpts/items with specific working clearances between eqpts to eqpts and from walls, after due consideration existing doors and windows. (viii) Schedule of item/description of equipment of all items with accounting unit, Qty and particuar specification etc.(ix) Full description of item/eqpt of schedule with recommended brand/makes. (x)Inside design conditions are required to be maintained irrespective of minor variations in outside. 96 Contd/-Notes :-(a)Contractor should submit 2 Nos CD showing detailed design with description/ specification complete alongwith heat load calculation (For summer, winter & monsoon) design, drawing bill of quantities and two Nos hard copies. (b)Outside design conditions can be obtained from concerned metrological authorities.(c)Contractor will develop the soft copy of all thedrawings required forthe work on the basis of Hard copy/line plan of the project.(d) The details given inAppendixs of particular specifications are tentative. Contractor has to obtain firm details from GE in consultantion with users.(e) Atmospheric/any other required data to be obtained from concerned metrological deptt/Govt institutions.(f) DPR should be vetted alongwith its drawing from IIT/NIT & finally approved by GE.(g)The work of Air Conditioning shall be carried out by specialist agency having past experience as approved by GE.(h)Noise level (sound pressure) should not exceed the permissible limits.(i)Testing includes phase- I, 24 Hrs continuous and Phase-II 24 Hrs continuous for all three seasons. (k) Any other connected works not mentioned above but considered necessary by the tenderer for successful installation, commissioning and operation and efficient performance of the plant shall be provided by the contractor and the rate for the same shall be deemed to be inclued in the quoted unit rates. 97 RAIN WATER HARVESTING WORKSNOTE:- For items of RAIN WATER HARVESTING WORKS notes given at the beginning of Sch ‘A’ Part-XIV (RAIN WATER HARVESTING WORKS) shall also be applicable. 98 M&L for 6000 Ltrs capacity triple layer rotational moulded polythene water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position all as specified in SSR Part I complete all as specified and as directed. 99 ROOF TOP SOLAR WORKSNOTE:- For items of ROOF TOP SOLAR WORKS notes given at the beginning of Sch ‘A’ Part-XV (ROOF TOP SOLAR WORKS) shall also be applicable. 100 Design,Supply, install, testing and commissioning of ON Grid connected roof top solar generation system of capacity not less than 150 KWp AC capacity all as specified in PS and directed as per PS clause and specification as follows (for Auditorium at Nasirabad Mil Stn):- 101 (A) Supply, Installation, testing and commissioning of not less than 150 KWp SPV system comprising of latest specification DCR solar photo voltic modules/array of high efficiency made of mono crystalline silicon solar PV cells with supply and fix of terminal box on the module havingprovision for opening & replacing the cable etc.as per IEC. The general features of PV modules shall be as given below :- a) The module shell be made up mono crystalline silicon cells. b) The interconnected cells shall be laminatedin vacuum to withstand adverse environmental conditions. c) The module frame is made of corrosion resistant materials, preferably having aluminium anodized finish. d) The minimum clearance between the lower edge of the modules & the developed ground level shall be 300 mm. e) Surge arresting devices to be provided at junction box and module shall be provided with bypass diode. f) The SPV module must be IEC 61215, IEC 61730 part I & part II, IEC 61701 certified from any of the accredited certifying agencies. g) Each solar PV module must be warranted by manufacturer at least 90% rated power at the end of 10 years & 80% at the end of 25 years. Note: Qty of PV module shall be decided as per OEM recommendation, design and layout drawing submitted to department duly approved by GE. 102 Note :- (i) Makes of panel provided shall be as per MNRE specification/ standard and registered in ALMM. (ii) 5% spare qty of modules shall be provided by the contractor for repair / replacement purpose. (iii) Addln module shall be provided / installed by the contractor to meet specified power output incase if the same not achived during testing and commissioning without any extra cost.(iv) Each PV module used in any solar power project must use a RF identification tag. The following information must be mentioned in the RFID used on each module:-(v) Name of the manufacturer of PV Module(vi) Name of the Manufacturer of Solar cells(vii) Month and year of the manufacture for solar cells and the module(viii) Country of origin (Make in INDIA only)(ix) I-Vcurve for the module(x) Wattage, Im, Vm and FF for the module(xi) Unique Serial No and Model No of the module(xii) Date and year of obtaining IEC PV module qualification certificate(xiii) Name of the test lab issuing EC certificate(xiv) Other relevant information on traceability of solar cells & module. 103 (B) Module Mounting Structure (MMS) :-Supply & fixing of the anti-corrosive factory made Gl structure on the RCC Roof for fixing of PV modules by fixing of suitable size fastner, spring washer, nuts & bolt. The minimum thickness of galvanization & mounting steel structure shall be as per IS 47592 & IS 2061-1992 respectively withstand the wind load of 180 Km/hr. as per IS 875. The array structure shall be fixed properly using maintenance free earthing kit. Note:- (i)The total load for roof top SPV should be less than 60 Kg/m2.(ii) The design of module mounting structure complying load withstand as per relevant IS alongwith fixing arrangement on roof shall be submittedby the contractor duly vetted from IIT/NIT/Govt Engg college for approval by GE.(iii) The material shall be corrosion resistant and electrolyticaly compatible with material used in module frame. (iv)The fasteners should be of stainless steel and should allow easy replacement of any module.(v) The minimum clearance of the structure from the roof level should be 300 mm. 104 (C) Solar DC Cables:- (i) Supply & laying of 1.1kv single core multi strandedPVC FRLSH insulated & unsheathed copper wire/ copper cable for 3 ph supply in ISI marked PVC rigid conduit pipe by saddling as per IEC. (For Solar Array DC supply connection). Note : (i) The size of cable shall be as per design given by OEM & approved by GE.(ii)Cable should be passes through PVC rigid pipe and pipe should be fixed properly inside cable tray for easily maintenance, is included in quoted rate(D) DC Combine boxA DC combine box shall be used to combine the DC cables of the solar module array with DC fuse protection for the outgoing DC cables to the DC distribution box.(E) Array junction boxes-The number of junction boxes as per design given by OEM are to be provided in the PV array for termination of connecting cables. All wire/cables must be terminated through cable lugs. Copper busbar/terminated blocks housed in the junction box conforming to IP 65 degree of protection with EPDM rubber gasket to prevent water entry. Junction boxes shall be mounted on the MMS such that they are easily accessible and protected from direct sunlight & harsh weather. 105 (F) On Grid Power Conditioning unit ( Inverter):-Supply & installation of 415V 3-ph, 50 Hz microprocessor DSP type grid connected Inverters which converts DC energy produce by the solar array to AC energy such that it synchronizes with the existing AC power source on site. Provisioning of power manager to get all parameter details. The Inverter shall have inbuilt MPPT (Maximum Power Point Tracker) feature so as to extract maximum power from PV modules & the MPPT units environmental testing should qualify IEC 60068-2 (1,2,14,30)/ Equivalent BIS standard. (The voltage variation of +/- 10% & frequency variation +/-3 Hz)Note :-(i) No of inverters shall be provisioned as per design given by OEM. (ii) Inverter should have internal protection arrangements against any sustainable fault in feeder line and against the lightning on feeder.(iii) Should have isolating transformer(iv) Inverter efficiency >93% with inbuilt galvanic isolation) (v) No load losses shall be less than 1% of rated power.(vi) The above quoted rate is inclusive of MS structure stand duly fixed and placing inverter. 106 (G) Solar meter & Net meter:-As per DISCOM requirement, to be provided at main MRS. Cost of Solar meter & Net meter, installation, connected accessories, necessory liasioning with DISCOM are included in quoted Rates. If DISCOM desires installation of above meters through deposit work including NOC if required, then cost of deposit shall be made by contractor and amount shall be included in quoted rates.(H) AC Distribution Board:-(i) Supply & installation of 415V 3-ph 50Hz AC distribution board control AC power from Inverter & provided by nacessary surge arrestors system and suitable capacity MCCBs.; Qty-01 No Note: ACDB shall be provided as per OEM design as approved by GE.(J) AC Cables:-(ii) Distribution wiring in 1.1kv single core multi stranded PVC FRLSH insulated & unsheathed copper wire fixed on wall on PVC batten or saddle(For AC power supply from Inverter to AC distribution board Panel).Note :- (i) The size of cable shall be as per design given by OEM & approved by GE.(K) Protection:-The system shall be provided with all necessary protection like earthing, lightening & surge protection as per relevant standard.(L) Performance testing:-Ratio between the theoretical energy outputs of the SPV plant is termed as performance ratio and is measured in accordance with IEC 61724. Based on prevailing climatic and temperature conditions in India, a performance ratio of 75% is expected for crystalline modules. (M) Other Misc items:-As per requirement given by OEM and approved by GE to be provided. 107 (N) Earthing:_As per MNRE specifications to be provided.(O) Lightening protection:-As per MNRE specifications to be provided.(P) Installation, Testing & Commissioning:-As per safety norms of SERC/CEA to be provided.(Q) O&M and Warranty:-5 years from the date of commissioning to be provided.Note: The quoted rate deemed inclusive of the following:-(i) Transportation charges with Transportation Insurance for the all material of on grid solar roof top system including loading & unloading at site from workshop.(ii) Insurance for the complete system for the 5 Years.(iii) AMC-Suraksha which include 24 Hour site Maintenance visits, Response time 2 hrs and turn around time 48 hrs, Monthly plant performance report. (iv) As per performance obligation, the contractor shall maintain minimum capacity utilization factor (CUF) of 13%. The report shall be submitted by the contractor to GE as per guidelines promulgated by SECI. (Contd..../-) 108 Contd..../-(v) Satisfactorily testing and commissioning of the system is to be done by the contractor in presence of the rep of accepting officer and the report of the complete system is submitted to department.(vi) Guarantee and warranty of Solar panel and connected devices is to be submitted to department. (vii) The report of generated unit of solar power on monthly basis is to be submitted to office.(viii) The cost of appropriate civil structure (Hot Dip Galvanised Iron structure) shall be included in quoted rate . The Civil structure incorporating Solar PV modules (arrays) should withstand the gusts of wind /cyclonic wind upto 150 km/hr from backside of panel.(ix). PV modules will be guaranteed against any manufacturing defect for 10 Years.(x). The contractor shall submitt design vetted from National Institute of Solar Energy or by Govt Institute authorised by MNRE or NISE or any reputed Institute / Agency authorised.(xi). The quoted rate shall be inclusive of all the components as specifed here-in-above as well as Particular Specification, unless otherwise specified.(xii). Suitable fastening arrangement such as grouting and calming should be provided to secure the installation against the specific wind speed. The Empanelled Agency shall be fully responsible for any damages to SPV System caused due to high wind velocity within guarantee period as per technical specification. 109 Supply and fixing heavy duty Self Priming Monoblock pump for cleaning of Solar Panel through pressure and fitted on MS base plate , having discharge of 638 Gln/Hr at a pressure head of 15-42m complete with standard accessories including 1-HP, single phse, 220V rating electric motor complete with DOL starter of suitable rating. 110 Supply and fix flexible, anti-twist, weather resistant, UV resistant thick water hose PVC pipe of size 15mm nominal dia for optimal water flow with leak proof tap adapter compatible with delivery pipe of mono-block pump(as specified in above item) with suitable reducer/ enlarger with clamp for cleaning and washing of solar panels all as specified and as directed. Note :- Make or quality as approved by GE. 111 Supply and fix adjustable type water spray gun compatible with PVC hose size of 15mm nominal dia, built of high quality brass material, durable and rust-proof, solid brass structure to ensure quick connection and with durable accessories, can withstand uptoPSI water pressure, and without any leakage of water all as specified and directed.Note :- Make or quality as approved by GE. 112 CEILING AND WALL PANELING, CARPETING WORKSNOTE:- For items of CEILING AND WALL PANELING, CARPETING WORKS notes given at the beginning of Sch ‘A’ Part-XIV (CEILING AND WALL PANELING, CARPETING WORKS) shall also be applicable. 113 Premium CarpetPile Content: Polyester fiber/olefin Frieze Heat Set FiberPile Structure: Cut PileBacking: Action Back PPThickness: 14 mmNRC: 0.35Pile Weight: 1500 GSMTotal Weight:2000 GSMWork executed by OEM