| 1 | Earthing with GI earth plate 600 mm x 600 mm x 6 mm thick including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc with charcoal/ coke as salt as required |
| 2 | Providing and fixing 25 mm x 5 mm GI strip in 40 mm dia GI pipe from earth electrodei/c connection with G.I. nut, bolt, spring, washer excavation and refilling etc as required etc as required |
| 3 | Providing and fixing 25 mm x 5 mmGI strip on surface or in recess for connection etc as required |
| 4 | Supplying & making endterminaton with brass compression gland and aluminium lugs for 3.5 x 35 sq.mmPVC insulated and PVC sheathed/ XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 5 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.63 mm dia (OD-63 mm & ID-51 mm nominal) |
| 6 | Laying of one number PVC insulated and PVC sheathed/ XLPE power armoured cable of 1.1 KV grade of following sizein the existing RCC/HUME/ METAL PIPE etcas required. (A) up to 35 Sqmm |
| 7 | Laying of one number PVC insulated and PVC sheathed/ XLPE power armoured cable of 1.1 KV grade of following size in the open duct as required (A) up to 35 Sqmm |
| 8 | Providing Installation testing and commissioning of 36 Watt LED glare less ceiling light fitting of size 2\" x2 \" complete with all acessories etcincluding connection with 1.5 sq. mm FRLS PVC insulated copperconductor single core cable etc as required. |
| 9 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 10 | Supply and installation 300 mm exhaust fandouble wall bearing of900 RPM Heavy duty motor with protective bird guard and louvers shutters complete with frame in the existing opening, including, making good the damage, connection, testing, commissioning etc. as required. |
| 11 | Supply and fixing Mirrior Light of 5 watt LED Batten with Installation testing etc. complete as required. |
| 12 | Installation of 18 watt LED surface light fittings directly on ceiling/ wallincluding connection with 1.5 sq. mm FRLS PVC insulated copperconductor single core cable etc as required. |
| 13 | Installation of 50 watt LED flood light fittings directly on ceiling/ wallincluding connection with 1.5 sq. mm FRLS PVC insulated copperconductor single core cable etc as required. |
| 14 | Providing and fixing of electric storage water heater of 25 ltr of 2 KW of havells make i/c fasteners with nut, bolts and washers including with connection, testing commissioning etc as required/ |
| 15 | Providing and fixing of 1.5 ton split air conditioner 240 volt 50 Hz copper winding i/c indoor and outdoor unit ,stablizer with nuts bolts and washer including connection ,testing and commissioning etc as required |