| 1 | Supply, installng, testing and commissioning indoor type, step down transformer, 11 KV/433 Volts (at no load) AC 3 phase 50 Hz, 200 KVA capacity, core type, copper wound, on HV& LV oil immerse, naturally cooled, Oil Natural - Air Natrual (ON AN), with external cooling tubes, delta connected on primary side (HV) and star connected on secondary side (LV)and having 7 step tapings at +/- 2.5% of each step to be changed by means of hand operated off load tap changer gear. The maximum temperature rise should not exceed 45 degree celsius in oil and 55 degree celsius in HV/LV winding when measured by resistance methodafter continuous full load run on ambient temp of 40 degree celsius. The transformer shall be in accordance with IS-1180 Part -I 2014 and shall comprise of the following :-(a) Three Nos porcelain bushing suitable for 11 KV on HV side, complete with copper rods, nuts and washers fitted in cable box.(b) Cable box on both HT < sideconsisting ofporcelain bushing with copper / brass rods, complete with nuts and washers, with cable glands suitable for taking out LT supply. The size of cable box at LT side should be suitable for terminating 3 Nos 3.5 Core 185 Sqmm Armoured Aluminium Cable. |
| 2 | Item NO. 1.00 Contd... (c) Oil conservator with filter type drain valve and oil level gauge.(d) De-hydrating breather with first fill of dehydrating agent (silica gel).(e) Explosive vent, Thermometer pocket on tank cover, oil level gauge, oil drain filter valve, lifting lugs/hooks, oil filling hole with cap/plug with connection plate complete, air release valve plug and four nos plain solid cast steel detachable rollers.(f) One No 100 mm dia, dial type thermometer, vapour pressure type, having range 0-120 degree celsius with metal guard having maximum perimeter temperature reading indicator with re-setting device.(g) Two earthing terminals on tank cover to facilitate fixing of 50x6 mm galvanized iron earth strip for earthing of body.(h) Rating plate and terminal marking plate.(j) Extra bushing for Neutral, in the LT cable box for connecting independent set of earthing for neutral.(k) First filling of new and unused transformer oil, IS-335 marked make Power oil/power link filtered and tested up to 60 KV dielectric strength at 2.5 mm air gap between testing electrodes. |
| 3 | M&L for trolley size of 3658mm Length X 1829mm Width X 2300mm Heightwith main (channel) chassis of size 100mm X 50mm MS channel, support channel of size 75mm X 40mm MS channel and floor with 6mm thick chequred plate.Side walls made up with welded wire mesh and Rear door fixed by hinges & lock.Axle 02 Nos of 65Sqmm, rim double plated 04 Nos.Tyres 04 Nos of size 7-50*16.Toe hook shall be made of forged steel, suspension system axle will be fitted with leaf spring and roof covered with GI sheet.Isolator and fuse mountins are of 63X63X4mm Box Pipe, 50x50x5mm MS Angle and 75x38 C Channel clamp for transformer of carrying capacity of 5 Ton for mounting of 200 KVA Transformer complete all as specified and directed by Engineer-in - Charge. |
| 4 | Supply, laying & testing XLPE insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) with stranded aluminum conductor, 11000 volts grade, of size 95 sqmm, 3 core complete all as specified and directed by Engineer-in-Charge. |
| 5 | M&L for cable Jointing kit for 33 KV (Earthed) grade cable for oudoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95Sqmm complete all as specified and as directed by Engineer-in-Charge |
| 6 | Supply, laying, connect test and commissioning of stranded copper conductor cable XLPE insulated screened PVC tape innersheathed, unarmoured electric power cable heavy duty with 1100 volts grade corss sectional area of 150 Sqmm single Core confirming to IS:7098 Part-I laid in trenches/floors complete testing and commissioning complete all specified and directed by Engineer-in-Charge. |
| 7 | All as per Item No. 5.00 here-in-before above but for stranded copper conductor cable XLPE of cross sectional area 120 Sqmm complete all specified and directed by Engineer-in-Charge. |
| 8 | S&F copper ling barrel lugs of size 150 Sqmm complete all specified and directed by Engineer-in-Charge. |
| 9 | S&F copper ling barrel lugs of size 120 Sqmm complete all specified and directed by Engineer-in-Charge. |