| Sl. No. | Item Description |
| 1 | SCHEDULE \"A\" Part - I (BUILDINGS/STRUCTURES WORK)Details of Buildings are given here-in-before:- |
| 2 | SCHEDULE \"A\" PART- II ( SITE CLEARENCE, SITE DEVELOPMENT AND EARTH WORK) Details of prepriced Schedule is given in tender documents |
| 3 | SCHEDULE \"A\" PART- III( INTERNAL ELECTRIFICATION)Details of prepriced Schedule is given in tender documents. |
| 4 | SCHEDULE \"A\" PART-IV ( INTERNAL WATER SUPPLY )Details of prepriced Schedule is given in tender documents. |
| 5 | SCHEDULE \"A\" PART- V (TERMAC/LINK TT)Details of prepriced Schedule is given in tender documents. |
| 6 | SCHEDULE \"A\" PART- VI (ROAD/PATH&CULVERT)Details of prepriced Schedule is given in tender documents. |
| 7 | SCHEDULE \"A\" PART- VII (SEWAGE DISPOSAL)Details of prepriced Schedule is given in tender documents |
| 8 | SCHEDULE \"A\" PART- VIII (AREA DRAINAGE)Details of prepriced Schedule is given in tender documents |
| 9 | SCHEDULE \"A\" PART- IX(RETAINING WALL)Details of prepriced Schedule is given in tender documents |
| 10 | SCHEDULE \"A\" PART- X (LIGHTNING PROTECTION)Details of prepriced Schedule is given in tender documents |
| 11 | SCHEDULE \"A\" PART- XI (EXTERNAL WATER SUPPLY)Details of prepriced Schedule is given in tender documents |
| 12 | SCHEDULE \"A\" PART- XII(EXTERNAL ELECTRIC SUPPLY)Details of prepriced Schedule is given in tender documents. |
| 13 | SCHEDULE \"A\" PART- XIII (CCTV & LAN)Details of prepriced Schedule is given in tender documents |
| 14 | SCHEDULE \"A\" PART- XIV(STANDBY DG SET)Details of prepriced Schedule is given in tender documents. |
| 15 | SCHEDULE \"A\" PART- XV(AIR CONDITIONING )Details of prepriced Schedule is given in tender documents. |
| 16 | SCHEDULE \"A\" PART- XVI(DEMOLITION/DISMANTLING)Details of prepriced Schedule is given in tender documents. |
| 17 | SCHEDULE \"A\" PART -XVII (MISCELLANEOUS ITEMS)Note:- This scheduleis not pre-priced by MES and the pre-priced rate indicated as \"Rs 0.00\" under Col.\" F \" signifies this fact only. |
| 18 | ( SITE CLEARENCE, SITE DEVELOPMENT AND EARTH WORK)Bringing approved Earth/River bed material (RBM) from out side of MoD land n exc 15 km distance and forming embankments including raising RBM, spreading in layers not exceeding 30cm thick, waterning. Ramming/rolling finished to required shape n.exc 1.5m above the starting point complete all as specified and direccted. NOTE :- (i) Finished embankment shall be measured for payment purpose(ii) 10% shall be deducted from finished embankment for bulkage(iii) Quoated rates shall be inclusive of all taxes and royalities and nothing shall be paid extra. |
| 19 | INTERNAL ELECTRIC SUPPLYS&F flame proof weather proof DB, TPN 415 volt 4 way with bus bar and cast aluminium LM6 enclosure, operated externally spring type knob complete with M-25 cable entry to suit incoming cable and 2 Nos M-20 cable entries for outgoing cables from bottom with cable gland suitable for hazaraduous area certified by CMRS dhanbad for group II A & II B etc complete all as specified, consiting of :Incoming : (a) MCB TPN 25 Amps -01 NoOutgoing:(a)MCB TP 16 Amps -01 No (For 3 Phase metal plug socket)(b)MCB SP 6-32 Amps -8 Nos |
| 20 | S&F flame proof weather proof DB, TPN 415 volt 4 way with bus bar and cast aluminium LM6 enclosure, operated externally spring type knob complete with M-25 cable entry to suit incoming cable and 2 Nos M-20 cable entries for outgoing cables from bottom with cable gland suitable for hazaraduous area certified by CMRS dhanbad for group II A & II B etc complete all as specified, consiting of :Incoming : (a) MCB TPN 25 Amps -01 NoOutgoing:(a)MCB SP 6-32 Amps - 11 Nos |
| 21 | S&F flame proof wall fan/ air circulator 600 mm single phase including with cable gland completewith all accessories etc complete all as directed and as specified. |
| 22 | S&F flame proof metal plug socket 32 Amp 5 pin TPN 415 V including with cable gland completewith all accessories etc complete all as directed and as specified. |
| 23 | S&F flame proof exhaust fan 300 mm dia complete with bird guard louvers and complete with all accessories etc complete all as directed and as specified. (For Toilet in BP 2 Nos) |
| 24 | S&F flame proof ceiling fan 1200 mm sweep single phase including with cable gland completewith all accessories etc complete all as directed and as specified. |
| 25 | S&F flame proof ceiling fan regulator completewith all accessories etc complete all as directed and as specified. |
| 26 | S&F flame proof weather proof DB, TPN 415 volt 4 way with bus bar and cast aluminium LM6 enclosure, operated externally spring type knob complete with M-25 cable entry to suit incoming cable and 2 Nos M-20 cable entries for outgoing cables from bottom with cable gland suitable for hazaraduous area certified by CMRS dhanbad for group II A & II B etc complete all as specified, consiting of :Incoming : (a) MCB TPN 25 Amps -01 NoOutgoing:(a) MCB SP 6-32 Amps -8 Nos |
| 27 | S&F Emergency LED bulb 9 watt B22 230V AC with minimum 4 Hrs battery back up, 3 mode dimmable optional and over charging protection complete all as directed and as specified. |
| 28 | S&F Oscillating wall mounted anti dust, AC single phase 230V of size 400mm sweep with plastic blades, frame and louvers, swing type plastic body, speed control by pulling cord system, tilt adjustment for adjusting the fan at desired angle etc complete all as directed and as specified. |
| 29 | S&F MCB 230 V,50 Hz, SP, 40 Amps, 10KA \"C\" curve complete all as specified and as directed. |
| 30 | TERMAC/LINK TTM&L for 280 mm Thick pavement quality concrete (PQC) of minimum 28 days field flexural strength of 45kg/Sqcm or 4.5 Mpa, aggregate gradation as per Table 3 of IRC 15-2017, coarse aggregate of clean, hard strong, dense, non-porous and durable pieces of crushed stone or gravel, fine aggregates of clean natural sand or crushed stone sand or combination of bouth using minimum 360 Kg/cum of cement with non-circualr, virgin synthetic monofilament polyester fibres fibre of 12-18 mm length, specific gravity 1.34 to 1.39 UV stable alkali resistant, with equivalent dia 15-40 micron, minimum melting temparature250*C and minimum tensile strength of 300 Mpa to be used upto 0.25% by weight of cement or as per manufacturer specification, in design.All properties/ specifications to meet test parameteters as per IS16481: 2016.For details, refer Particular specifications issued vide this HQ Policy letter N0 95610/Policy/Mon/E2W(RI-I) dated 26 Oct 2020. Design Mix to be prepared after incorporating fibers. PQC laid, spread and compacted with slip-form paver of minimum 7.50m width, including curing and lining by texturing cum curing machine complete all as specified and directed. Required surface texturing to be done as specified in clause 10.1.14 and Table 9 of IRC 15-2017 |
| 31 | M&L for 400 mm Thick pavement quality concrete (PQC) of minimum 28 days field flexural strength of 45kg/Sqcm or 4.5 Mpa, aggregate gradation as per Table 3 of IRC 15-2017, coarse aggregate of clean, hard strong, dense, non-porous and durable pieces of crushed stone or gravel, fine aggregates of clean natural sand or crushed stone sand or combination of bouth using minimum 360 Kg/cum of cement with non-circualr, virgin synthetic monofilament polyester fibres fibre of 12-18 mm length, specific gravity 1.34 to 1.39 UV stable alkali resistant, with equivalent dia 15-40 micron, minimum melting temparature250*C and minimum tensile strength of 300 Mpa to be used upto 0.25% by weight of cement or as per manufacturer specification, in design.All properties/ specifications to meet test parameteters as per IS16481: 2016.For details, refer Particular specifications issued vide this HQ Policy letter N0 95610/Policy/Mon/E2W(RI-I) dated 26 Oct 2020. Design Mix to be prepared after incorporating fibers. PQC laid, spread and compacted with slip-form paver of minimum 7.50m width, including curing and lining by texturing cum curing machine complete all as specified and directed. Required surface texturing to be done as specified in clause 10.1.14 and Table 9 of IRC 15-2017 |
| 32 | SEWAGE DISPOSALM&L for RCC septic tank conventional type designed to carry sewage and sullage water, excavation in any type of soil, PCC (1:4:8) type D2, below foundation, RCC (M-30) Design Mix in walls, Base slabs, Baffle walls and Roof slab including beams etc with vent shaft, manhole openings with cover connection etc, complete with effective depth of 1.50 metre and over all depth of 3 metre for 50 users etc, complete all as per DRG NO AF/STD/STRU/265 SHEET NO 1/2 & 2/2, DT 24/04/2023. |
| 33 | M&L for Soakage wells for 50 users, excavation, in any type of soil, foundation in PCC (1:3:6) type C2,walls of honey combed masonry with top ring of RCC M25 (Design Mix) concreete indluding intercepting chamber and screen chamber made of Brick masonry in CM, RCC cover slab in M25/SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats of size not less than 2.40 M dia x 3.00 M effective depth etc, complete all as per DRG NO AF/TD/STRU/236 SHEET NO 1/2 & 2/2 DT 19/08/2014. |
| 34 | LIGHTNING PROTECTIONS&F MS Junction box for mounting Test terminal block including provision of passing earth strips from top and bottom of the box all as specified and directed.. |
| 35 | EXTERNAL WATER SUPPLYConstruction of brick masonry valve pit of size 60cm x 60cm x 60cm (internal dimensions) with one brick thick wall in cement mortar (1:4) on 100 mm thick PCC (1:4:8) type D2 (using 40mm graded crushed stone aggregate) as in foundation lean concrete, including PCC (1:3:6) type C-1 (using 20mm graded crushed stone aggregate) as in bedding and coping and 10mm thick cement plaster in CM (1:4) internally and externally up to 15cm below ground level including three coats of white wash on plastered surface providing valve pit 40 x 40 x 5mm MS angle iron frame all-round the fixed point by means of 4Nos holdfast 150mm long made out of flat iron 25 x 6mm embedded in PCC block (1:2:4) type B-1 (using 20mm graded crushed stoned aggregate) of size 230 x 200 x 100mm including provision of hinges welded with angle iron frame and MS cover 3mm thick, MS handle of suitable and size welded with MS cover and suitable locking arrangement including 65mm diapad lock and applying two coats of synthetic enamel paint over a coat of red oxide primerincluding necessary excavation and earth work, removing/returning filling in, any type of soil complete all as specified and directed. |
| 36 | EXTERNAL ELECTRIC SUPPLYSupply, installation, testing and commissioning of outdoor 11 kVpackage substation having outdoor type enclosure, modular construction of galvanised sheet steel minimum 2 mm thick with 4 mm base suitable for outdoor installation, consisting of HT VCB, cast resin/VPI dry type transformer, LT paneland capacitor panel with all interconnections, metering, protection, internal HT XLPE cable and LT copper bus duct suitable for short circuit current, internal earthing connections, type tested as per IEC codes including foundation etc. complete in all respects as required of following capacities, and as per single line diagram and specifications:- Vacum circuit breaker1 No. 11 KV 630A, 25 KA vacum circuit breaker enclosedin sheet steel tank with metering and protection of transformer, self powered microprocessor based numerical relays and dedicated CTs for protection of transformer.Metering and protection shall be as per single line diagram.Transformer 1 no. 100 KVA, 11 kV /0.433 kV Delta/Star, Dyn11, insulation Class-F, naturally cooled, dry type transformer with OFF load tap changer with - 5% to + 5% tapping in steps of 2.5% on HT side.LT Panel Incomer(a) 1 no. 200 A 415V 4P MCCB (35 kA) complete with necessary auto on/off mechanism , electrical and mechanical interlockingas required and as per drawing.(b) 2 set ON/OFF/TRIP indicating lamps.(c) 2 set LED phase indicating lamp with 2A SP MCB.(d) 2 no. multi-function meter,(e) 3 set 160/5A Class-1 CT for MFM & APFCR.(f) 1 no. Type I Surge Protection Device |
| 37 | Serial Item No. 29 (Contd....) Bus Bars 300A, 415V, 35 kA, 50 Hz, 3-phase, 4-wire, Aluminium bus bars,Outgoing(a) 02 no. 125 A, 4P MCCB, 35KA with electronic release (01 No spare)(b) 03 no. 40 A, 4P MCCB, 35KA with electronic release (01 No spare)(c) 10 set LED phase indicating lamp with 2A SP MCB.(d) 02 set 125/5A Class-1, CT ,(e) 02 set 0-125A Digital ammeter (f) 03 set 40/5A Class-1, CT ,(g) 03 set 0-40A Digital ammeter Capacitor Panel (30 KVAR)Incomer(a) 1 no. 100A 415V TP MCCB, 35KA with electronic release (b) 1 SetON/OFF/TRIP indicating lamps (LED).(c) 1 SetON/OFF push buttons. (d) 1 Set LED phase indicating lamps with 2A SP MCB.(e) 2 set100/5A Class-1 CT(f) 1 No. 0-500 V Digital voltmeter (g) 1 Set 0-100A Digital ammeter(h) 1 No. APFC relay Bus Bars 150A, 415V, 35 kA, 50 Hz, 3-phase, 3-wire, Aluminium bus bars Outgoing (a) 2 no. 32 A, 3P MCCB, 35KA with capacitor duty contactor, ON/OFF push buttons and LED indicating lamps. (b) 1 no. 20 A, 3P MCCB, 35KA without capacitor duty contactor, ON/OFF push buttons and LED indicating lamps. (c) 2 set 5 KVAR capacitor banks.(d) 2 set 10 KVAR capacitor banks. |
| 38 | Serial Item No. 29 (Contd....)Note:-This item inclusive ofProviding & fixing chainlink fencing as per given drawings. All earthwork, steelwork, painting, steel gate, PCC, removal of surplus soil within MOD land,sand, gravel etc all complete as directed by GE and cost deemed to be included in the quoted rate, nothing to be paid extra. |
| 39 | Supply, install, commissioning and testing double door factory madefloor mounted outdoor cubical type LT panel board of size 1.2m (height) x 1.0m (width) x 0.8m (depth), made out of 3.15mm thick CRCASheet and angle iron 50x50x6 mm frame facory made CPRI approved totally enclosed dust and vermin proof both side hinged opening arrangment on front and back with locking araggement cable entry and exist from bottom with cable glands and gaskets, aluminium bus bar of suitable rated fixed on porcelain insulator with internal wiring with suitable size of aluminium strips to be used for incoming and outgoing connections of all MCCB\"s & Bus-bar shall be insulated with colour code sleeves/ tapes and to be connected withAluminium lugs, including two coats of synthetic enameled paint on the surface externally & internally over a coat of red oxide primer paint incl necessary PCC (1:3:6 ) typeC2 in foundation all as directed ,comprisioning of the following:-.(FP - 2 Air crew rest room)Incoming:-(a)MCCB 4 pole, 160 Amps, 415 Volts35 KA - 01 No(b) Digital type Ampere meter 0-250 Amps with Cts & selecter switch - 01 Set(c) Digital type Volt meter 0-500 Volts with PTs & selecter switch - 01 Set (d) LED Indicating lamps for main supply indicating \"R\", \"Y\", \"B\" - 01 Set(Set of 3)(e) Aluminium Bas Bar rating 250 Amps - 01 Set(Set of 04)Outgoing:-(a) MCCB 63 Amps, 415 Volts 4 pole, 16/25 KA - 03 No(b) MCCB 32 Amps, 415 Volts 4 pole, 16/25 KA - 01 Nos (c) MCCB 16 Amps, 415 Volts 4 pole, 16/25 KA - 02 No (c) Digital timer switch panel with contactor and wiring complete - 01 No |
| 40 | Supply, install, commissioning and testing double door factory madefloor mounted outdoor cubical type LT panel board of size 1.2m (height) x 0.8m (width) x 0.6m (depth), made out of 3.15mm thick CRCASheet and angle iron 50x50x6 mm frame facory made CPRI approved totally enclosed dust and vermin proof both side hinged opening arrangment on front and back with locking araggement cable entry and exist from bottom with cable glands and gaskets, aluminium bus bar of suitable rated fixed on porcelain insulator with internal wiring with suitable size of aluminium strips to be used for incoming and outgoing connections of all MCCB\"s & Bus-bar shall be insulated with colour code sleeves/ tapes and to be connected withAluminium lugs, including two coats of synthetic enameled paint on the surface externally & internally over a coat of red oxide primer paint incl necessary PCC (1:3:6 ) typeC2 in foundation all as directed ,comprisioning of the following:-. (FP - 1 HAS 3) Incoming:-(a)MCCB 63 Amps, 415 Volts 4 pole, 16/25 KA - 01 No(b) Aluminium Bas Bar rating 100 Amps - 01 Set(Set of 04)Outgoing:-(a) MCCB 25 Amps, 415 Volts 4 pole, 16/25 KA - 03 No(b) LED Indicating lamps for main supply indicating \"R\", \"Y\", \"B\" - 01 Set(Set of 3) |
| 41 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 70 sqmm complete all as directed and as specified. . |
| 42 | Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 240 sqmm complete all as directed and as specified. . |
| 43 | M&L for boring of holes under road, pavement, hard standing mannually or by trenchless technology using ultra sounding technique and necessary machine or mannuallyetc as per site requirment including provision of 150mm dia HDPE Pipe suitable for 0.4 mpa working pressure etc complete allas specified and directed . |
| 44 | S&F LED Street light 36 W IP 65, 230 V powder coated pressure die cast aluminium compact high power with heat resistant toughened glass with 40 mm dia GI bracket, etc, complete with all accessories internally prewired and including connected with three core twisted flexible wire copper conductor cable of suitable size with system output of 120 lm/w. (Around the Air crew restroom) etc complete all as specified and as directed. |
| 45 | Supply and fix Cable Junction Boxes of size 155 x 210x 92 mmIP 66 (Grey) with integrated membranes / metric knockouts for cable entry for street light pole etc complete all as specified and as directed. |
| 46 | Supply, installation of Led flood light of capacity200 watt including all connected wiring of luminaries with all wiring material like PVC insulated with PVC sheathed flexible cable of suitable size with suitable lugs etc, The flood light luminaries shall be shall be gray epoxy powder coated pressure die cast aluminium housing (LM 24) with IP- 66 protection and elegently desiged heat sink for efficient thermal management, sturdiness and excellent corrosion resistant and cable gland is to be provided at cable entry for maintaining ingress protection with heat resistant clear toughened glass fixed to the frame with silicon gasket and SS screw with high efficiency long life LED chips in module with Ra more than 70 and lumen efficiency of 120 lumen per watt in-built electronic driver with APFC , colour temperature 5700k complete all as specified and directed. for \"Y\" dispersal area including foundation and fixing arrangement etc complete all as sprcified and as directed. |
| 47 | Supply, installation and commissioning 12.5 mtrs motorised high mast having provisionfor 100 watt 04 Nos LED FLOOD LIGHT LUMINAIRES thickness : Top- 3 mm, bottom -4 mm, Diameter : 150 mm, bottom 300 mm, wide spread 180 Km/Hr internal motor , 6 mm Hoisting SS ropes Drouble Brum Winch, Movable Landem Carriage , 5 core 4 sqmm Trilling Cable, Lightning FInal, Anchor Plate and template. Hot dip nGalvanised system internally and externally including necessary foundation, foundation bolts and nuts with including following with tow luminaire mounting arm, pulley assembly, including LED aviation obstruction lights, ligtening arrestor spike , monkey menace spike with including suitable timer panel RCC FOundation as per manufacturer instruction complete, suitable for 08 Nos 100 watt LED Flood lights all as specified and directed by Engineer-in-Charge.Note : Rate quoted shall be inclusive for necessasry earth work for installtion at any type of soil and following and Luminaires installed in HIgh Mast will be measured and paid separatelyNote :- 1. A vendal and weather proof door with provision to padlock is to be provided to have clear access to the base compartment equipments like winch, motor, cable, termination etc. The base flange welded to high mast shaft develops full strenghts of the section.2. Winches are completly self sustening with out the need of any break / spring / clutch, self lubricating by means of oil bath, worm gear driven of ratio 53:1 grooved drums for tidy an smooth rope lay. The winch is desined to install or remove through the mast door. Name plat is provided giving the details of type of winch, SWL, operating speed and year of manufacturing and instruction plate for the typr of the lubrivcating. |
| 48 | Serial Item No. 40 (Contd....)3. Stainless steel wire ropes in grade 304 or 36 in flexible 7/19 construction (central coreis also of same material ) of various diameter to have factor of safety more thn 5 specified in the TR No. 07 ropes for two wire rope, DD type winches have bothe ends with factory fitted talurit and thimble and copper crimpin.4. The standard luminary\"s carriages in two halves is of welded construction fabricated from durable round steel tubes for aerodynamic effect and to act as conduit with holes in bottom side to take the wiring flexible cable. Arms with circular profile for mounting luminaires are welded to the rin. HDG clamps ith SS hardware are provided to mount the CG boxes and balances the wirght on carraiges to avoid eccentric load. Legs are welded to anchor the wire rope for two or three ropes.5. Provision of lightening arrestor spike alongwith earthing connection and canopy to fix the hot dip galvanised ligtening final fabricated out of ERW tube. |
| 49 | Supply, installation of Led flood light of capacity100 watt including all connected wiring of luminaries with all wiring material like PVC insulated with PVC sheathed flexible cable of suitable size with suitable lugs etc, The flood light luminaries shall be shall be gray epoxy powder coated pressure die cast aluminium housing (LM 24) with IP- 66 protection and elegently desiged heat sink for efficient thermal management, sturdiness and excellent corrosion resistant and cable gland is to be provided at cable entry for maintaining ingress protection with heat resistant clear toughened glass fixed to the frame with silicon gasket and SS screw with high efficiency long life LED chips in module with Ra more than 70 and lumen efficiency of 120 lumen per watt in-built electronic driver with APFC complete all as specified and directed. |
| 50 | Removing of existing steel tubular pole at dispersal area including with LED light and LT UGcable depositing to MES store of for credit all as directed by Engineer-in-charge. |
| 51 | STANDBY DG SETSupply, installation, commissioning and testing of Water cooled diesel engine driven silent generating set with acoustic enclosure confirming to CPCB- IV+ norms of capacity 20 KVA415 Volts in 3-Phase 4 wire system at 1500 rpm.Engine shall be as per IS: 10001/ 10002 and alternator shall be as per IS: 4722 / IS: 13364 or relevant IS/SSR specifications mounted in common base complete with special AMF Paneland duly mounted with all necessary metering equipments, fuel tank and battery anti vibration mounting etc. and dimension as per standard design of manufacturrer including PCC foundation works as per manufacturer specification and making necessary Electrical connections by using lugs, nut bolt etc comprising with the following items/ spares as given in note below including PCC foundation of required size for keeping DG set complete all as specified and as directed . Make : KIRLOSKAR oil Engines or Equivalent of CUMMINS / ASHOK LEYLEND/Mahindra :-.Note: (a) DIESEL ENGINE : Water cooled , two cylinder for developing 27.8 BHP for run the alternator 20 KVA @ 1500 rpm. Engine shall be cooled by rail mounted engine driven radiator of adequate capacity , with blower fan, fan guard, fan belt, Alternator etc with an overload capacity of 10% for one hour of operation. Diesel Engine shall comply with latest CPCB norms i.e. CPCB IV+. Engine shall be fill up with manufacturer specified lub oil, Coolants etc in required quantity as per manufacturer specifications. (b) ALTERNATOR : Alternator shall be suitable forgiving output 20 KVA, 415 Volt, 3 Ph, 50 Hz, 0.8 PF (Lag) @ 1500 RPM&self excited Regulatedwith brushestype , The Alternator conform to IS-4722/ IS: 13364 and shall be suitable for tropical conditions. Full load efficiency of Alternator shall be not below than 90% & stator assy shall be copper wound with Class of insulation H. Enclosure shall be conform to IP-23. alternator shall be coupled with Engine suitable type couplings as per standard instructions of manufacturers. |
| 52 | Serial Item No. 44 (Contd....)(c) AMF CONTROL PANEL : Self supported indoor type totaly enclosed LT Panel board conforming to IS 8623, AC suitable for 3 phase, 4 wire, 440 volt, compartmental design, dust and vermin proof, made out of 2 mm thick CRCA sheet, cubical type, duly powder coated, IP-51 protection having front and rear hinged door, bottom detachable gland plate with holes for incomong and outgoing cable and control circuit diagram with colour code complete with following accessories :-(i) MCCB 32 Amps, 4 pole, 25 KA- 03 Nos (for main supply, generator supply and for changeover supply) (ii) 3 phase heavy duty power contactors 40 Amps , 415 volt, 4 pole 2 NO + 2 NC conforming to IS/ IEC 60947-4-1 & IEC 60947 -4-A complete - 02 Nos Protection Relays-(i)Microprocessor based DG Set power command module(ii) Under voltage relay(iii)Over voltage relay(iv)Differential relay(v) Combined O/C and E/F protection(vi)Over load protection(vii)Reverse power protection(viii) Field failure relay(ix)Master trip/ high speed tripping(x) Relay with auxiliary relay(xi)Excitation system protection relays (xii) Under frequency relay. |
| 53 | Serial Item No. 44 (Contd....) Metering & indication:-(i)Digital ammeter with selector switch-01 No(ii) Digital voltmeter with selector switch-01 No(iii)Digital frequency meter-01 No(iv)Electronic type 3 phase multifunction meters (Amp, volt, pf, Hz, KVA, KW, KWH etc)-01 No(v) DC amp meter for fixed / excitation current-01 No(vi)DC volt meter for fixed /excitation voltage-01 No(vii) Speed indicator (0-2000 rpm)(viii) Starting battery voltage meter(ix)Lubricating oil pressure meter(x) Engine coolant temperature indicator(xi)Float cum boost chargre equipment suitable for battery along with all input / output/ indication /instrumentation devices complete in all respect.(xii) Instrument fuses & control wiring.(xiii)Pilot lamps for \"Load on\" and \" Set running\"(d) Safety Alarm systems : safety alarm system for High Engine Temperature, Low lub Oil pressure, low water radiator level, low fuel level & Under/ Over speed. (e) Safety Trip/ Shut Down systems : safety trip system for High Engine Temperature & Low lub Oil pressure(f) Base frame :Suitabe Base frame made out with steel and totally enclosed type with salient design as per manufacturer standard design. (g) Fuel Tank :8 hrs capacity with fuel indicatorwith inlet and outlet arrengements , air vent&drain plug etc as per manufacturer standard design.(h) Batterry : 01 Nos X 12 V, 110 AH maintenance free with leads and connecting accossories - 01 Nos. |
| 54 | AIR CONDITIONERSupply and fix air cooled split inverter unit air conditioner electric driven single phase of capacity of 1.5 TR, BEE 5 star rated all as per specified and as directed. |
| 55 | Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 155 V to 270 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 4 KVA etc complete allas specified and directed |
| 56 | TAXI LIGHTSupply, laying, testing & commisioning of 1C x 6 Sqmm 5KV Grade XLPE insulated Airfield Lighting Cable with Stranded tinned/annealed Copper conductors, EPR/XLPE insulation having CPE/PE outer sheath of black colour complying FAA-L-824 Primary cable for 90 mtrs apron/taxiway Airfield lighting circuits etc complete all as specified and as directed.Make: EUPEN/ Nexans/ Aloke/ RR kabel Note:- Each light distance 10 RM |
| 57 | Supply and laying of HDPE Pipe 63mm OD Confirming IS14930, Part II 600 mm deep laying in soft soil all as specified and as directed.Make:Astral/ Gemini/ DuralineNote:- Each light distance 10 RM |
| 58 | Supply, fixing & commisioning of Taxiway Edge light 45 W , 6.6 A , elevated type Blue Dome Omini directional as per specifications and complete withh base plate, rubber gasket, nut, bolt & washers, breakable coupling with secondary leads and 45 W halogen Lamp with holder. The fixture shall be in comlaint with Annex. 14 , Volume I para 53.17 and FAA specification for light fixtures for Apron/ Taxiways with respect to materials, construction performance and testing etc completeall as specified and as directed. Make:AMA/ OCEM/ ADB safegate |
| 59 | Supply & fixing of TCI box round type of size 330mm dia ,450mm deep. Made of 10mm thick cast iron moulding, except top surface which is 15 mm thick suitable to recieve a lightfitting base plate on the top and undergroundhousing associated with transformer power cable and having 3/2/1 Nos holes as per site requirement on the periphery wall , centre 75 mm above bottom surface suitable to recieve 50 mm ID HDPE Pipe as required. The box should have 2 nos - SS earth bolts of M10 x 40 MM for Earthing tapped to recieve 15mm dia. of 100 mm lenght B-class GI & having clear opening of 220 mm at the top surface and 6 nos M10 tapped hole having centre distance of 260mm along with bolts all as specified and as directed. Note :- For 10 Nos new taxi light and 49 Nos for Existing taxi track light. |
| 60 | Supply, fixing & commisioning of Copper wound Series Isolating Transformer 45 W, 5KV rating with 1m secondary cable lead with plug type connector . The transformers shall be in complaint to IEC and ICAO Annex 14 notification. all as specified and as directed. Make: EFLA |
| 61 | Labour for removal/Taking out/Dismantling of existing taxi way, Dispaersal edge light,CI box,disconnecting all electric wiring including transportation to and from the Runway site upto store(with in 1 KM) for safe handling andre-installation , testing and commissioning of theTaxi way lights at new raised surface of Txiway/Dispersal/Links and making good the existing surface with adequite material to match the existing surface complete all as specified and as directed. |
| 62 | Supply and fixing of 6 sqmm 5 KV grade plug and receptacles of type I , class \"B\" connector for 6 sqmm primary cable all as specified and as directed. Make: EFLA/AMA/ADB surface.Note: - For 30 Nos against reapir/replacement and 10 Nos against new taxi track light. |
| SR No | FileName | File Description |
| 1 | Click here to download tender document | Tender Documents |
| 2 | Click here to download tender document | Tender Documents |
| 3 | Click here to download tender document | Tender Documents |
| 4 | Click here to download tender document | Tender Documents |
| 5 | Click here to download tender document | Tender Documents |
| 6 | Click here to download tender document | Tender Documents |
| 7 | Click here to download tender document | Tender Documents |