| 1 | Taking down carefully (aluminium) point wiring complete of any type (batten/surface conduit or concealed) for light point, fan point, bell point socket point or power point complete with all fitting such as switches, sockets pendants, ceiling rose, round block etc complete removing material to store of keeping in safe custody or for taking creditand making good disturbed surfaces of wall, floor or ceiling with plaster of tiles or roof treatment etc and finishing the surfaces with distemper/white washing/colour washing to match with the existing surface complete all as specified and directed. |
| 2 | Material and labour for point wiring includingconcealed in surface of structure/ truss etc rigid non-metallic PVC conduit pipe medium grade, ISI marked heavy duty in size 20 MM diawith 1.5 Sqmm FRLS insulated unsheathed, multi stranded copper conductor cable, single core 1100 volt grade with flush cast iron/ pressed steel terminal boxes of suitable size for fixingsuch as switches, sockets and fan regulators etc with modular cover plate and fixing with brass screws/cup washer and including FRLS insulated & unsheathed 1100 volts grade cable with multi stranded copper conductor of size 1.5 Sqmm as continous earth wire complete including making good the disturbed surfaces for the following:- Note:-Quoted rate shall be included cost of cheaseLing, cutting, plastering and colouring etc to surface of wall / beam/ roof etc as site requiredmatchingwith existed surface and blank plate to be cover up to extra gap in mountingboard in given module /make / model etc.(a) One light/ fan point controlled by one way indepdentswitch. |
| 3 | (c)One 3 pin 5 Amps socket out let point on same board controlled by one switch. |
| 4 | (d)One 3 pin 5 Amps socket out let point on independent board controlled by one switch. |
| 5 | (e) All as per above item No-2 here in before point wiring for 15 Amps socket using 2.5 Sqmm copper cable for phase and neutral and 2.5 Sqmm as earth wire complete. |
| 6 | All as per above item No-2 here in beforepower point wiring using 4 Sqmm copper conductor cable FRLS insulated unsheathed and unsheathed copper conductor of 4 Sqmm as earth wire complete. Note : All circuit shall be taken from seperate control DBs (connected with energy meter)to be connecting indivisual power load. |
| 7 | Supply and fix sheet metal enclosure, Single pole and neutral with a two pin and earth plug and socket for AC box complete with one single pole MCBfor 240V, 20Amp complete all as specified and as directed. |
| 8 | M&L for point wiring in PVC Casing & Caping single corePVC insulated unsheathed 1100 volt grade FRLS cable with multi stranded copper conductor of size 1.5 sqmm (Nominal area), fixed on walland on ceiling with GI saddles, GI screws, rowel plugs with all fittings including tee, junction boxesand drawing continuous earth wire with and including PVC insulated unsheathed 1100 volts grade cable with multi stranded copper conductor of size 1.5 sqmm (Nominal area) connected to earth dolly complete all as specified and as directed. one light point or one fan point controlled by one switch with cable 1.5 sqmm size |
| 9 | One 3 pin socket outlet, 5 Amps on the same board with cable 1.5 sqmm size other switchescomplete all as specified and directed. |
| 10 | One 3 pin socket outlet, 15 Amps on the same board with cable 2.5 sqmm size other switches complete all as specified and directed. |
| 11 | Supply and fix switch piano, flush type, single pole, one way 5 Amps complete all as specified and directed. |
| 12 | Supply and fixsocket combination 2 in 1, 5 pin 5 Amps flush type complete all as specified and directed. |
| 13 | Supply and fix Switch socket combination 2 in 1, 3 pin, 6 and 16 Amp flush type universal complete all as specified and directed. |
| 14 | Supply and fixing ceiling rose surface type 65 MM x 50 MM, 2 to 3 terminal complete all as specified and directed. |
| 15 | Supply and fixing modular switch , one way 6 Amps 1 module complete all as specified and directed. |
| 16 | Supply and fixingmodular switch, one way 16 Amps 1 module complete all as specified and directed. |
| 17 | Supply and fixingmodular socket 6 A, 2/3 pin combined 2 module complete all as specified and directed. |
| 18 | Supply and fixingmodular socket 16 A, 3/5 pin combined 2 module complete all as specified and directed. |
| 19 | Supply and fixingin replacement modular fan regulator step type 120W 2 module complete all as specified and directed. |
| 20 | Supply and fixing in replacement white cover plate with frame 3 module complete all as specified and directed. |
| 21 | Supply and fixing in replacementwhite cover plate with frame 4module complete all as specified and directed. |
| 22 | Supply and fixing in replacement white cover plate with frame 6 module complete all as specified and directed. |
| 23 | Supply and fixing in replacement white cover plate with frame 8 module complete all as specified and directed. |
| 24 | Material and labour for sub main wiring with two runs of single core PVC FRLS IS-694 cable with unsheathed multi-stranded copper conductor of size 06 Sqmm and drawing through in concelead rigid non metallic PVC conduit pipe medium grade heavy duty in suitable size with all necessary fittings including one run of FRLS insulated unsheathed stranded copper conductor cable of size 06 Sqmm as earth wire (green in colour) and connected to common earth dolly complete including taking down of old unserviceable sub main wiring including taking out to old unsv sub main wiring with accessories complete all as specified and as directed. Note : (i) Two run of 06 sqmmwith one run of earth with one run PVC conduit pipe shall be measured agaist one unit. (ii)Cost of cutting /chasing/ plastering /colouring etc as site shall be included matching to disturbed surface all as existed. |
| 25 | All as above item but here in before three run of4 Sqmm for phase, neutral and earth wire with suitable size concealed PVC conduit pipe complete all as specified and directed. |
| 26 | Material and labour for sub main wiring with two runs of single core PVC FRLS IS-694 cable with unsheathed multi-stranded copper conductor of size 06 Sqmm and drawing through in PVC casing caping in suitable size with all necessary fittings including one run of FRLS insulated unsheathed stranded copper conductor cable of size 06 Sqmm as earth wire (green in colour) and connected to common earth dolly complete including taking down of old unserviceable sub main wiring including taking out to old unsv sub main wiring with accessories complete all as specified and as directed. Note : (i) Two run of 06 sqmmwith one run of earth with one run PVC casing shall be measured agaist one unit. |
| 27 | All as above item but here in before three run of 4 Sqmm for phase ,neutral and earth wire with suitable size concealed PVC casing complete all as specified and directed. |
| 28 | All as above item but here in before three run of 10 Sqmm for phase, neutral and earth wire with suitable size concealed PVC casing pipe complete all as specified and directed. |
| 29 | Supply only PVC insulation tap in 25 mm width 25 Mtrs long suitable for upto 1.1 KV ISI marked complete all as specified and directed. |
| 30 | Supply and fixing in replacement LED Bulb 15 w including taking out to unsv oldcomplete all as specified and directed. |
| 31 | Supply and fix flame proofsheet metal enclosure for MCB distribution board SPN of size 330X350X190, 8 way with incoming MCB 2P ,32Amp outgoing MCB1P -10Amp-06Noswith complete internal busbar & wiring up to terminals. Note; Quoted rate shall be included cost of MCC, and fixing complete all as specified and directed. |
| 32 | Supply and fix sheet metal enclosuredistribution board TPN, 4 poles ,double door, 4 way with 200 Amps ratedbus bar vertcal type withMCCB 4 pole 100 Amps 415 volt thermal megnatic base operated as incomer incl concealed in surface of wall and making all connection using gland, thimbles in required size including taking down to old unsv DBs in any make/ model/ way etc with accessories complete all as specified and directedNote: Quoted rate shall be included cost of MCCB, cutting plastering, colouring to surface of wall to be concealedetcall site requiredmatching with existing surface. |
| 33 | Supply and fix sheet metal enclosure for MCB distribution board SPN, double door, 8 way with 200 Amp rated bus bar 230 Volts including taking down to old unsv DBs in any make/ model/ way etc with accessories complete all as specified and directed. |
| 34 | Supply and fix sheet metal enclosure for MCB distribution board SPN, double door, 4 way with 200 Amp rated bus bar 230 Volts including taking down to old unsv DBs in any make/ model/ way etc with accessories complete all as specified and directed. |
| 35 | S&F MCCB, 415 volt, 4 poles 63 Amps ,16 KA breaking capacity, thermal based adjustable type complete all as specified and directed. |
| 36 | Supply and fixing MCB, SPN, 2 pole 220 volts , 63 Amps, \"C\" Curve 10 KA complete all as specified and directed. |
| 37 | Supply and fixing MCB, SPN, 2 pole 220 volts, 32-40 Amps, \"C\" Curve 10 KA complete all as specified and directed. |
| 38 | Supply and fixing MCB, single pole 215 volts, 06- 40 Amps, \"C\" Curve 10 KA complete all as specified and directed. |
| 39 | Taking down old unsv Tube light fitting and S&F recess mounted LED fitting 36 watt LED luminiare size 2\" x 2\" with CRCA housing in white powder finish, high translucent PMMA diffuser provides soft glare free light suitable for surface/recess mountedopenable cleanroom luminiare with IP 65 with all accessories, pre-wired connecting up complete with 3 core flexible cable white of size 23/0.0076 complete all as specified and directed. |
| 40 | Taking down old unsv fitting and supply and fixing recess mounted LED downlight square/ round shape capacity 18 watt with PDC aluminium body and high transmittance diffuserand connecting up complete with 3 core flexible cable white of size 23/0.0076 all complete all as specified and directed. |
| 41 | S&F in replacement LED bollard 10 watt with coverage of 360º lighting area and IP65 protection luminaire, corrosion resistant complete with all accessories including making proper base structure for fitting complete all as specified and as directed. |
| 42 | Supply and fixing LED Post top light fitting 40 W energy saving heavy duty IP 65 protection including GI pipe light grade in suitable size grouting in brick wall to be fix light fittings using nut bolts clamps and making all electric connection using three core flexible copper cable of suitable size drawn through in flexible conduit pipe including taking down of old light fitting complete all as specified and directed. |
| 43 | Supply and fixing LED Tube light fitting 20 watt 4 feet with PC batten, compact appearance suitable for Retrofit LED Tube 20 watt including LED tube rod 20 watt self ballasted retrofit lamps with thermoplastic body 270 degree wide distribution CCT 6500 K including fitting fixed on wall/ceiling and connecting up complete with 3 core flexible cable white of size 23/0.0076 including taking down old unsv tube light fitting and making necessary connection complete all as specified and directed. |
| 44 | Supply and fixing in replacementLED tube light fitting with frame, driver etc in 10 W2 feet long white colour mounting on tow Nos of PVC round/ squire block on surface of wall / beam etc incl making all electric connection using three core copper cable drawn through in PVC flexible counduit pipe from ceiling rose to fittings including taking out to unsv old fittings complete all as specified and directed. |
| 45 | M&L for Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick surrounded with charcoal and salt, buried directly in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of plate not less than 1.5 metre below normal ground level connected to galvanized earth leadusing galvanised earth lead strip 25×4mm means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical Plate No 3 of MES SSR Part-I connected to main switch board or main control board all as specified and testing on completion including provision of earth wire protected by galvanized iron15 mm dia light grade pipe and watering pipe shall be 20 mm bore light grade including all excavation and earth work in any type of soil, PCC pit with pre-cast RCC cover, charcoal/salt, funnel etc complete all as specified and directed.(i) The concrete pit shall be PCC 1:3:6 type C-1, 40 mm thick pre cast cover slab of RCC (1:2:4) type B-1 using 20mm graded stone aggregate reinforced with 8mm TMT bars @ 10 cm C/C on both sides with suitable cast iron handle shall be provided in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I.(ii) Item includes the cost of 7.50m GI pipe for protection of earth wire/strip Any variation in length shall be adjusted through deviation order.(iii) Item includes cost of 7.50m earth lead wire/strip. Any variation in length shall be adjusted through deviation order.(iv)PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself and the extra cost of additional length of watering pipe, bends, elbow etc shall be deemed included in the unit rate. |