Supply Of Supply & Testing Of 750 Kva, 11/0.75 Kv, Step Down Transformer, Confirming To Is: 2026, Three Phase, 50 Hz, Oil-Immersed, Natural Cooled (Onan), Core Type, Double Wound With Copper Conductor Having No Taps, 50/55 Deg. Centigrade Temperature Rise In Oil And Winding Respectively, High Voltage Side Connected In Delta Whereas Low Voltage Side Connected In Star With Vector Group Referance Dyn11 With Neutral Of The Secondary Winding Brought Out For Earthing, Outdoor Type, Having Porcelaen Bushings On Hv And Lv Side Complete With First Filling Of Oil Complying With Is: 335 And Fittings And Accessories As Per Is:2026 As Applicable. Make: - Eastern Transformer, Kanohar, Stanelec Or Any Other Make/Brand Confirming To Above Technical Specifications.Supply & Testing Of 750 Kva, 11/0.75 Kv, Step Down Transformer, Confirming To Is: 2026, Three Phase, 50 Hz, Oil-Immersed, Natural Cooled (Onan), Core Type, Double Wound With Copper Conductor Having No Taps, 50/55 Deg. Centigrade Temperature Rise In Oil And Winding Respectively, High Voltage Side Connected In Delta Whereas Low Voltage Side Connected In Star With Vector Group Referance Dyn11 With Neutral Of The Secondary Winding Brought Out For Earthing, Outdoor Type, Having Porcelaen Bushings On Hv And Lv Side Complete With First Filling Of Oil Complying With Is: 335 And Fittings And Accessories As Per Is:2026 As Applicable. Make: - Eastern Transformer, Kanohar, Stanelec Or Any Other Make/Brand Confirming To Above Technical Specifications.,Supply & Testing Of 750 Kva, 11/0.75 Kv, Step Down Transformer, Confirming To Is: 2026, Thre E Phase, 50 Hz, Oil-Immersed, Natural Cooled (Onan), Core Type, Double Wound With Copper Conductor Havi Ng No Taps, 50/55 Deg. Centigrade Temperature Rise In Oil And Winding Respectively, High Voltage Side Conne Cted In Delta Whereas Low Voltage Side Connected In Star With Vector Group Referance Dyn11 With Neutral Of The Secondary Winding Brought Out For Earthing, Outdoor Type, Having Porcelaen Bu