| 1 | Wiring for light point/ fan point/ exhaustfan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required . GroupC |
| 2 | Wiring for circuit/ submain wiring alongwith earh wire with the followingsizeof FRLS PVC insulatedcopper conductor, single core cable in surface/recessed medium class PVC conduitconduit as required. (A) 2 x 2.5 sqmm+ 1 x 2.5 sqmm earth wire |
| 3 | Wiring for circuit/ submain wiring alongwith earh wire with the followingsizeof FRLS PVC insulatedcopper conductor, single core cable in surface/recessed medium class PVC conduitconduit as required. (B) 2 x 4 sqmm+ 1 x 4 sqmm earth wire |
| 4 | Wiring for circuit/ submain wiring alongwith earh wire with the followingsizeof FRLS PVC insulatedcopper conductor, single core cable in surface/recessed medium class PVC conduitconduit as required. (C) 2 x 6 sqmm+ 1 x 6 sqmm earth wire |
| 5 | Supplying and fixing 63 Amp, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 6 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (A) Single pole |
| 7 | Supplying and fixing 12 way , Double door, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 8 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 9 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 10 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings). |
| 11 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 12 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc.with charcoal/ coke and salt as required. |
| 13 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthingalong with existing surface /recessed as required conduit /submain wiring /cable as required. |
| 14 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 15 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 16 | Supplying and fixing modular TV antenna socket outlet on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 17 | Supplying and fixing modular Telephone socket outlet on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 18 | Supplying and drawing co-axial TV Cable RG-6 grade, 0.7 mm solid copper conductor PE insulator, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/PVC Conduit as required. |
| 19 | Providing and fixingof 12 W square LEDsurface ceiling light fitting, with premium diffuser to ensure glare free & even light distribution. (Make- Havells, Phylips etc as required. |
| 20 | Providing and fixing 20 watt 4 feet batten,single phase , 230 volt complete fittingi/c connection testing etc as required. Mak- Havells, Phylips, Crompton |
| 21 | Supplying and fixing mirror light 10 watt 2 feet LED batten cool day light (Mirror light) Complete set i/c connection etc as required.(Make- Havells, Philips,Bajaj |
| 22 | Providing and fixing 50 watt energy saving enviromentalfriendly long life LED flood light single phase , 230 volt complete i/c connection testing etc as required. Mak- Havells, Phylips, Crompton |
| 23 | Supplying and fixing of 300 mmmetal body exhaust fan complete set with louver (make crompton/Orient/Havell ) in the existing opening making the hole to suit the size of above fan making good the damage connection testing etc as required. |
| 24 | Providing and fixing of three pole 63 Amp MCCB 25 KA thermal magnetic in the existingpanel including connection etc as required. Make- L&T, schneider/Standard |
| 25 | Supplying and fixing offour pole Busbar chamber 100 Amp, 415 volt 50 HZ 4 way with connections, testing and commissioning etc as required.(Make :- Havells) |
| 26 | Suppying and laying of One number XLPE insulated and PVC Shealded Power Aluminium cable of 1.1 KV grade of cable size 2 x16 sqmm core armured cable make:-Havells as required |