Tender For Annual Repair & Maintenance Of 11 Kvsub Station And External Feedr Panel Equipments For The Year 2025-26 At 39Th Bn Itb Police, Greater Noida. (Up).; 1 Annual repair & Maintenance of 11 KVSub station and External Feedr Panel equipments 2 Servicing of oil cooled Transformer of 11KV 1000KVA, the scope of work includes:• Dehydration and filtration of oil for removal of suspended particles Such as colloidal particles, carbon Oxidation, sludge, and degassing. The dehydration shall be done under vacuum, circulation of heated oil, de acidification by evaporation and absorption method to provide longer life to the transformer.• Oil leakage removed by tightening all connections and nuts & bolts.• Removal of oil and WTI prods to check and topping up oil• Repair of oil leaks from Top Gaskets, Side gasket, Buchholz Relay, cable box.• Testing of OTI, WTI, Buchholz Relay for Alarm and Trip• Tightening of grounding connection of neutral & body• General cleaning (outside) 3 Servicing of oil cooled Transformer of 11KV 800KVA, the scope of work includes:• Dehydration and filtration of oil for removal of suspended particles Such as colloidal particles, carbon Oxidation, sludge, and degassing. The dehydration shall be done under vacuum, circulation of heated oil, de acidification by evaporation and absorption method to provide longer life to the transformer.• Oil leakage removed by tightening all connections and nuts & bolts.• Removal of oil and WTI prods to check and topping up oil• Repair of oil leaks from Top Gaskets, Side gasket, Buchholz Relay, cable box.• Testing of OTI, WTI, Buchholz Relay for Alarm and Trip• Tightening of grounding connection of neutral & bodyGeneral cleaning (outside 4 Service charges for OLTC oil dehydration and annual maintenance.The scope of work includes• Removal of complete oil by filtration machine, general cleaning inside by removing top cover, lubrication of moving parts, tightening loose connection, tightening of inter connector joints between transformer & OLTC, refilling oil by filtration machine and finally oil filtration.• Wiping the tap position indicator dial switch fixed studs clear and smearing a little.• Greasing of all gear teeth, Geneva locking Faces.• Checking the general condition of Main Spring, particularly checking elongation if any holes in the end fittings through which the spring passes checking the general condition of Main Spring.• Particularly checking elongation if any holes in the end fittings through which the spring passes.• Checking the tension of the drive motor Belt, if necessary, remove one link to reduce the slack. 5 Supply and replacement of the silica gel breather. 6 One-time annual periodic onsite test of Transformers such as • Winding Resistance Test, • Breakdown Voltage Test, • Insulation Resistance Test, • High Potential Test• Magnetic Balance Test 7 Supply of Fresh Transformer oil (as reqd.) 8 Servicing of 11KV VCB, the scope of work includes• Cleaning of HT Breaker with CRC-226 and dusting out• Removal of old grease and re-greasing the same with recommended grease• Checking condition and alignment of jaw Contact• Cleaning the operation mechanism including spring mechanism/motor operation, limit switches etc., of the Breaker.• Checking and proper tightening of hardware• Checking motor operation and mechanism.• Checking of auxiliary contacts continuity proper change over• Checking, cleaning bushings/ Insulators/ Spouts.• Checking the internal wiring of the unit includes metering, indication lamps, switches. 9 Charges for testing of 11KV HT Breakers.Primary Current Injection TestHigh Potential TestInsulation Resistance Test 10 Supply of 11KV Current Transformer 11 Supply of 11KV Potential Transformer 12 Service charges for the removal of damaged CT & PT and installation/ Testing/ Commissioning of new supplied CT & PT. 13 Service charges for Main LT Panel, length 15mtr approx.The scope of work includes General cleaning, dusting out, physical inspection, tightening of connections, tightening of earth connections, MCCBs, MCBs, control wiring and other wirings, opening and closing of Covers, share observation reports 14 Service charges for ACBs, 1250A, Legrand.The work scope includes• General cleaning, dusting out, tightening of connections,• Cleaning of parts• Tightening of Aux Connection• Earthing joints• Checking alignment of jaw contacts with cradle terminals• Operation Check• Mechanism of breaker• Decarburization of contacts• Checking of arc chutes and Paper impression test of contacts• Checking of ACB operation through shunt release• Lubrication of Moving parts 15 Service charges for Main Capacitor Panel, length 2-3mtr approx.The scope of work includes General cleaning, dusting out, physical inspection, tightening of connections, tightening of earth connections, MCCBs, MCBs, Contactors, Capacitors control wiring and other wirings, Testing of all the capacitors, Relay Programming etc. 16 Service charges for Main LT Panel, length 3mtr approx.The scope of work includes General cleaning, dusting out, physical inspection, tightening of connections, tightening of earth connections, MCCBs, MCBs, control wiring and other wirings, opening and closing of Covers, share observation reports.