Provn of transformer for ASC in North Camp, Provn of 15 mtr high mast lights in West Camp, Provn of electricity supply to shelters in East Camp and Spl repair to LT panels and connected works in North & South Camp at MFFR under AGE(I) MFFR.; 1 Supply and installation, testing and commissioning of transformer of capacity 250 KVAstep-down, Level-3, outdoor type copper wounded 11/0.433KV (at no load ) AC 3 phase, 50 HZ on secondary side double wound oil immersed naturallyair cooled with external cooling tubes/ radiator, delta connected as on primary and star connectedin accordance with vector group DYN-11 with neutral brought on secondary side and having tapping at (+/-) 2.5%, (+/-) 5%, (+/-) 7.5% to be changed by hand operated OFF LOAD tap changing gear. The maximum temperature rise should not exceed 45 degree centigrade in oil and 50 degree centigrade in HV/LV winding when measured by the resistance method after continuous full load run in ambient temperature the transformer shall conform to IS 2026. 1997 and comprising of following accessories:- 2 03 Nos porcelains HV bushing with arching horns on HV side suitable for 11 KV complete with bushing rods nuts. 3 01 No cable end box on LV secondary side consisting of 04 nos porcelain bushing with bushing rods and nuts washers and cable glands suitable for reception of 3.5 core 400sqmm cable, 2 runs, LT 1100 V grade XLPE insulated heavy duty including gland joint complete. 4 Oil conservator with filter type drain valve and oil level gauge. 5 Dehydrating breather with first filling of dehydrating agent. 6 Explosive vent. 7 THERMOMETER pocket. 8 Two earthing terminal on tank body to facilitate fixing of 32x6mm copper strips 9 One No thermometer dial type vapour pressure type having range 0-120 degree centigrade with maximum temperature indicator and re-setting device to maximum temperature including needle of temperature gauge : Max reading painted terminal. 10 Rating plate with terminal plate. 11 Oil level gauge. 12 Oil filling hole on top cover with plug. 13 Air release valve/plug. 14 4 Nos plain solid cast steel detachable rollers. 15 Extra bushing for neutral outside the cable box and providing independent earthing for neutral. 16 First fill of transformer oil conforming to IS 1180 and tested upto 60KV dielectric strength. 17 M&L for platform for transformer of size 3.0x3.0x1.5m high from GL including excavatiion in trenches not less than 1 mtr, PCC 1:5:10 type E2 for foundation, brick work in CM 1:6, PCC 1:2:4 type B1 in coping, plaster 10mm thick in CM 1:6, PCC 1:2:4 type B1 , 100mm thick as in flooring using extra cement over 75mm thick PCC 1:4:8 type B1 sub base, including returning filling , removal of surplus soil, 2 Nos ISMB 100mm channel for fixing transformer and fancing of transforner including ramp of suitable size mounting of transformer complete all as specified and as directed 18 M&L for Prestressed concrete pole, 11 metres long, 152 mm x 152 mm at top and 152 mm x 260 mm at bottom,class 9 including painting with two coats of synthetic enamel paint (in alternate black & white/yellow strips of 30 cm height) upto 1.5 meter height from top of PCC coping and also including numbering to poles with synthetic enamel paint on black base of size 15 cm x 10 cm and numbering in 8 cm height of number with white paint incl required iron channels/clamps/GI pipe for the protection of flexible cable connecter box with bus bars, bolts & nuts complete all as specified and as directed. 19 Supply, installing and testing of Lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 Kilo Amp capacity suitablefor 11 KV complete all as specified and as directed. 20 M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections, including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and as directed. 21 S&F Switch air break, gang operated outdoor, Horizontal operatedtype, HT 11 KV, Triple pole, 200 Amps, 3 insulator per phase, tilting/rocking horizontal type, with fixed contacts of phosphorous bronze and moving contacts of copper, manually operated from ground level with operating mechanism including GI tubing medium grade 25 mm bore operating rod, pad locking arrangements, MS arcing horns, flexible braiding earthing blades, rod and contacts without drop out fuse assembly and jumpers with Mink conductor line, taps, clamps, colour coated HT sleeves and fittings suitable for horizontal mounting, complete all as specified and as directed. 22 M&L for Danger notice plate of size 25cm x 20 cm x 3 mm thick of mild steel sheet, vitreous, enameled white, with letters, figures and conventional skull & bones in signal red colour and fixed with MS clamps made out of 25mm x 3mm MS flat iron including bolts and nuts of approved size for HT 11000 volts, complete all as specified and as directed. 23 S&F Anti-climbing device spikes type fabricated out of M.S. bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole complete all as specified and as directed. 24 Supply, laying & testing of XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminum conductor,11000V grade, of cross section area95 sq mm 3 core complete all as specified and as directed. 25 S&F cable jointing kit for 11 KV grade (Earthed) cable for outdoor terminal heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of 95 sq mm,outdoor complete all as specified and as directed. 26 M&L for Cable route indicator showing HT Cable and route/joint of cable with arrow made of PCC 1X2X4 type B1 duly rendered with plaster 10 mm thick of size 40 X50X20cm fixed and erected on PCC plateform of sixe 40X40X10 CM goruted in grounts duly painted on both sides with HT Cable Route complete all as specified and as directed. 27 Supply, laying and testing of cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor complete all as specified and as directed of following sizes:- 28 185 Sqmm 3.5 core. 29 150 Sqmm 3.5 core. 30 120 Sqmm 3.5 core. 31 95 Sqmm 3.5 core. 32 70 Sqmm 3.5 core. 33 50 Sqmm 3.5 core. 34 35 Sqmm 3.5 core. 35 35 Sqmm 2 core. 36 25 Sqmm 4 core . 37 25 Sqmm 2 core. 38 16 Sqmm 4 core. 39 16 Sqmm 2 core. 40 Excavating in trenches, not exc 1.5 metre wide and not exc 1.5 metre in depth, for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, laying cables, pipes, etc. not exc 10 Sqm on plan & not exc 1.5m in depth and getting out in soft/loose soil complete all as specified and as directed. 41 Returning, filling in, including spreading, leveling watering and well ramming in layers not exc 25 cm thick in soft/loose soil complete all as specified and as directed. 42 Removing excavated soil/material to a distance not exc 50 metre and depositing where directed at a level not exc 1.50 metre above the starting point complete all as specified and as directed. 43 All as per Srl item No. 15 here in before but exc 1.5m and not exceeding 3.0 in depth complete all as specified and as directed. 44 Boring of holes under road, pavement, hard standingby manually without damaging of road, material & labour includingpipe 80 mm dia suitablecomplete all as specified and as directed.Note; length of pipe to be measured and paid seperately under relavant item. 45 M&L for PCC 1:4:8 type D2 using 40mm graded crushed stone aggregate as in foundations of poles, filling, mass concrete and similar works, complete all as specified and as directed.Note : Volume of pole/strut embedded in concrete shall be deducted for the purpose of payment. 46 M&L for cement concrete 1:2:4 type B1 using 20mm graded crushed stone aggregate as in copings, pedestal of poles and the like including use and waste of form work (straight or curved), all exposed surface of concrete finished even & smooth without using extra cement, complete all as specified & as directed.Note : Volume of pole/strut embedded in concrete shall be deducted for the purpose of payment. 47 S&F GaIvanised steel tubes of size 80mm, light grade with all fittings laid in trenches complete including cutting and thereading all as required at site complete all as specified and as directed. 48 S&F double wall corrigated pipe of outer dia 120mm and inner dia 103 mm for cable protection as per IS-16205 complete all as specified and as directed. 49 All as per Srl item No. 21 here in before but outer dia 50mm and inner dia 38 mm complete all as specified and as directed. . 50 Supplying and laying synthetic insulating rubber mat for electrical installations, ISI marked of IS:15652 and of size 2 mtr x 1 mtr x 2.5 mm suitable for 11 KV system complete all as dirceted. 51 Supply, installing, commissioning and testing of LT panel board outdoor type,cubical type made out CRCA sheet 3.15 mm thick dust and vermin proof and panel shall be mounted on angle iron frame andlegs made from angle of size 50x50x6mm, pedestal flame grouted in PCC (1:2:4) type B-1 20 mm graded stone aggregated thimble and cable entry boxes with cable glands. Panel should covered from all sides with front and back lockable door and hinges complete with aluminum bus bar of 600Amprs,coil CT ratio100/5A,(in separate chamber) including painting with two coats synthetic enameled paint over a coat of red oxide primer and consisting of the following:- 52 MCCB400 Amp , 4 pole,36 kA-01 Each . 53 MCCB250Amp , 4 pole,36 kA -02 Each. 54 MCCB160Amp , 4 pole,36 kA -01 Each. 55 Digital Amp meter (0-600)-01 Each. 56 Digital Volt meter (0-500) -01 Each. 57 RYB Indicator-01 Set. 58 Supply, installing, commissioning and testingof LT BUs Barboard outdoor type,cubical type made out CRCA sheet 3.15 mm thick dust and vermin proof and angle iron of suitable size, pedestal flame grouted in PCC (1:2:4) type B-1 20 mm graded stone aggregated thimble and cable entry boxes with cable glands. Panel should covered from all sides with front and back lockable door and hinges complete with aluminum bus bar of 300Amprs,coil CT ratio 100/5A with provision of 6 way outgoing connection ,(in separate chamber) including painting with two coats synthetic enameled paint over a coat of red oxide primer and consisting of the following:- 59 On load change over switch 250A. 60 MCCB160Amp , 4 pole,36 kA -02 Incoming (Main & DG Supply). 61 Digital Amp meter (0-250)-01 Each. 62 Digital Volt meter (0-500) -01 Each. 63 RYB Indicator-01 Set. 64 Supply, installing, testing and commissioning of factory made floor mounted LT cubical panel confrming to CPRI specification board out type (double door) made out of 3.15mm thick CRCA sheet totally enclosed with necessary ventilations, weather, dust and vermin proof IP-53 minium with front and rear opening and locking arrangement 415Volts, 3 phase, 50 Hz having aluminium bus bar of capacity 125Amps and of suatable size to house all LT switch gears and accusories as mentianed below and full neutral duly colour coded and for neutral supported with DMC/SMC insulators colour codedcomplete connection from bus bar to MCCB with suitable copper cable, panel board shall be grouted in the ground with suitable size of foundation in PCC 1:2:4 type B1, MS channels for base frame 50x50x6 mm and supports, GI nut, bolts, washers etc.The panel board shall be powder coated and red oxided primed :- 65 The following items are provided in one compartment :-(i)Digital Voltmeter - 01 No, (ii)Digital Ameter - 01 No (iii)Three Indication LED Lamp 66 Incomming - 67 MCCB 4P, 63AMP, 25 KA -01 No 68 Out going :- 69 (i)RCCBFOR EARTH LEAKAGE, OVERLOAD & SHORT- CIRCUIT PROTECTION 4P,100mA, 40 Amp -05 Nos,(ii) onload change over 100A FP-01 70 M&L for Earthing to Transformer / GOD switch / equipments / panels etc with & including galvanised mild steel earth plate electrode of size 60 cm x 60 cm x 6 mm thick buried vertically in ground (earth pit not less than2.25 m below normal ground level) with top edge of the earth plate at a depth not less than 1.5 m below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, connected to & including galvanized mild steel strip 32x6 mm as earth lead, including nuts, bolts, check nuts & washers of galvanized iron or steel and riveted/welded to earth plate at one end and other end of strip connected to transformer / GOD / Panel / equipment body / test point with two Nos nuts bolts or welding with steel structure, GI earth strip encased in and including 40mm bore GI light grade pipe with all fittings from upper edges of earth plate upto 7.5 metre above ground level fixed with and including providing watering pipe 20mm bore GI pipe medium grade from earth pit to top of electrode and including funnel, wire mesh, copper lugs etc complete with earth pit in PCC 1:3:6 type C1 using 20mm graded crushed stone aggregate and 40mm thick RCC (1:2:4 type B1) cover complete all as specified and shown in electrical plate No 3 of SSR Part-I including necessary excavation and earthwork in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance not exc 50m complete all as specified and as directed including dismantling & taking out old existing unserviceable earthing.Note : PCC chamber shall be constructed at least 1.5 mtr away from the earth electrode and pipe for watering shall be provided in slanting manner. 71 M & L in replacement for Earthing complete with galvanised steel earth plate electrode 60cm x 60cm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 metre depth below normal ground level) with top edge of plate at a depth not less than 1.5 mtr below ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides, connected to galvanized earth wire 04 mm dia with and including bolts, nuts, check nuts and washers of galvanised iron or steel and riveted to earth plate and one end and connecting to main switch board or metallic bodies of HT/LT equipments etc at the other end, GI wire encased in and including 15 mm bore GI light grade pipe with all fittings, from top of electrode to body of equipment fixed with and includingflatiron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI light grade and including funnel, wire mesh, copper lugs etc from bottom of earth pit to top of electrode complete with earth pit in PCC 1:3:6 type C-2 using 40 mm graded crushed stone aggregate and CI cover complete all specified and shown in electrical plate No 03 of SSR Pt-I connecting earth electrode to test point with and including earthing lead including neessary excavation and earthwork in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance n.exc 50m, material and labour complete all as specified and as directed. 72 M&L for GI strip of size 32x6mm as earth continuity conductor burried in ground or drawn in pipe or fixed to wall on saddle complete all as specified and as directed. 73 M&L for cable end box jointing kit suitable for LT UG cable of size 16 Sq mm 3½ core to 25 sqmm3½ core including cuting,stripping the cable and connection etc complete all as specified and as directed. 74 M&L for cable end box jointing kit suitable for LT UG cable of size 95 Sq mm 3½ core to 150 sqmm3½ core including cuting,stripping the cable and connection etc complete all as specified and as directed. 75 M&L for 40mm graded coarse stone aggregate, deposited, spread and leveled in layers not exc 15 cm thick, rammed to a true surface, under 2/4 pole structure and around the 2/4 pole structure & outdoor electrical installations, complete all as specified and as directed. 76 M&L for Brick work with fly ash bricks old size straight or curved on plan exceeding 6m mean radius built in CM 1:6 complete all as specified and as directed. 77 Supply & installation of Galvanized steel high mast lighting system of 16 meter in two section hot dip galvanised as per BS - 729 in single dip with logitudinal weld and without any circumferential weld, suitable for wind velocity 180 KMPH as per IS : 875/1987 (Pt-III)3 mm section thickness, top dia 150 mm,bottom dia 300 mm . It shall also include accessories of high mast including head frame cast aluminium pully suitable for trailing cable and wire ropes with bush bearing and stainless steel spindle povided with guides, separators and adjustor to prevent ropes and cables with 2/3 wire rope system and its accessories. Pully assembly to be housed in chasis integral with 6 mm 316 grade ss hoisting ropes of 7/19 construction hacing factor of safety more than 5 in the TR No.7 rope for 2 wire rope. DD type winches having both end with factory fitted talunt and thimble. Copper cripping with single drum winch galvanised lantern carriage arrangement suitable for 6/9 luminaries symmetrically and control gear box and lightening finial pole design BS 5649 CP-3 steel grade BSEN shape mast shall be hexagonal including the following:-(a) Provision of construction of RCC foundation as per manufucture requirement for 15 mtr high mast bolt, bolt dipped galvanised high tensile stud with nut ,washer, anchor plate to cast into the foundation is suppliedfor each mast complete template is provided for precise setting the bolts. 78 (b) Errection commissioning of the high mast with the help of suitable T&P/Equipment.(c) Design and casting of suitable shallow foundation as per manufacture requirement with M-25 design mix concrete for the high mast.(d) Twin dome LED aviation light luminari comprising of aluminium hosing with polycarbonate enclosure and LED lamp.(e) Control panel suitable for switching and up-down operation of mast including suiatble size digital voltmete and ammeter with built in selector switch, CTs and indicator lamps.(f) Copper Trailing cable 5 core 2.5 sqmm of suitable length as required for installation of high mast. (g) Manual and electric operation Non flame proof integral motor as per manufacturer design with gears, rope, double drum winch andmovable lantern carriage for up and down operation.(h) Wiring of fixture with copper wire 3 core 1.5 sqmm, flexible conduit and copper lug. Note :Contractor shall be submitt the high mast drawing with foundation detail as per menufracture for approval of accepting officer. 79 Supply and fixing in replacement of LED based Flood lights, housing made of pressure die cast aluminium alloy with effective thermal management sturdiness. The fixture should have a minimum system efficacy of more than 110 lumen/Watt and a minimum system lumen output of not less than 7600 lumens and maximum system wattage 170 watts.The fuxture shall have a color temperature of minimum 5700 k at a CRI of minimum 70.The fixture shall be designed for a system life of 50,000 hours @ 70% lumen maintenance, lngress protection of IP66 (lamps and gear compartment and Mechanical Impact) Resistance Rating of IK>= 05.The fixture should comply with the parameters as per IEC 60598 and IS 10322, and LED drive should apply to IEC 61000-3-2 ed 3.2. per haronics IEC 61347-2-13, 2006 in confirmation with IEC 61347-1 ed, 2.0, 2007 for electrical safety, LM 79 and LM 80 test report needs to be sumittedabove parameters.The fixture driver should have an operating voltage range of 140-300V, frequency 50-60 Hz, surge protection not less than 4KV, PF>0.95 and THD<15%.The driver should have double phase protection.LED lights fitting should be suitable for ambient temperature from (-) 10 digree C to (+) 50 digree C, including street light GI bracket 40 mm dia bent to shape 1200and down 15mm Bore GI pipe with GI clamps with junction box for fixing LED lightrequired, with suitable size clamp, nut bolts and washers as per site requirement complete all as specified as directed. (Note-The manufacture of LED fitting shall give Guarantee for 2 years from the date of installation and complete fixed with suitable bracket & Accessories). 80 M&L for Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using galvanised iron strip 25×4mm as earthing leadby means of bolts, nuts check nuts and washers of GI or steel and connecting to earthing test point, main switch board, testing on completion includingGI pipe 20 mm dia mediumgrade for watering and bringing the same upto 30 cm above normal ground level with plug at top including pipe fittings etc complete and GI pipe 40 mm dia light grade for the protection of GI strip from earth pit to earth point complete including necessary excavation and earth work in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance n.exc 50 m all as specified as shown in electrical plate No 2 SSR Part-I complete all as specified and as directed. 81 M&L for installation, commissioning & testing of LT panel board (outdoor type) double door fabricated 3.15 mmthick CRCA sheet, duly powder coated,dust and vermin proof, totally enclosed metal clad, cubicle type accessible from front and rear side both with locking arrangement 3 phase 4 wire system at AC 440 volts, 50 Hz, indoor type applied with two coats of vsynthetic enamelled paint and mounted on angle iron of size 50x50x6 mm grouted in PCC foundation and suitable to house the following accessories;- 82 Aluminium bus bar of capacity duly covered with colour coded shrinkable sleeves not less than 200 Amps for phase and 100 Amps for neutral - 01 set. 83 Voltmeter AC 3 phase, 415 volt, digital type flush pattern 0-500 volts with selector switch- 01 No. 84 Panel indicating lamp neon/LED type (red,yellow&blue) with lamp holders - 03 Nos. 85 Panel internal wiring with FRLS2.5 Sqmm copper wire single core - 01Job. 86 MCCB 63 Amps, 4 pole Make- Legrand ( as incoming ) -01 No. 87 MCB 63 Amps TPNMake- Legrand ( as outgoing ) -01 No. 88 Contactor of capacity 32 Amps Make- L &T - 02 Nos. 89 S&F of automatic street light switch using infrared sensor based Nture Switch-, 25 kw equally distributed,63 Amps,3-pole,Model - Swadeep-02 EC 25 Kw3Pfor automatic switching of street lights based on LUX level of natural light . The sensor(Nature switch ) along with suitable power contactorrating 63 Amps 3- pole & 40 Amps 2-pole, MCB SP 63 Amps -03 nosand support terminals should be enclosed in pole/wall mountable enclosure made of rust proof ,electric shock proof, termite proof and FR grade SMC Junction box (Sintex make) confirming to IP54.The contactor suitable to 3- phaseload of 25 kw , rating 63 amps 3pole, MCB rating 63 amps SP 03 NOs complete all as specified and as directed. 90 S&F of double wall corrigated pipe of outer dia 77mm and inner dia 63 mm for cable protection as per IS-16205 complete all as specified and as directed. 91 S&F factory made Octogonal Hot rolled steelpole confirming to IS 2062/BSEN 10025 with hot dipped galvanised finishing of 7 mtr long with mild steel base plate grouted alongwith foundation by means of 04 Nos M20 x 600 LG foundation bolts including single swan neck backet and one MCB for switching the light on and off inside the pole complete all as specified and as directed. Note:- (i) Excavation,earth work shall be measured and paid separately under appropriate Sch.(ii) RCC M-20 and steel for foundation shall be as per OEM recommendation and drawing which shall be deemed to be included in the quoted rate. 92 S&F of 35Watt LED street light fitting of following Wattage 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and as directed. 93 M&L for Cable PVC insulated PVC unsheathed un-armoured flexible copper conductor (multi stranded) of cross sectional area 2.5 sqmm 2 core all as required for connections to light fittings complete all as specified and as directed. 94 Supply, installing, commissioning and testing of LT panel outdoor type,double door front and back both openable, cubical type made out CRCA sheeet 3.15 mm thick dust and vermin proof and angle iron of suitable size, pedestal flame grouted in PCC (1:2:4) type B-1 20 mm graded stone aggregated thimble and cable entry boxes with cable glands, bus bar should covered from all sides with front and back , complete with 200 Amps (3phase) & 200 Amp (Neutral) rated aluminium bus bar of suitable size, including painting with two coats synthetic enameled paint over a coat of red oxide primer and consisting of the following:- 95 MCCB 100 Amp, 4 pole, 415 V, 25 KA-01 Each (01 In-coming). 96 Digital Amp meter (0-250) -01 Each. 97 Digital Volt meter (0-500)-01 Each. 98 RYB Indicator -01 Set. MCB TPN 63A FP-02 Nos Outgoing. 99 M&L for Earthing complete with galvanized steel perforated pipe electrode 40mm boreburied directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meter below normal ground level connected to galvanized iron strip 32x6mm as earthing lead by means of bolts, nuts, check nuts and washer of galvanized iron or steel all as shown in electrical plate No 3 of SSR Part-I connected to panel/pole/bus bar complete all as specified and testing on completion, including provision of earth wire protected by 40mm dia GI light grade protection pipe from test point to main board and 20mm GI medium grade watering pipe funnel, PCC earth pit and RCC cover charcoal, salt and GI wire including excavation and earth work etc complete all as specified and as directed. 100 Supply, errection,commisioning and testing in replacement ofLT panel pillar box cubical type ofcomprising size (Panel box size), with bus bar chamber having 4 wire 415 Volts, CPRI type tested factory made dust proof vermin proof for out door use made out of CRCA sheet 3.15 mm thick powder coated, machine pressed, both side opening with double door (front & rear) in two shalves with provision of rubber beadings and locking system, danger Notice board infront and rear sides including insulated aluminium bus bar of 1.6 times of main incomming MCCB capacity in Amp, 4 stripmounted on porcelain insulator, bus bar chamber shall be provided with inspection covers, each MCCB/ cubical switch shall have be independent opening , panel shall be mounted on angle iron frame andlegs made from angle of size 50x50x6mm , frame and legs duly spray painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, legs grouted in PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) complete including all connections/control wiring incoming/out going with suitable size of copper conductor cable complete.Foundation is not less than 30 cm below ground level and not less than 45 cm above ground level, legs of panels will be grouted in centre of PCC foundation centre place will be open for connection of Under ground cables complete all as specified and as directed including provision of following :- 101 (i) MCCB 400 Amp Adjustable thermal setting 36 KA, FP, single frame, thermal magnetic trip (incoming) - 01 Nos. (ii) MCCB 125 Amp Adjustable thermal setting 35 KA, FP, single frame, thermal magnetic trip(Outgoing) - 04 Nos. (iii) MCB SPN 40 Amp(Outgoing) - 02 Nos.(iv) on load Changeover - FP 200Amp(Outgoing) - 01 No. (v) Digital Voltmeter with built inselector switch 0-500 volts -1 No.(vi) Digital Ampmeter with built inselector switch 0-250 Amps with Suitable CTs -1 No.(vii) LED indicating Lamps ( R,Y,B) one set-01 No. 102 All as per Serial Item No 45 here-in-before but with provision of following:-(i) MCCB 160 Amp Adjustable thermal setting 36 KA, FP, single frame, thermal magnetic trip (incoming) - 01 No. (ii) MCCB 125 Amp Adjustable thermal setting 35 KA, FP, single frame, thermal magnetic trip(Outgoing) - 05 Nos. (iii) MCB SPN 40 Amp(Outgoing) - 02 Nos. (iv) Digital Voltmeter with built inselector switch 0-500 volts -1 No.(v) Digital Ampmeter with built inselector switch 0-250 Amps with ratio 100:5 CTs -1 No.(vi) LED indicating Lamps ( R,Y,B) one set-01 No. 103 All as per Serial Item No 45 here-in-before but with provision of following:- (i) MCCB 200 Amp Adjustable thermal setting 36 KA, FP, single frame, thermal magnetic trip (incoming) - 01 No. (ii) MCCB 125 Amp Adjustable thermal setting 35 KA, FP, single frame, thermal magnetic trip(Outgoing) - 04 Nos. (iii) MCB SPN 40 Amp(Outgoing) - 02 Nos . (iv) on load Changeover - FP 200 Amp (Outgoing) - 01 No.(v) Digital Voltmeter with built inselector switch 0-500 volts -1 No.(vi) Digital Ampmeter with built inselector switch 0-250 Amps with ratio 100:5 CTs -1 No.(vii) LED indicating Lamps ( R,Y,B) one set-01 No. 104 All as per Serial Item No 45 here-in-before but with provision of following:-(i) MCCB 63 Amp Adjustable thermal setting 25 KA, FP, single frame, thermal magnetic trip (incoming) - 01 Nos (ii) MCB SPN 63 Amp(Outgoing) - 05 Nos (iii) On load Changeover - FP 63 Amp (Outgoing) - 01 Nos (iv) Digital Voltmeter with built inselector switch 0-500 volts -1 No(v) Digital Ampmeter with built inselector switch 0-250 Amps with Suitable CTs -1 No(vi) LED indicating Lamps ( R,Y,B) one set-01