| 1 | BACGH 500 KVA TRANSFORMER |
| 2 | Supplying, installing, testing & commissioning 3 phase, 11/0.433 kV, 50 Hz., 500KVA, Mineral oil immersed and naturally cooled outdoor type, CopperwoundNon-sealed transformer delta/star connected with additional neutral brought out on load side, temperature rise shouldnot exceed 45℃ by thermometer in oil and 50℃ by the resistance methodin winding at full load rating, using type A winding insulation (kraft paper) with HV tapping (with off load tap changer)off load +5 to -10 in steps of 2.5%,+5 to -10 in steps of 2.5%, having 7 number of tap positions with standard accessories complete with test certificate with losses below 1025 Watts at 50% load, 3100 Watts at 100% load as per IS:1180 (part 1) : 2014 with necessary permissions of Electrical Inspector, as per specifications |
| 3 | Supply Installation Testing and Comissioning of 11KV Ring Main Unit (RMU) 2 (In) & 1 (Out) Make :C&S |
| 4 | Supply Installation Testing and Comissioning of 11 KV Check and Main Metering Kiosk with CTR 100/5 Amp 0.2s Class 10VA & PTR 11KV/110V 0.2 Class 50 VA Make: Huphen/ Electromech. |
| 5 | Supply Installation Testing and Comissioning of 11kV 120 sq mm XLPE Round armoured HT Cable Make : Polycab |
| 6 | Supply Installation Testing and Comissioning of 11KV touch proof termination Kit suitable for 3C x 120 sq.mm cable Make: Raychem |
| 7 | Supply Installation Testing and Comissioning of 11KV Heat Shrinkable Straight Through termination Kit suitable for 3C x 120 sq.mm cable Make:Raychem |
| 8 | Supply Installation Testing and Comissioning of 11 KV Heat Shrinkable Indoor termination Kit suitable for 3C x 120 sq.mm cable Make: Raychem |
| 9 | Supply Installation Testing and Comissioning of Cu Earthing Strip 25 x 3 MM |
| 10 | shed for Metering Kiosks with required height ,asbestos sheet ,M.S.angles and allied work |
| 11 | Chain Link Fencing Metal Spreading and Danger Borads for Complete yard as specified or indicated or directed as per site condition by E I/C including allied civil works complete |
| 12 | Supplying and layingXLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 185 sq.mmX 3 1/2 core |
| 13 | Supplying and layingXLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 120 sq.mmX 3 1/2 core |
| 14 | Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less\"than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion Painting to fencing structure and allied works |
| 15 | Supplying and laying synthetic Rubber insulated mats 2.5 mm thick for voltage upto 3.3 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable forelectrical shock safety of sizes 2m x 1m. |
| 16 | Supply & layingHDPE (DWC)Pipe for cable protection 120 mm size |
| 17 | Painting to fencing structure and allied works |
| 18 | Supplying and erecting triple pole mini feeder pillarwith500V, 600A FPMCCB as incomer and 3 outgoing circuits with HRC fuse base and cartridge of 100A with aluminium bus bar erected in 14 SWG CRCA sheet box with supporting angles, self locks, gasket having IP54,IK10 protection and slanting top to be erected on provided foundation as per specification |
| 19 | Making foundation for the 11kv outdoor type RMU and Transformer |
| 20 | 20mm Aggrigate for filling in switch yard |
| 21 | Electrical testing & permission charges & Sundries |