| 1 | Replacement of grid power by CPP Power to MCC N1, N3 & N4 Panel |
| 2 | Supply, Installation, Fixing, Testing and commissioning of 800 Amps, 415V, 50 Hz, Pedestral Type, Indoor Change Over Panel for Power Supply to MCC-N1Panel, epoxy powder coated, enclosed with spacious sheet steel enclosure with 02(Two) Nos. of 800 Amps, 415 V, 50 Hz, Air Circuit Breaker,EDO,800 Amps,4-pole Draw-Out ACB ,50KA800A 4 Pole 50 KA CNCS EDO ACB as Incomer with SR18G microprocessor based, Make: Lauritz Knudsenand01(One) No. 800 Amps, 415 V, 50 Hz,FP On-Load Change Over Switch (Make: Lauritz Knudsen ). ON-OF Indication in each Feeder including Digital Ammeter, Voltmeter and Energy Meter.Electrical and Mechanical interlock to be provided as mentioned in the Annexure-A. The Panel Board Should be CPRI Approved having Alluminium Bus Bar as per Rated Current, made out of 2 mm (14SWG) good quality Sheet Steel Enclosure along with 7 tank facility powder coated paint of Siemens Grey Colour, the board should be of cubicle pedestral type and mounted on PCC foundation(which is under contractor\"s scope) etc.as per proper IS Standard as directed and as per the instruction of Engineer In-Charge. Make of Switchgear: Lauritz Knudsenand Panel Board should be Lauritz KnudsenAuthorized Panel Builder with CPRI Approved. Minimum Panel Component as per annexure –VIII of the NIT document |
| 3 | Laying , Termination, Clamping, Testing and Commissioning of the following size XLPE Insulated, Armoured LT Aluminium Conductor Main Power Supply Cable 650/1100 Volt Grade as per the IS Standard of latest Amendment with the excavation of the Cable Trenchs and caution it by sand & brick and laying the cable through it from different panels and Isolation Transformers, Termination/Energization/Jointing of Cable For Power Supply to different panels, Isolation Transformers for CPP Power Supply to the APL Township including supply and fixing of stainless steel pipe in the road crossing / aluminium/ lead strip number tags for each Cable, supply and applying offireproofing paint to meet the OISD requirement (for 01 meter length near termination), supply and fixing of GI saddles and saddle bar if required, including transportation from store / yard to site at the place of installation, unpacking including labour and materials as per the approved drawings and directions of the Engineer In-Charge. |
| 4 | 3R X 3.5 Core X 300 Sq. mm (From CPP PMCC 301, 15FB Panel Feeder to new Changeover panel) |
| 5 | 3R X 3.5 Core X 300 Sq. mm (From PCC Panel Feeder to new Changeover panel |
| 6 | 3R X 3.5 Core X 300 Sq. mm (Fromnew Changeover panel to MCC N-1 Panel) |
| 7 | 1R X 3.5 Core X 240 Sq. mm (From 125 TPD Formalin Plant to Mechanical Workshop) |
| 8 | Supply and Installing of following size of perforated Hot dipped Galvanised Iron Cable Tray (Galvanised thickness not less than 50 micron) with perforation not more than 17.5%, in convenient sections, joined with connectors over the ground @ minimum height of 01 feet from the ground, along with the wall, suspended from the ceiling with G.I suspenders, including bolts and nuts, painting suspenders as required etc. All the materials including Cable Tray bends, M.S angle, M.S bracket, nut bolt for installing the cable trays are in the scope of vendor. All the materials are under the scope of the contractor. |
| 9 | 300 mm width X 50 mm depth X 1.6 mm thickness. |
| 10 | Supply including fitting and fixing of heat shrinkable jointing kit including ferrules and other jointing materials forpvc insulated and PVC sheathed/ XLPE Al conductor including testing and commissioning as specified and directed by site Engineer. Size : 3.5coreX (185-300) mm2, 1.1 KV |
| 11 | Supplying and making end termination with brass compression gland and aluminium lugs for pvc insulated and PVC sheathed/ XLPE Al conductor of 1.1 KV grade 3.5 Core X (240-300) sqmm |
| 12 | Providing, Laying and installation of non pressure NP2 class (light duty) RCC Pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete 300 mm dia R.C.C pipe (for cable crossing). All the materials are under the scope of the contractor. |
| 13 | Supply and laying underground GI pipe of 150 mm for 2 nos of road crossing. Filling back the soil to make convenient for vehicle movement. All the materials are under the scope of the contractor. |
| 14 | Supply, installation & testing of G.I. earth station with perforated 40 mm dia and 4.50 Metre long heady duty G.I. pipewith necessary 40 mm dia. G.I. Fittingslocking arrangement 300 mmx300 mmx6 mmhinged cover C.I. earth plate complete with digging of earth pit, construction of brick chamber and plastering of both inner & outer surface of wall, watering pipe etc. charcoal/coke and salt as required andas specified and directed by the deptt . All the materials are under the scope of the contractor. |
| 15 | Providing and fixing of 50 mm X 5 mm GI strip in 40 mm dia GI pipe from earth electrode including connection with GI nut, bolt, spring washer, excavation and re-filling etc. as required. All the materials are under the scope of the contractor. |
| 16 | Dismantling, Installation of 02(two) nos. of lighting panel in Electrical Control Roomof size LBH (in cm)(109 X 30 X 137) & (110 X 30 X 166) and re-installation of these panels at different location in Electrical Control Roomincluding termination of existing cables in electrical control room |
| 17 | Supply installation fixing testing and Commissioning of 415 V Outdoor LT Feeder Piller with laying of cable for CPP Power supply to APL Office Building and Deep Tube-wells of Assam Petro-Chemicals Ltd., Namrup. |
| 18 | Supply, installation, fixing, testing & commissioning of 630Amps, 415V, 50 Hz, Pedestal Type Leg Mounted Outdoor Changeover Panel for Power Supply to existing APL Office Building and Deep Tube wells power panel, epoxy power coated, enclosed with spacious sheet steel enclosure with 02 Nos. of 630Amps, 415V, 50 Hz, FP MCCBs (Make: Lauritz Knudsen/ABB/Schneider/C&S/Havells) as Incomer having overload and Short circut and under voltageprotection with R-Y-B, ON-OFF indication including Digital Ammeter, Voltmeter and Energy Meter( Elite -500, Make-Secure), 01 No. of 630Amps, 415V, FP, On-load Change over Switch (Make: Lauritz Knudsen/ABB/Schneider/Legrand) and 06 (Six) Nos. of Out going Feeders. The detail specifications of 06 (six)Nos. outgoing Feeders are as follows:- (1) 03 Nos. of 250 Amps, 415 V, 50Hz, FP MCCB (Make: Lautitz Knudsen/ABB/Schneider/C&S/Legrand/Havells) with ON-OFF indication and Digital Ammeter & Voltmeter. (2) 03 Nos. of 160 Amps, 415 V, 50Hz, FP MCCB (Make: Lauritz Knudsen/ABB/Schneider/C&S/Legrand/Havells) with ON-OFF indication and Digital Ammeter & Voltmeter. The panel board should be CPRI Approved having Alluminium Bus Bar as per rated current, made out of 2 mm (14SWG) good quality sheet steel enclosure along with 7 tank fascility power coated paint of Siemens Grey Colour, the board should be cubicle Pedestal type Leg Mounted outdoor panel being mounted in PCC foundation (which is under contractor\"s scope) etc. with rain protection shed and Fencing barrication over the panel board in complete and as per proper IS Standard as directed and as per the instruction of Engineer In-Charge. The Panel Builder should be CPRI Approved reputed panel builder preferably L&T Authorize Panel Builder.All the materials are under the scope of the contractor. |
| 19 | Supply, installation, testing & commissioning of perforated 40 mm dia 4.5 Meter long heavy duty G.I. Pipe with necessary 40 mm dia G.I. Fittings locking arrengement, 300 mmX300mmX6mm hinged cover C.I. Earth Plate, complete with digging of earth pit, construction of brick chamber and plastering of both inner and outer surface of wall as specified and directed by the Engineer In-Charge. All materials are under the scope of the contractor. |
| 20 | Supply including fitting and fixing of Resin Cast type 1.1KV PVC/XLPE/PILC Straight through joing kit suitable for jointing of 2 core X 240 Sq.mm PVC insulated Armoured Cable (Make: RAYCHEM/3M/M-Seal/Elechem) including all accessories as required and as directed by Engineer In-Charge. All materials are under the scope of the contractor. |
| 21 | Laying, termination, Clamping, Testing and Commissioning of 650/1100 VoltPVC Insulated Armoured Cable of following size as per IS Standard with latest amendment with the excavation of Cable trenchs and caution by sand & brick, clamping in the wall, laying over existing cable tray from CPP Sub Station to the outdoor townsip panel yard for 415 Volt 3-phase power supply provision from CPP to the APL Office Building and Deep Tubewells and fixing of Stanless Steel pipe in road crossing, alluminium/lead strip namber tags for each cable, supply and applying of fire proofing paint to meet the OISD requirement (for 01 meter length near termination), supply and fixing of GI saddles and saddle bar if required, including transporation of cable drum from APL Store/yard site at the place of installation, unpacking including labour and materials with tools and tackes as per approved drawings and directions of the Engineer In-Charge. |
| 22 | 2 Core X 240 Sq.mm PVC Insulated Armoured Cable |