| 1 | Taking down carefully existing copper/Aluminum point wiring (light,fan, socket or power) complete including fixture and fittings such as switches, bellpushes, ceiling roses, pendents, regulators, sockets, light fitting, callbells etc removiing materials to store for keeping in safe custody or for taking credit(credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors etc. to match existing complete allas specified and directed |
| 2 | M & L forPoint wiring with multi-stranded copper conductor, single core, PVC insulated and unsheathed cable, including PVC insulated unsheathed multistranded copper conductor single core cable as earth continuity conductor to common earth and connected to earth dolly, GI terminal boxes, modular frame & cover plate (suitable for modular switch/sockets) comprising the following: - |
| 3 | One light point controlled by one switch or one fan point controlled by one switch & fan regulator etc. with 2.5 Sq. mm (nominal area) cable & 2.5 Sq. mm (nominal area) cable as earth continuity conductor, in existing concealed conduit all as specified. |
| 4 | One Socket outlet three pin, 6 Amp, on the same board, with 2.5 Sq. mm (nominal area) cable & 2.5 Sq. mm (nominal area) cable as earth continuity conductor, all as specified |
| 5 | One Socket outlet three pin, 6 Amp, independent, with 2.5 Sq. mm (nominal area) cable & 2.5 Sq. mm (nominal area) cable as earth continuity conductor,in existing concealed conduit all as specified |
| 6 | One Bell/Buzzer point controlled by one push button with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor,in existing concealed conduit all as specified. |
| 7 | One light point controlled by two two way switch. with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, in existing concealed conduit all as specified |
| 8 | One socket outlet three pin, 5/15 Amp, independent, with 2.5 Sq. mm (nominal area) cable & 2.5 Sq. mm (nominal area) cable as earth continuity conductor,in existing concealed conduit all as specified. |
| 9 | S&F Switch piano, flush type single pole, one way 5 Amp complete all as specified |
| 10 | S&F Switch piano, flush type single pole, two way 5 Amp complete all as specified |
| 11 | S&F Switch piano, flush type single pole, one way 15 Amp complete all as specified |
| 12 | S&F Bell push 5/6 Amps 230 V AC complete all as specified |
| 13 | S&F Socket outlet 3 pin, 5A, flush type all as specified |
| 14 | S&F Socket outlet 2 in 1, 3 pin, 5 and 15 Amp flush type complete all as specified |
| 15 | S&F Stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc. as reqd complete all as specified |
| 16 | S&F Ceiling rose, 3 terminal PVC/polycarbonate, suitable for 230 V, AC, 50 Hz |
| 17 | S&F call bell ding dong type AC 230 V complete |
| 18 | S&F Lamp holder PVC/polycarbonate type with back plate complete all as specified |
| 19 | S&F post top lantern LED type 20 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistance complete with driver and lamp complete all as specified and directed |
| 20 | S&F LEDdownlighter/spot light fitting, recessed mounted, round shaped of ceiling cut outφ160mm, 12watts efficacy not less than 90 lumen/watt, 3000/6500K extruded Aluminium/polycarbonate, PC diffusor, module and inbuilt driver complete including making connection complete all as specified and directed |
| 21 | S&F LEDlandscape/bollard light fitting, round shaped of 0.6m pole size, 3 watts solar lights , efficacy not less than 90 lumen/watt, extruded Aluminium/polycarbonate, IP65, PC diffusor, module and inbuilt driver complete including making connection & fixing of pole base with nut and bolt to PCC pedestal/coping complete all as specified and directed |
| 22 | Supply and FixingLED flood light fitting sqaure shape 70 Watt 230V AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp, bracket with impact and corrossion resistant complete with IP 65/66 protection with suitable bolt and nuts, fixing at any height upto 15m complete with making connection complete all as specified and directed |
| 23 | S&F LED Bldg securitylight fitting 35 Watt 230V AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp bracket with impact and corrossion resistant complete with IP 65/66 & IK 08 protection complete with GI bracket as required size bend to shapeincluding fixing with suitable bolt and nuts complete with making connection complete all as specified and directed. |
| 24 | S&F in replacement sub main two single core PVC copper conductor unsheathed wiremulti stranded 4 sqmm along with earth wire 4.0 sqmm copper conductor single core wire connected by common earth inexisting surface/recessed PVC/steel conduit complete all as specified.(Note :- two lengths of 4.0 sqmm cable and one length of 4.0 sqmm earth cablewill be measured as one running length) |
| 25 | S&F in replacement sub main two single core PVC copper conductor unsheathed wiremulti stranded 6 sqmm along with earth wire 6.0 sqmm copper conductor single core wire connected by common earth inexisting surface/recessed PVC/steel conduit complete all as specified.(Note :- two lengths of 6.0 sqmm cable and one length of 6.0 sqmm earth cablewill be measured as one running length) |
| 26 | S&F in replacement sub main two single core PVC copper conductor unsheathed wiremulti stranded 6 sqmm along with earth wire 6.0 sqmm copper conductor single core wire connected by common earth inand including surface/recessed PVCconduit complete all as specified.(Note :- two lengths of 6.0 sqmm cable and one length of 6.0 sqmm earth cablewill be measured as one running length) |
| 27 | S&F in replacement sub main two single core PVC copper conductor unsheathed wiremulti stranded 10 sqmm along with earth wire 10.0 sqmm copper conductor single core wire connected by common earth inexisting surface/recessed PVC/steel conduit complete all as specified.(Note :- two lengths of 10.0 sqmm cable and one length of 10.0 sqmm earth cablewill be measured as one running length) |
| 28 | S&F in replacement sheet metal encloser double door 4 way TPN 415V ISI marked complete with neutral and earth link and bus bar complete made out of CRCA steel sheet Factory made including blanking plate for unused module complete all as specified and directed |
| 29 | S&F in replacement sheet metal encloser double door 8 way TPN 415V ISI marked complete with neutral and earth link and bus bar complete made out of CRCA steel sheet Factory made including blanking plate for unused module complete all as specified and directed |
| 30 | S&F in replacement sheet metal encloser double door 8 way SPN 240V ISI marked complete with neutral and earth link and bus bar complete made out of CRCA steel sheet Factory made including blanking plate for unused module complete all as specified and directed |
| 31 | S&F in replacement sheet metal encloser double door 12 way SPN 240V ISI marked complete with neutral and earth link and bus bar complete made out of CRCA steel sheet Factory made including blanking plate for unused module complete all as specified and directed |
| 32 | S&F in replacement single pole and neutral enclosure 240V with a two pin and earth plug and socket complete with one double pole MCB 20Amp complete all as specified and direcetd |
| 33 | S&F in repair MCB 6-32 Amp 240V SP 10 KA ‘B’ series complete all as specified |
| 34 | S&F in repair MCB 40-63 Amp 240V SPN 10 KA ‘C’ seriescomplete all as specified |
| 35 | S&F in repair MCB 415V 40 to 100Amp TPN 10 KA ‘C’ seriescomplete all as specified |
| 36 | S&F in repair MCCB 415V, FP 63A 16kA complete all as specified |
| 37 | S&F in repair MCCB 415V, FP 100A 16kA complete all as specified |
| 38 | S&F in repair MCCB 415V, FP 125A 16kA complete all as specified |
| 39 | M & L for earthing with galvanized steel plate electrode 600 x 600 mm x 6 mm size directly burriedin ground vertically to earth pit not less than 2.25 meter deep below normal ground level with top edge of the earth plate not less than 1.5 m below normal ground level surrounded with coal dust and common salt filling in alternative layers of 15 cm thick eachconnected to and including GI earth wire 4 mm dia by means of nuts, bolts, check nuts & washers etc connecting to earthing test point, main switch board and including 15 mm dia GI pipe light grade for protection of earth lead from earth plate to distribution board and 20 mm dia GI pipe medium grade connected with funnel having wire mess for watering purpose including necessary excavation and earth work, PCC (1:2:4) type B-1 (using stone aggregates)for earthing pit, 10mm thick cast iron cover with angle iron frame all as specified and shown in electrical plate No 3 of SSR Part-I andtesting on completion including replacement of old unserviceable.Note:- It is mandatory to paint a sqaure shape notice board of yellow color with legible black color letters of earthing mentioned details as below; Cost incurred deemed to be inlcuded in quoted rate:- |
| 40 | S&F in repair rigid non metallic PVC conduit medium grade 25 mm nominal dia,\"ISI marked\" inclusive of all fittings (such as junction boxes, bends, elbows, tees, reducers, bell mouth tube ends) and all fixing accessories such as couplers lock nuts, saddles, pipe hooks etc for telephone socket, complete all as specified |
| 41 | M&L for Cutting chases, pinning in. making good to facings where required and pointing in cement mortar 1:3 to ends or edges of landings, steps, cills, sunshades, shelves, lintels, etc.; and cutting chases for concealed water tubing or concealed conduit wiring, etc., and making good, cutting not exc 10 cm girth |
| 42 | Supply, installing, commisioning & testing of LT panel board IP65 415-433V made of 2.0 mm thick RAL 7032/7035 coated CRCA steel complete with wiring, fittings and accessories, locking arrangements and painting of adequate size for housing equipment, internal wiring and termination of external cables, lugs and glands and fixing on wall/ Grouting in wall incl neccesary repair work and disturbed surfacemaking good , matching with existingand solid/ flexible conduits as required, comprising of the following:- |
| 43 | Incomer 125 A 4 pole MCCB 440V 25kA-01No |
| 44 | Indicating lamps R.Y.B with control fuses |
| 45 | Copper Busbars 200A TPN & earth |
| 46 | 63A TPN MCBs C Curve-04Nos(For DUs meters) |
| 47 | 6A DP MCB C Curve-01 No(For staircase lighting meter) |
| 48 | 6A SP MCB C Curve-01 Nos(Outgoing for staircase) |
| 49 | Provisional arrangement for energy meters with transparent acrylic sheet with separate locking arrangements-05 Nos |
| 50 | Refixing and connecting energy meters retrived -04 Nos |
| 51 | Supplying and fixing in replacement 1100volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular of size 6sqmm complete all as specified |
| 52 | Fixing only wall mounted extruded Aluminium/polycarbonate integrated LED batten fixture with tube 1.2 m, 20watt, 1.2 m3000/6500K,efficacy not less than 90 lumen/wattextruded Aluminium/polycarbonate, PC diffusor and integrated inbuilt driver completecomplete including making connection complete all as specified and directed |