| 1 | Total amount ofSch \"A\" Part-I ( Bldg Work) |
| 2 | Total amount ofSch \"A\" Part-II ( Plumbing Work) |
| 3 | Total amount ofSch \"A\" Part-III (Internal water supply) |
| 4 | Total amount ofSch \"A\" Part-IV (Path Works) |
| 5 | Total amount ofSch \"A\" Part-V(Section I)( SEWAGE DISPOSAL) |
| 6 | Total amount ofSch \"A\" Part-V (Section-II) (SEWAGE DISPOSAL) Note : This schedule is not pre priced by MES and the pre priced rate indicated as \"Rs. 0.00\" under Col.5 signifies this fact only |
| 7 | Supply and installation of Polythehe (LLDPE Underground septic tank) of capacity 1000 Ltr (CCST-100-01) of Roto moulding grade conforming to IS 10146:2003 and Relaince \"O\" 35042 grade MFI : 2.0 to 6.0 gm/10 minutes and denisity 932 to 943 Kg/Cum and carbon blackmaster batch content 40% +1% and ash content 1% max. The avarage weight oftank shall be 40+1Kg and wall thickness 7.3mm. The tank shall be installed as per manufacturer instructions. Note :- The excavation in any type of soil, PCC 1:4:8 below foundation, vent shaft, connection etc complete all asrequired as per manufacturer\"s instructions will be included in cost of LumpSum quoted against this item and nothing extra shall be paid on this account and tenders are to quote their rates accordingly. |
| 8 | Total amount ofSch \"A\" Part-VI (Section-I) (Internal Electrification) |
| 9 | Total amount ofSch \"A\" Part-VI (Section-II) (Internal Electrification)Note : This schedule is not pre priced by MES and the pre priced rate indicated as \"Rs. 0.00\" under Col.5 signifies this fact only |
| 10 | LEDlight fitting 1X20 watt with lens connector block, all accessories prewired with suitable size cable including 20watt Led tube rod and connecting electrically using PVC insulated and overall sheathed flexible copper conductor cable of size 0.75 sqmm 3 core, complete all as specified and directed by Engineer-in-Charge.. |
| 11 | LEDlight fitting 1X10 watt 2\" longwith lens connector block, all accessories prewired with suitable size cable including 10watt Led tube rod and connecting electrically using PVC insulated and overall sheathed flexible copper conductor cable of size 0.75 sqmm 3 core, complete all as specified and directed by Engineer-in-Charge. |
| 12 | LED street light of 1X45 watt, IP 66 powder coated pressure die cast aluminium compact high power LED street light with heat resistance toughened glass including street light bracket made of 25/40mm (as per dia of fitting) GI tubing light grade including clamps, nuts, bolts etc for fixing on wall, complete all as specified and directed by Engineer-in-Charge.. |
| 13 | Heavy duty exhaust fan ( as per BEE recommendation) 300mm sweep singlephase 230 volts 50 Hz AC supply totally enclosed heavy duty motor with die cast aluminium rotory mounted on two ball bearing complete louvers including cutting chases for fixing fan, connecting electrically using 3 core 0.75sqmm PVC insulated flexible copper conductor cable over all sheathed all as required at site including required accessories, complete all as specified and directed by Engineer-in-Charge. |
| 14 | MCB single pole & neutral 240 volts 6 to 32 amps, with rupturing capacity 10KA (ISI Marked) , completeall as specified and directed by Engr-in-Charge. |
| 15 | MCB single pole 240 volts 6 to 32 amps, with rupturing capacity 10KA (ISI Marked) ,complete all as specified and directed by Engr-in-Charge. |
| 16 | Total amount ofSch \"A\" Part-VII (Section-I) (External Electrification) |
| 17 | Sch \"A\" Part-VII (Section-II) (External Electrification ) Note : This schedule is not pre priced by MES and the pre priced rate indicated as \"Rs. 0.00\" under Col.5 signifies this fact only. |
| 18 | Supply, Installation, Commissioning and testing of silent type with accoustic encloser diesel enginegenerating set complete with panel for automatic starting on main failure output of 62.5 KVA (NTP) after considering derating factor for 10600 feet above mean sea level (MSL) and including acoustic enclosure suitable for working at 10600 feet above mean sea level (MSL)and working temperature range (-)20 degree centigrade to (+) 40 degree centrigrade and alternator of suitable capacity and RPM coupled with each other and capable to taking 10% overload for one hour on every 12 hours with flexible coupling mounted on common base plate and antivibration pad on foundation as recommended by manufacturer. The DG set shall comprise of electric starter motor with batteries of 24 volts, 160 AH including suitable lead for charging with copper/brass terminals. The DG set shall have turbo charger after cooled type and electronic governor. AVR with all standard fittings, fixtures and all piping etc as furnished below and specified in particular specification :-a) Multifunctional meter for measuring DG parameters as per manufacturing Design (cont to 10.02 to 10.08) |
| 19 | b) Indicator lamp : Indicator lamp with LED type 230 Volts core Gen set/Main supply ON/OFF indication and different relay position etc all as required and recommended by manufacturer.c) Bakelite fuse : Bakelite fuse base carrier with HRD fuses 160 Amps. 415 Volts suitable for and including knife type HBC fuse link of- 08 Nos.d) Accessories and prewiring : All accessories should have prewired with suitable size PVC insulated copper conductor cable of appropriate size including foundation as per manufacturer recommendation.e) Foundation : PCC foundation as per manufacturer\"s instructions / recommendations or required at site or as directed by Engr-in-Charge. Cost of the same shall be deemed to be included in the lump sum cost of DG set quoted by tenderer.Note : The engine shall be affixed with label mention the following :-i) Name and address of the engine manufacturer.ii) Type approval certificate number.iii) Date of manufacture of engine.iv) The complete generating set inclusive control panel base frame coupling etc. shall be from the OEM and shall be assembed and tested at engine manufacturer\"s workshop and test certificate shall be provided by contractor. |
| 20 | Environementi) Engine conforms to environment (protection) rule 1986.ii) Humidity upto 95% (non condensing).iii) Operating temp range (-) 20 degree centigrade to (+) 40 degree centigrade.iv) Height above means Sea level (MSL) 10600 feet.AlternatorThe Alternator 62.5 KVA, 3 Ph, 415 V, 0.8 PF, 4 wire, H-class insulation, self excited, self regulated, screen protected drip proof type with two end ball bearing / roller bearing with damper winding in each pole faces as per IS 4722 or BS 2613-1970 all as specified as below :-a) Time permitted to build up rated voltage < 5 sec.b) Short circuit with stand time 10 sec.c) Short circuit ratio 0.4.d) Overload withstand capacity minimum 150% for 15 sec.e) Type of cooling system alternator - Air cooled system.f) Temp rise of armature winding - 125 degree centigrade.g) Temp rise of field winding - 125 degree centrigradeh) Flow of alternator - 15 m4/min (appx)j) Heat rejection by alternator - 7.7 KW |
| 21 | k) Efficiency of alternator :-i) at 100% MCR & rated PF - 94.0%ii) at 75% MCR & rated PF - 94.1%iii) at 50% MCR & rated PF - 93.6%Diesel EngineDisel Engine air cooled and electric start suitable to drive above alternator independently coupled directly through flexible coupling, multi cylender four stroke, cold starting 1500 RPM industrial type as per BS-649 or IS 1601 with A1 class electronic governer integral with fuel system, providing capability for isochroonous goverering to regulate speed of DG set from no load to full load complete with fuel tank of capacity as per manufactured recommendation including lowest weight to power ratio of 2.18 for engine, silencer, exhaust pipe duly insulated with asbests rope and support and silencer muffier etc for contineous operation and standard accessories sump preheater etc all as specified and directed as follows :-(Note : Nine free service checks during warranty perid)a) Aspiration - Turbo charged & after cooled.b) Staring system - 24 volts, electric.c) Exhaust silencer type - Residential / Hospital grade.d) Exhaust noise level (with silencer ) @ 1 M - < 75 DB (A) |
| 22 | f) Recovery time in governor system - <8 secg) Max time to start from cold & attain rated speed & ready to start - 5 sec.h) Overload capacity - 10% for 1 hour in 12 hours of operation.Control panel :-The standard control panel corprising of control cubical fabricated sheet steel construction indoor type suitable for mounting accessories as given below :-Operator interface :- Threshold Warning Indicationa) Manual start/stop a) Low oil pressureb) Auto/remote startb) Low engine coolant tempraturec) Auto LED c) High engine coolant tempratured) Not in Auto LED d) Low coolant levele) Manual LED e) Low Battery voltagef) Common shutdown LED f) High Battery voltageg) Common warning LED g) Battery Alt charge faulth) Exercise LEDh) Over currentj) Emergency stop (local and remote) j) Overloadk) Alphanumeric screenl) Remote start input active LEDm) Fault reset |
| 23 | Measurement & Instrumentation - (Engine Side)a) Oil Pressureb) Oil Tempraturec) Water Tempratured) Engine Speede) Hours Runf) Number of startsg) Battery Voltageh) Exhaust TempratureMeasurement & Instrumentation - 3 Phase L-L & L-N Voltage & Frequency (Alternator side)a) 3 Phase Currentb) KWhc) Total KVAd) Total KW & KVAre) PFf) Per Phase, KVAr, KWg) Per Phase KVAShutdown Protection & Shutdown Protection & Indication Indication - (Engine side) (Alternator side)a) Low Fuel Level i) Under & Over Voltageb) High Fuel Level ii) Under & Over |
| 24 | c) Low Oil Pressure iii) Over Currentd) High Engine Coolant tenpratureiv) Earth Leakagee) Failure to Crank Shutdown v) Reverse Powerf) Over Crank (failur to start) vi) Reverse VarPower Transfer Function -a) Open Transition Transferb) Hard Closed Transitionc) Soft Closed Transition (ramping)d) Transfer & Base Load (Utility)e) Gen/Mains Breaker Staus ProtectionElectric Starter Equipment -The Equipment will comprise the followings :-a) Maint free Battery duly initially charged and battery lead with copper/brass terminals with 160 AH capacity.b) Starter motorc) Starter gearing d) Start / stop push buttone) Invertor cum battery charger 500 VA capacity suitable to work on 230 Volts, 50 Hz, AC supply system for charging of DG set batteries externally when DG set is in off position.f) Alternator/dynamo of suitable capacity to charge the batteries while DG set is running complete with auto cut out all as per manufacturer recommendations. |
| 25 | AMF PANELAuto mains failure panel 415 Volts, 50 Hz suitable for 62.5 KVA DG sets made out of 16 guage steel sheet factory made cubical type floor mounted front and rear door openable doors with locking arrangement duly powder coated suitable for including the followings :-a) Microprocessor based auto transfer switch 4 pole 200 Amps 415 volts MCCB 02 Nos electronic control box for automatic switching on and off of DG set and transfer of load pre assembled and ready to use complete in all respect equipped.b) On load change over switch 4 pole, 415 volts, 50 Hz, 160 Amps in open execution for manual change over of supply of AMF panel failure. |
| 26 | Supply & fixing of of Flood light fitting heavy duly type weather proof construction with anodizes aluminium reflector lamp holder, heat resisting rubber, glass base plate seiveling & fitting bracket for wall or pole mounting suitable for 400 watt MH lamp, complete all as specified and as directed. |
| 27 | Supply and install Aviation obstruction light twin fitting comprising for LED with 100Nos lamps complete with LED lamp and fixing on top of watch tower, complete all as specified and as directed. |
| 28 | Supply ,installation, commissioning of Bus bar chamber cubical floor mounted type made out of 3.15mm thick MS sheet duly painted with two coats of synthetic enamel paints, bus bar 400 amps rating made of copper strip duly drilled holes for connections and mounted on epoxy based post insulators for 3 phase 4 wire 415 volts 50HZ AC supply, complete all as specified and as directed. |
| 29 | Supply & fixing of security lights LED 45 watts walls/surfaces by means of MS clamps of flat iron 25X4mm, nuts, bolts and washes of required size and galvanised iron bracket of light grade. 40mm dia size pipe not less than 1.50 meters long bent to shape for mounting of including drilling of holes on walls grouting on walls with provision of hold fasts etcall as directed by the Engineer-in-Charge. |
| 30 | Supply & fixing of search light of 800 watt with MH lamp incl stand and fixing arrangement for fixing on plateform etc and provn of movement in 360 degree angle complete with all accessories including copper ballast/gear box complete and including all accessories, complete all as directed by the Engineer-in-Charge. |
| 31 | Material and labour for mild steel clamps made out of mild steel strip 20X3.15mm fixed to poles with nuts, bolts and washers(Two clamps per pole) of suitable size, complete all as directed by the Engineer-in-Charge. |
| 32 | Supply and fix PVC twin core cables of size 4.0 Sqmm, complete all as specified and as directed. |
| 33 | MCB DP 32amps, 240 volts complete all as specified and as directed. |
| 34 | Supply, install , testing and commissioning of outdoor LT panel cubical, CPRI approved having insulated copper bus bar 400 amps duly drilled holes for connection and mounted on epoxy based post insulators for 3 phase, dust and vermin proof totally enclosed plateform mounted factory made (Protection class IP-65) double shutter gearsfront & rear door openable with locking arrangement floor mounted type made out of 3.15 mm thick MS sheet and inner sheet 2mm thick duly painted with powder coated overtwo coats of red oxide primer and made out of50 x 50 x 6 mm thick angle iron frame four Nos not less than 75 cm long legs with natural breathing arrangements all as specified including necessay foundation bolt grouted in PCC 1:2:4 type B-1 for mounting the panel suitable for 415 Volts, 50 C/s 3 phase and neutral system and internal wiring with suitable size of solid copper conductor comprising of following accessories:-(a) MCCB 4 pole 415 volts, 26 KA, 125 Amps (electronic release) - 01 No (Main incoming).(b) MCB SPN 32 amps-01 No(c) Digital Ammeter 0-200amps with selector seitch-01 No.(d)Digital volt meter 0 -500 volts with selector switch-01 No.(e)LED indicating lamp (RYB)- 01 set of three.(f) On load change over switch 125 amps 415 volts 50Hz(g) MCCB 3 pole 415 volts, 16 KA, 63 Amps (electronic release) - 03 No (out going). |
| 35 | Total amount ofSch \"A\" Part-VIII (Site Clearance, Excavation and Earth Work) |