| 1 | Taking down carefully copper/ aluminum point wiring (light, fan, socket or power) complete, including all fittings such as switches, ceiling roses, pendants, regulators sockets etc.) removing material from the site and making good the disturbed surfaces of walls, floor or ceiling etc. to match with existing specifications, keeping aside serviceable items and removing to store for reuse within the same bldg or otherwise removing unserviceable items from site complete all as specified and directed. (Note: The decision of the Engr-in-Charge as to which materials are serviceable or otherwise credit to be afforded by the contractor for the unserviceable material shall be final and binding. |
| 2 | M&L for point wiring for one light point/fan point controlled by one-one way switchwith 1.5 Sqmm. (nominal area) single core FRLS,PVC insulated 1100 Volts, grade multi stranded unsheathed copper conductor unsheathed in and including non metalic rigid PVC casing & caping of 25mm width (Medium grade double locking system)complete with all acessories including PVC sunken box ISI marked for mounting of switches, sockets, fan regulator etc with 3 mm thick plastic laminated sheet as top cover, and 1.5 Sqmm. (nominal area) single core FRLS, PVC insulated 1100 Volts, grade multi stranded unsheathed copper conductor cable as earth wire upto common earth and connected to earth dolly including cutting, chasing and making good to the diturbed surfaces to match with existing, compete all as specified and directed.(Note:- Three run of copper conductor of required size and one run of casing capping measured as one unit and also colour coding of wiring to be followed as red/yellow/blue for phase, black for neutral and green for earth) |
| 3 | Description all as per srl item No. 2.00 above but for socket out 5 Amps on same board complete all as specified and directed. |
| 4 | Description all as per srl item No. 2.00 above but for socket outlet 5 Amps on independent board complete all as specified and directed. |
| 5 | Description all as per Serial item No 2.00 above but for one 3 pin 16 Amp socket outlet independent with2.5 sqmm PVC insulated FRLS multistraind copper cable with 2.5 sqmm single core multistraind FRLS copper cable as earthling lead complete all as specified and directed. |
| 6 | M&L for point wiring for one light point/fan point controlled by one-one way switchwith 1.5 Sqmm. (nominal area) single core FRLS,PVC insulated 1100 Volts, grade multi stranded unsheathed copper conductor unsheathed in and including rigid PVC conduit pipe not less than 20mm dia (Medium grade) concealed in wall /ceiling surface complete with all acessories including pressed steel terminal boxes of suitable size ISI marked for mounting of switches, sockets, fan regulator etc with 3 mm thick plastic laminated sheet as top cover, and 1.5 Sqmm. (nominal area) single core FRLS, PVC insulated 1100 Volts, grade multi stranded unsheathed copper conductor cable as earth wire upto common earth and connected to earth dolly including cutting, chasing and making good to the diturbed surfaces to match with existing, compete all as specified and directed.(Note:- Three run of copper conductor of required size and one run of PVC conduit pipe measured as one unit and also colour coding of wiring to be followed as red/yellow/blue for phase, black for neutral and green for earth) |
| 7 | Description all as per srl item No. 6.00 here-in-before but for socket out 5 Amps on same board complete all as specified and directed. |
| 8 | Description all as per srl item No. 6.00 here-in-before but for socket outlet 5 Amps on independent board complete all as specified and directed. |
| 9 | Description all as per Serial item No 6.00 here-in-before but for one 3 pin 16 Amp socket outlet independent with2.5 sqmm PVC insulated FRLS multistraind copper cable with 2.5 sqmm single core multistraind FRLS copper cable as earthling lead complete all as specified and directed. |
| 10 | S&F for switch piano flush type single pole one way 5 amps 240 volts complete all as specified and directed. |
| 11 | S&F for switch piano flush type single pole one way 15 amps 240 volts complete all as specified and directed. |
| 12 | S&F for bell push flush type single pole one way 5 amps 240 volts complete all as specified and directed. |
| 13 | S&F for socket outlet 2 in 1, 5 pin, 5 amp flush type, 230 volts complete all as specified and directed. |
| 14 | S&F for socket outlet 2 in 1, 5 pin, 15 amp flush type, 230 volts complete all as specified and directed. |
| 15 | S&F switch socket combination combined with box 2 in 1, 3 Pin, 6 and 16 Amp flush type universal 230 volts, complete all as specified and directed. |
| 16 | S&F for ceiling rose 3 phase/PVC/polycarbonate isolated body surface bakelite2 to 3 terminals complete all as specified and directed. |
| 17 | S&F for lamp holder insulated body PVC/ Polycabonate type with back plate suitable for batten/angular/pendent fittingscomplete all as specified and directed. |
| 18 | S&F for modular switch 6 Amps, one way, one module complete all as specified and directed. |
| 19 | S&F for modular switch 16 Amps, one way, one module complete all as specified and directed. |
| 20 | S&F for modular socket 6 Amps, 2/3 pin combined two modulecomplete all as specified and directed. |
| 21 | S&F for modular socket 6/16 Amps, 6 pin combined two modulecomplete all as specified and directed. |
| 22 | S&F for modular switch bell push 6 amp,one module, complete all as specified and directed. |
| 23 | S&F for modular fan regulator electronic, 120 watt,step type 2 module, suitable to control speed of fan from 0 to 100% and connecting electrically, complete all as specified and directed. |
| 24 | M&L in replacement for 12 Watt LED surface decorative wall/ ceiling mounted LED light fitting 3000k/6000k, LED backlit round or square (as reqd at site) down lighter with high effcient LEDs & glate free opal diffuser IP20, internally prewired, 230 V, complete with all accessories such as electronic driver, connector block etc and necessary fixing arrangement at any height complete all as specified and directed. |
| 25 | S&F in replacement of high efficacy 2 x 2 feet recess / surface mounting LED flat panel light fittings 36W LED 3000K - 6000K edge - lit luminaire as required on siteand including LED lamp suitable for armstrong/grid ceiling complete for low ceiling applications complete with all accessories pre wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size, completeall as specified and directed.Note: Material required for safety harness, ladder and T&P etc will be provided by the contractor without any extra cost. |
| 26 | M&L in replacement for LED Tube light fitting, complete with 1x 20 watts, 4feet long, 220V, AC decorative box type with driver, holder in andincluding LED tube light connection complete prewiredand connecting electrically to ceiling rose to fitting using PVC insulated and overall sheathed flexible copper conductor cable of size 0.75 sqmm 3 core and connector block etc and necessary fixing arrangement at any height, complete all as specified and directed. |
| 27 | S&F in replacement for LED tube light fittings 1x10 watts, complete with 2 feet decorative ultra slim near LED lighting fixture with co extruded polycarbonate body, environmental friendlyenergy effcient ready to use complete prewire and connecting electricaly using cord flexible 3 core PVC insulated over all sheathed with flexible copper conductor of size 0.75 sqmm complete all as specified and directed. |
| 28 | S&F in replacement for call bell AC, 230 volts, single pole, ding-dong sound type, complete all as specified and directed. |
| 29 | M&L in replacement for sheet metal enclosure MCB distribution board, double door single pole and neutral with IP-66 protection single phase 240 volt 8 way, including suitable size copper bus bar and neutral link fixed flush in wall including chases wall for fixing DB and making good disturb wall surfaces to match with existing specification, complete all as specified and directed.(Note:-MCBs will be measured and paid separately.) |
| 30 | M&L in replaement for sheet metal enclosure MCB distribution board, double door single pole and neutral with IP-66 protection single phase 240 volt 4 way, including suitable size copper bus bar and neutral link fixed flush in wall including chases wall for fixing DB and making good disturb wall surfaces to match with existing specification, complete all as specified and directed.(Note:-MCBs will be measured and paid separately.) |
| 31 | S&F in replacement for sheet metal enclosure with socket plug top and MCBs single pole with one MCB 240 volts 20 amps,complete all as specified and directed. |
| 32 | M&L in replacement for MCB single pole,240 volts any rating from 6 to 32 amps, with rupturing capacity 10 KA, including providing thimble for out going cables, complete all as specified and directed. |
| 33 | M&L in replacement for MCB single pole & neutral 240 volts any rating from 6 to 32 amps, with rupturing capacity 10 KA, including providing thimble for out going cables, complete all as specified and directed. |
| 34 | Supply, Laying, connecting and testing of service cable of size 6 Sqmm 2 core 1100 volts grade heavy duty cable PVC insulated stranded aluminium conductor, served with an inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 mtr apart including 4mm suspension wire or drawn in and including medium grade non metallic rigid PVC conduit as per site requirement, flat or circular after taking down old unserviceable cable including others accessories, complete all as specified and directed. |
| 35 | Supply, Laying, connecting and testing of service cable of size 10 Sqmm 2 core 1100 volts grade heavy duty cable PVC insulated stranded aluminium conductor, served with an inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 mtr apart including 4mm suspension wire or drawn in and including medium grade non metallic rigid PVC conduit as per site requirement, flat or circular after taking down old unserviceable cable including others accessories, complete all as specified and directed. |
| 36 | M&L for sub main wiring complete with 2 run of 6 sqmm, single core, copper conductor cable 1100 volts grade, FRLS type, PVC insulated, unsheathed, flexible, multi strandedduly colour coded cable drawn through and including PVC casing and caping of size 25mm width or above as required at site and accessories such as tee, corners,overlaping connector etc of suitable size fixed on surface of walls/roofs/ceiling and including 02 run of 6 sqmm single core, copper conductor cable 1100 volts grade, FRLS type, PVC insulated, unsheathed, flexible, multi stranded of green colour as earth continuity conductor connected to common earth dolly including removing old unserviceable sub main wiring, complete all as specified and directed.(Note : -02 run of 6 sqmm single core copper conductor cable and 01 run of 6 sqmm single core copper conductor and 02 run of PVC casing and caping shall be measured as one unit and also colour coding of wiring to be followed as red/yellow/blue for phase, black for neutral and green for earth). |
| 37 | M&L for sub main wiring complete with 2 run of 10 sqmm, single core, copper conductor cable 1100 volts grade, FRLS type, PVC insulated, unsheathed, flexible, multi strandedduly colour coded cable drawn through and including PVC casing and caping of size 25mm width or above as required at site and accessories such as tee, corners,overlaping connector etc of suitable size fixed on surface of walls/roofs/ceiling and including 2 run of 10 sqmm single core, copper conductor cable 1100 volts grade, FRLS type, PVC insulated, unsheathed, flexible, multi stranded of green colour as earth continuity conductor connected to common earth dolly including removing old unserviceable sub main wiring, complete all as specified and directed.(Note : -02 run of 10 sqmm single core copper conductor cable and 2 run of 10 sqmm single core copper conductor cable and 01 run of PVC casing and caping shall be measured as one unit and also colour coding of wiring to be followed as red/yellow/blue for phase, black for neutral and green for earth). |
| 38 | S&F in repacement for LED bulb 15 watt complete all as specified and directed. |
| 39 | S&F in repacement for LED bulb 9 watt rechargable inverter emergency bulb, complete all as specified and directed. |
| 40 | S&F for PVC insulation tape of 6.5m suitable for wires insulations complete all as specified and directed. |
| 41 | S&F in replacement for PVC insulated and sheathed multi - staranded flexible wires 3 core with Copper conductor 1.5 Sqmm, FRLS for wiring complete all as specified and directed. |
| 42 | S&F in replacement for PVC insulated and sheathed multi - staranded flexible wires 3 core with Copper conductor 2.5 Sqmm, FRLS for wiring complete all as specified and directed. |
| 43 | M&L for earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6 mm thick buried directly in ground vertically to a depth not less than 2.25 mtr below ground level with top edge of the earth plate at a depth not less than 1.5 mtr below ground level, earth plate surrounded by and packed with 15 cm thick layer of char coal dust and common salt, earth lead GI wire 4.00 mm dia by means of bolts, Nuts, Check Nuts and washers of galvanized iron and thimbles and other end of the earth wire connected to main switch board and protected by galvanized iron pipe light grade 15 mm bore and water pipe 20 mm bore GI light grade with funnel and wire mesh PCC chamber in cement concrete 1:3:6 type C-1 & RCC cover all as specified & shown in elect plate No. 3 of SSR part I of 2009 including testing on completion including taking down existing unserviceable earthing complete all as specified.(Note:-Earth strip and protection pipe upto board is included in the rate quoted) |
| 44 | S&F in replacement for new generation LED post top lantern light fitting 25watts, 5700k, energy saving, environmental friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminaire with high power LEDs as light source including GI pipe 40mm dia light grade 1.5mtr long (0.3mtr fixed below ground) and fixing arrangementwith base PCC 1:2:4 fixed on wall/floor including suitable size of wire as per requirement and making good the distrubed portion to match with existing surface complete all as specified and directed. |
| 45 | Supply and fixing in replacement energy saving and environmental friendly long life LED bldg security light fitting made up of pressure die cast aluminium housing with acrylic cover as diffuser with IP66 protection and Impact resistance of IK07 and electronic driver of 30W LED 5700K and making necessary connections including street light bracket made out of 25 mm dia GI tubing light grade made to shape 1.2 mtr long dulypainted with synthetic aluminium paint over a coat of primer incl MS clamps and back plates fabricated from steel section including nuts, bolts, washers 02 set complete as in repairs all as specified and directed. |
| 46 | S&F in replacement for environmental friendly, ultra modern, energy saving, surface mounted, decorative oval bulk head 10 watt 6000 K inbuilt LED luminaire comprising of high brightness LEDs, IP54 protection including connecting electricaly using cord flexible 3 core PVC insulated over all sheathed with flexible copper conductor of size 0.75 sqmm complete as in repair all as specified and directed. |
| 47 | Taking down/ dismantling of defective/rusted storage type hot water heater/ Geyser of 50/35/25 Ltr capacity from different locations by disconnecting inlet/outlet connections and taking out unserviceable parts such as glass wool, element, water tank, flange assembly, gasket of any type, nuts/bolts, clamp by unscrewing bolts and nuts, de-scaling/cleaning internally and externally including checking for leakagein tank and rectification by gas welding as required etc. Checking defects, re-assembling and re-installing the Geyser in position after complete servicing, connection and testing to entire satisfaction of Engr-in-Charge.(Note:- Cost of gas welding, nuts/bolts, clamps, shall be deemed to be included in this item and indicating lamp, thermostate, heating element, bottom plate, flange assemble are measured and paid separately as supply only rates and fixing charges for the same shall deemed to be included in this item.) |
| 48 | Supply only Heating element 1.5 KW (ISI marked) round/triangle shape complete all as specified and directed. |
| 49 | Supply only Heating element 2.0 KW (ISI marked) round/triangle shape complete all as specified and directed. |
| 50 | S&F for PVC insulated and sheathed multi - staranded flexible wire 3 core with Copper conductor 2.5 Sqmm round type, complete all as specified and directed. |
| 51 | Supply only Thermostat of range 60-90 degree centigrade adjustable type operative on 250 volts complete all as specified and directed. |
| 52 | Supply only ndication lamp (Green/Red) round/ square as per requirement and complete all as specified and directed. |
| 53 | Supply only Inner tank made out of stainless steel of standard gauge suitable for 25/35 litres capacity geyser make as approved by GE complete all as specified and directed. |
| 54 | Supply only Inner tank made out of stainless steel of standard gauge suitable for 50 litres capacity geyser make as approved by GE complete all as specified and directed. |
| 55 | Supply only for geyser syphon assemble chromimum plated suitable for 50 ltr capacity geyser ISI marked complete all as specified and directed. |
| 56 | Supply only for geyser syphon assemble chromimum plated suitable for 25/35 ltr capacity geyser ISI marked complete all as specified and directed. |
| 57 | S&F in replacement PVC connection 15mm dia (heavy duty) with two nos of brass adaptor and washer of size 450mm to 600mm long for hot/cold water suitable for geyser complete all as specified and directed. |
| 58 | Taking down/ dismantling complete ceiling fan of size 1200/1400 mm sweep and, exhaust fan/pedestal fan/air ciculating fan any sweep from various building (or collecting from MES E/M store yard), opening up for servicing /repair , removing dust and dirt, cleaning fan motor with cotton/waste malmal, washing blades with detergent powder, greasing to serviceable bearings, checking of nuts , bolts, washer, rubber buff, split pin, condensor, MS clamps, rubber packing, condensors block, rubber reel etc for any damages and replacement of damaged and unserviceable items for the smooth and satisfactory functioning, refixing fans etc in same position connecting to electric system and testing complete all as specified and directed. (Note :- Replacement of damaged /unserviceable part shall be measured and paid separetaly). |
| 59 | Rewinding of AC ceiling fan motor 240 volts, 50Hz, 1200/1400mm sweep of any make with super enameled copper winding wire of existing size including sleeve work , varnishing with \"B\" class insulation varnish, connection with flexible copper wire of 0.472mm dia upto connector block including cutting down and removing complete burnt winding after inspection complete all as specifid and directed.Note:- (i) Motor shall be wound with machine with same No of turns as per existing. (ii) Make of copper winding wire as approved by Engr-in-Charge. |
| 60 | Rewinding of exhaust fan motor 240 volts, 50Hz, 300mm sweep of any make with super enameled copper winding wire of existing size including sleeve work , varnishing with \"B\" class insulation varnish, connection with flexible copper wire of 0.472mm dia upto connector block including cutting down and removing complete burnt winding after inspection complete all as specifid and directed.Note:- (i) Motor shall be wound with machine with same No of turns as per existing. (ii) Make of copper winding wire as approved by Engr-in-Charge. |
| 61 | Rewinding of exhaust fan motor 240 volts, 50Hz, 450mm sweep of any make with super enameled copper winding wire of existing size including sleeve work , varnishing with \"B\" class insulation varnish, connection with flexible copper wire of 0.472mm dia upto connector block including cutting down and removing complete burnt winding after inspection complete all as specifid and directed.Note:- (i) Motor shall be wound with machine with same No of turns as per existing. (ii) Make of copper winding wire as approved by Engr-in-Charge. |
| 62 | S&F in replacement for Capacitor AC 415 volts 4 MFD 50 Hz complete all as specified and directed. |
| 63 | S&F in replacement for Capacitor AC 415 volts 2.5/3.15 MFD 50 Hz complete all as specified and directed. |
| 64 | S&F in replacement for fan blade set of 1200/1400mm sweep ceiling fan (as per sample colour/white) complete all as specified and directed. |
| 65 | S&F in replacement for upper/lower canopy of 1200/1400mm sweep ceiling fan (as per sample) colour as per existing fan colour complete all as specified and directed. |
| 66 | S&F in replacement of ball bearing inner and outer of fan of size 6201/6202complete all as specified and directed. |
| 67 | Supply only fan hanging rod of 2.5 feet long including hanging clamps, nuts, bolts, washer and safety pin, complete all as specified and directed |