| 1 | RENOVATION OF CIVIL WORK. |
| 2 | Dismentling existing plaster including disposal of refuse as directed by Engineer-incharge within a distance of 60 meters. |
| 3 | Removing white or colour wash by scraping and sand paering and preparing the surface smooth including necessary to scratch etc complete. |
| 4 | 12 mm cement plaster of mix : 1: 6 (1 cement : 6 coarse sand) |
| 5 | 15 mm cement plaster on rough side of single or half brick wall of mix: 1:6 (1 cement : 6 coarse sand) |
| 6 | Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 metres lead. |
| 7 | Providing and laying of 8 to 10 mm thick ivory or light shade vitrified tiles of 600 mm x600 mm size in flooring or skirt ing laid with 1:3 cement mortar (1 cement :3 coarse sand) finishing with cement slurry & with pigment grouting & polishing complete i/c supply of all materials, labour T &P required for proper completion of work. |
| 8 | Sand filling in plinth under floors including watering, ramming, consolidating and dressing complete including lead up to 50m and lift upto 1.5m and including cost of sand. |
| 9 | Providing and laying cement concrete 1:4:8 (1 cement :4 coarse sand :8 graded Stone aggregate 40 mm nominal size) including supply of all materials, labour T & P rtc required for proper completion of the work and curing complete also including cost of formwork in foundation & floors. |
| 10 | Finishing walls with Acrylic smooth exterior paint of required shade: - New work (Two or more coat applied @ 1.67 Ltr./10 Sqm over and including base coat of water proofing cement paint applied @ 2.20 kg/10 Sqm. |
| 11 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade : New work (two or more coats) over and including water tinnable priming coat with cement primer |
| 12 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 13 | Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 |
| 14 | (1 cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep. e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above |
| 15 | operations to be done in order and as directed and specified by the Engineer-in- Charge :With average thickness of 120 mm and minimum thickness at khurra as 65 mm. |
| 16 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters: |
| 17 | 30 mm thick including ISI marked Stainless Steel butt hinges with necessary screws (single leaf) |
| 18 | 30 mm thick including ISI marked Stainless Steel butt hinges with necessary screws (double leaves) |
| 19 | Providing & Fixing decorative high pressure laminated sheet of plain / wood grain in gloss / matt/ suede finish with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, including cost of adhesive of approved quality. |
| 20 | 1.0 mm thick |
| 21 | Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of flush door shutters (over all area of door shutter to be measured). |
| 22 | Extra for providing vision panel not exceeding 0.1 sqm in all type of flush doors (cost of glass excluded) (overall area of door shutter to be measured): Rectangular or square |
| 23 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works.(M.S. GRILL & Z-SECTION) |
| 24 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): With float glass panes of 5 mm thickness (weight not less than 12.50 kg/sqm) |
| 25 | Disposal of building rubbish / malba / similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping groundor as per direction of engineer-in-charge. |
| 26 | Dismentaling of old damagesanitary & water supply/refuse malvafittings/ installation and disposal of unserviceable materials. or as per direction of engineer-in-charge. |
| 27 | Dismentaling of old damage internal & external electrification work and disposal of unserviceable materials. |
| 28 | Cement concrete flooring 1:2:4 (1 cement :2 coarse sand :4 graded stone aggregate 12-20mm nominal size laid in one layer neat cement (25 mm thick floor). |
| 29 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources). |
| 30 | P/F Mild steel or iron in plain work such as reinforced concrete or reinforced, brick work (when not included in over all rates ) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage bend hooks and authorised over lapping shall be measured upto floor two level. |
| 31 | M.S. or Iron work of small sizes and sections such as holding down bolts, hold fast tie rods, gratings etc. wrought to required from including supply of steel bolts, nuts wastage etc and fixing required for proper completion of the work. |
| 32 | Providing & fabricated of hold fast for chaukhatsof doors and windows. |
| 33 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in:1:4 (1 cement : 4 sand) |
| 34 | Providing and fixing 150 mm bright finished floor brass door stopper with rubber cushion, necessary brass screws etc. to suit shutter thickness complete. |
| 35 | Providing & fixing Stainless steel sliding door bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc complete. (a) 250mm x 16mm . |
| 36 | Providing and fixing stainless steel towerbolts (barrel type) with necessary screws etc. complete.(a) 250 x 10mm |
| 37 | (a) 250 mm x 10mm |
| 38 | Providing and fixing stainless steel handles with screws etc. complete (a) 125 mm |
| 39 | Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and manufacture |
| 40 | Providing & fixing PVC pipes conforming to IS make workinh pressure 6 Kg/cm² including testing, labour, T&P and all complete fittings. 110mm dia |
| 41 | Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and 3 mm M.S. gusset plates at the junctions and corners, all necessary fittings complete, including applying a priming coat of approved steel primerUsing M.S. angels 40x40x6 mm for diagonal braces. Using flats 30x6mm for diagonal braces and central cross piece(Rateof .8222) |
| 42 | ELECTRICAL WORK. |
| 43 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class pvc conduit, with mdular type switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 44 | Group A |
| 45 | Twin Control Point wiring in PVC conduit, with piano type switch :- |
| 46 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class pvc conduit, 2 way piano type switch, phenolic laminated sheet, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 47 | Power plug wiring in PVC conduit (2 x 4 Sq.Mm.) :- |
| 48 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class pvc conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 49 | Power plug wiring in PVC conduit (4 x 4 Sq.Mm.) :- |
| 50 | Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class pvcconduit alongwith 2 Nos. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 51 | Circuit / Sub main wiring in PVC conduit :- |
| 52 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class pvc conduit as required. |
| 53 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire. |
| 54 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire. |
| 55 | 4 x 10 sq.mm. + 2 x 6 sq.mm. Earth wire |
| 56 | S/F light plug point piano type accessories :- |
| 57 | Supplying and fixing metal box of 150 mm X 75 mm X 60 mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 3 pin 5/6 A socket outlet and 5/6 A piano type switch, connections, painting etc. as required. |
| 58 | S/F power plug point piano type accessories :- |
| 59 | Supplying and fixing metal box of 180 mm X 100 mm X 60 mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 A & 15/16 A socket outlet and 15/16 A piano type switch, connections, painting etc. as required. |
| 60 | Supplying and fixing 20 amps, 240 volts, SPN, industrial type socket outlet, with 2 poles and earth metal enclosedplug top alongwith 20amps. \"C\" curve, SP MCB in sheet steel enclosure, on surface or in recess, with chainedmetal cover for the socket outlet, and complete with connections, testingandcommissioning etc. as required. |
| 61 | S/F modular type electronic fan regulator :- |
| 62 | Supply and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 63 | S/F modular type blanking plate :- |
| 64 | Supply and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 65 | Supply and fixing offollowingsizes of medium class PVC conduit along with accessories in surface/recess including cuttingthe wall and making good the same in case of recessed conduit as required : |
| 66 | 20 mm. |
| 67 | Supplying and fixing 5 amps. to 32 amps. rating, 240 volts `C\" series,miniature circuit breaker (MCB)suitable for inductive load offollowingpolesin the existingMCBDBcomplete with connections, testing andcommissioning etc. as required. |
| 68 | single pole |
| 69 | Supplying & fixing single pole, blanking plate in the existing MCBDBcomplete etc. as required. |
| 70 | S/F DP MCB Isolator |
| 71 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. |
| 72 | 40 Amps |
| 73 | 63 Amps |
| 74 | S/F TP MCB Isolator |
| 75 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. |
| 76 | 63 amps. |
| 77 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts,residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existingMCBDBcomplete with connections, testing andcommissioning etc. as required. |
| 78 | 40 amps. |
| 79 | 63 amps. |
| 80 | Supplying and fixing followingway, SP&N, sheet steel,MCB distribution board, 240 V on surface / recess, completewith tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB / RCCB / Isolator) |
| 81 | 6 way, Double door |
| 82 | Supplying and fixing followingway, horizontal type TP&N, sheet steelMCB distribution board,415 V on surface /recess,completewithtinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required (But without MCB / RCCB / Isolators). |
| 83 | 4 way (4 + 12), Double door |
| 84 | Earthing with GI earth plate 600mm x 600 mm x 6mm thick including accessories and providing masonary enclosure withcover platehavinglockingarrangementand watering pipe of 2.7 metre long etc, with charcoal/ coke and salt as required. |
| 85 | Supplying and laying 25 mm x 5 mm.G.I. strip at 0.50 metre belowground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 86 | Providing and fixing 25 mm x 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 87 | Providing and fixing 25mm x 5 mm G.I strip on surface or in recess for connections etc. as required. |
| 88 | Providing and fixing 6 SWG dia G.I. wire onsurfaceorin recessfor loop earthing as required. |
| 89 | Providing and fixing M.V. dangernotice plate of 200mmx150mm made of mild steel, atleast 2mm thick and vitreous enamelled white on both sides and with inscription singleredcolouronFRLSontsideas required. |
| 90 | Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing. |
| 91 | Supplying and fixing Internet Socket outlet modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 92 | Installation, testing and commissioning of pre-wired, flourescent fitting / compact fluorescent fitting of all types, complete with all accessories and tubes etc. directly on ceiling / wall, including connection with 1.5 sq. mm. FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 93 | Installation, testing and commissioning of ceiling fan including wiring the down rod of standard length (upto 30 cm.) with 1.5 sq. mm. FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required. |
| 94 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required |
| 95 | Upto 450 mm sweep |
| 96 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 97 | Supply of LED Tube Light with Metal heavy duty Box type batten Light fitting 1X22 watt suitable for upto 1X22 watt LED Polycarbonate tube light complete Including tube suitable for both surface & suspended complete in all respect. |
| 98 | Supplyof LED Tube Light with Metal heavy duty Box type batten Light fitting 2X22 watt suitable for upto 2X22 watt LED Polycarbonate tube light complete Including tube suitable for both surface & suspended complete in all respect. |
| 99 | Supply of recess/surface mounting round 10 W to 15 W LED Cut out Min 125 mm, Height Min. 40mm, LED Down lighiter having powder coated die cast aluminium housing with heat shink,diffuser/reflector and driver set. suitable for 24Hr Continuous Operation, Complete in all respect. |
| 100 | Supply of 225/230mm sweep ventilating (Light Duty) exhaust fan complete with Metallic Blade (Steel bird guard protector /Copper motor for high air suction performance /Capacitor etc.), Noise level : (45 - 50) dB, Power consumption : 45 W, Rated voltage : 230 V, Rated frequency : 50 Hz, Motor type : Normal Speed. Complete in all respect. |
| 101 | 230 mm sweep |
| 102 | Supplyandlayingof aluminiumconductorPVCinsulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 103 | 16 sq. mm 4 core |
| 104 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. |
| 105 | 16 sq. mm 4 core |
| 106 | 3½ X 35 sq. mm (35mm) |
| 107 | GST extra as per applicable |