| 1 | Surface dressing n.exc (not exceeding) 15 cm deep and getting out Hard/dense soil. |
| 2 | Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on planand n exc 1.5 m in depth and getting out soft/Disintegrtated rock complete all as specified. |
| 3 | M&L for plain cement concrete 1:3:6 type D-2 (using 40mm graded stone aggregate) as in foundation, filling & mass concrete, sub base complete all as specified. |
| 4 | M&L for plain cement concrete 1:4:8 type D-2 (using 40mm graded stone aggregate) as in foundation, filling & mass concrete, sub base complete all as specified. |
| 5 | M&L for providing reinforced cement concrete (M-25) Design Mix using 20 mm graded stone aggregates as infoundations, including rafts, footings, foundation beams; plinth beams; bases for columns, etc.; basement slabs, under-reamed piles and mass concrete complete all as specified. |
| 6 | M&L for providing reinforced cement concrete (M-25) Design Mix using 20 mm graded stone aggregates as inColumns, pillars, piers, posts and struts complete all as specified. |
| 7 | M&L for providing reinforced cement concrete (M-25) Design Mix using 20 mm graded stone aggregates as inSlabs supported on walls,beams and columns in floors,roofs, complete all as specified. |
| 8 | M&L for providing reinforced cement concrete (M-25) Design Mix using 20 mm graded stone aggregates as in Beams, cantilevers, bressummers, lintel over 1.5 span complete all as specified. |
| 9 | Use of formwork to sides of concrete foundations, footings, bases of columns, raft and raft beams, sides and soffits (if any) of foundation and plinth beams; and similar work; vertical or to batter (rough finished surface) complete all as specified. |
| 10 | Use of formwork to sides of pillars,posts, struts, piers, columns and stanchions (square/rectangular/ polygonal) rough finished surface complete all as specified. |
| 11 | Use of formwork to soffits of suspended slabs such as roof slabs, floorslabs, landings and similar work not exceeding 200 mm thick rough finishedin flat surface complete all as specified. |
| 12 | Use of formwork to sides and soffits of floor or roof beams, beam haunchings,girders, bressummers,lintels, cantilevers, shelvesincluding supports,overhangs,etc. also splays between floors in rough finished flat surfaces and etc complete all as specified. |
| 13 | Use of formwork to edges of concrete flats, treads, breaks in floors, window cills, concrete rail ings, openings in concrete walls, floor and roofs n exc 20 cm wide and sides of RCC/ PCC bands in walls, horizon tal or sloping and similar work exc 10cm but n exc 20cm wide (rough finished surface)complete all as specified. |
| 14 | M&L for Mild steel TMT bars 10 mm dia and over, cut to length, bent to shape required including cranking, bending for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia or securing with clips etc complete all as specified. |
| 15 | All as peritem No. 15 above but 5 mm dia & over upto & including 10 mm dia in stirrups,spacers and binders, complete all as specified. |
| 16 | S&F Hand rails, half round or other steel section or core for wooden hand-rail straight portion, drilled and countersunk for balusters running bars, for doors, balusters, nosing to steps including embeding in concrete and screwing etc. wind ties for roof including securing bolts; posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming to Fe-290 Gde E-165 |
| 17 | M&L prepration of new Steel surfaces of any description, not otherwise described, over 10cm width or girth & applying two coats of synthetic enamel paint over coat of red oxide primer complete all as specified |
| 18 | M&L for brick work with flyash bricks, straight or curved on plan exc 6.0 mtr mean radius built in cement mortar 1:6 etc complete all as specified. |
| 19 | M&L for rendering 15 mm thick in cement mortar (1:6) onbrick work or concrete surfaces finished even and smooth (without using extra cement) complete all as specified. |
| 20 | M&L for 15 mm thick plastering in two layers (10+5) mm in cement mortar (1:4) on brick or concrete surfaces including rendering on fins, fascias, chajja, parapets etc and finishing the surfaces even and fair (without using extra cement), top layer shall be with WPC as per manufacturer\"s instruction and complete all as specified.Note: WPC shall be measured and paid separately. |
| 21 | M&L rendering 10mm thick in cement mortar (1:3) as in ceilings finished even and smooth (without using extra cement) complete all as specified. |
| 22 | M&L for preparation ofnewly plastered or unplastered/undecorated surface of wall and applying two coats of oil bound distemper over one coat of primer complete all as specified. |
| 23 | M&L for preparation ofnewly plastered or unplastered/undecorated surface of ceiling and applying two coats of oil bound distemper over one coat of primer complete all as specified |
| 24 | M&L Preparing of new surface of wall and applying twocoatsofexterior emulsion paint over a coat primer on walls complete all as specified and directed by Engineer-in-charge. complete all as specified and as directed by Engineer-in-Charge . |
| 25 | Supply only intergral water proofing compound ISI Marked complete all as specified. |
| 26 | M&L for Hardcore (broken stone or boulders) of gauge n exc. 63 mm, deposited, spread and levelled in layers n exc. 15 cm thick, watered and rammed to a true surface complete. |
| 27 | M&L for sand filling under floors or in foundations including watering and consolidation complete all as specified. |
| 28 | M&L for 75 mm thick cement concrete (1:4:8) type D-2 (using 40 mm graded stone aggregates) asin sub base of flooing etc complete all as specified. |
| 29 | M&L for cement concrete(1:2:4) type B-0 (using 12.5 mm graded stone aggregates) 25 mm thick as in sub base of flooring/tiles etc completeall as specified. |
| 30 | M&L for screed bed or bedding layer of mortar 15 mm thick in cement mortar (1:4)for bedding of tilescomplete all as specified. |
| 31 | M&L 10 mm thick rendering in cement mortar (1:3) on vertical surfaces for backing of tiles/granite etc complete all as specified. |
| 32 | M&L for 18-20 mm thick machine cut kota stone slab as in flooring, steps of stair(treads), set with neat grey cement slurry @ 3Kg/Sqm, laid over and including 20mm thick cement and sand mortar (1:6) screed bed/bedding layer, jointed with grey cement slurry mixed with pigment to match the sahde of the slab including rubbing and polishing damaged stone slab of any description complete all as specified |
| 33 | M&L for 18-20 mm thick machine cut kota stone slab as in riser of steps, skirting, dedo and pillar, laid over and including 15mm thick cement and sand mortar (1:6) screed bed/bedding layer, jointed with grey cement slurry mixed with pigment to match the sahde of the slab including rubbing and polishing damaged stone slab of any description complete all as specified |
| 34 | M&L for Non - skid (joint free) coloured Ceramic coloured tiles 7 to 8 mm thick area of each tile exceeding 0.11 sqm but not exceeding 0.18 sqm, in floors/skirting etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match complete all as specified. |
| 35 | M&L for Glazed ceramic colouredtiles in vertical surface 450X 300X 6 mm thick set and jointed in neat cement slurry and pointed in white or colour cement to match complete all as specified. |
| 36 | M&L for PCC 1:2:4 type B1 (using 20mm graded stoneaggregates) as in lintels upto 1.5m clear span, cills, steps, seismic and other similar bands, plinth courses, coping, bed plates and the like including weathering, slightly rounded or chamfered edges and throating including necessary form work, complete all as specified. |
| 37 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm thick with soft/loose soil etc complete all as specified. |
| 38 | Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified. |
| 39 | M&L for Treating the top surface of filled earth at the rate of 5 litres of emulsion per square metre of surfacecomplete all as specified. |
| 40 | M&L for Treating the soil under plinth protection at the rate of 5 litres of emulsion per square metre of surface areacomplete all as specified. |
| 41 | M&L for 15 mm thick plaster in cement mortar (1:4) mixed with water proofing compound on roof slabs finished even and smooth without using extra cementcomplete all as specified.Notes : WPC shall be measured and paid seperately. |
| 42 | M&L for water proofing treatment with 3mm APP (Atactic Polypropylene) modified polymeric prefabricated five layer membrane over roof consisting of cleaning of concrete or plaster surface of roof & parapet walls and applying evenly a bitumen primer confirming to IS 3488 @ 0.40 Kg per sqmlaid using buten torch and sealing all joints of APP modified polymeric water proofing membrane minimum weight 3.6 kg/sqm reinforced with non woven polyester fabric (weight not less than 160 grams per sqm) unrolled and bonded to substrata with logitudinal and end laps 100 mm and 150 mm respectively as per manufacturer\"s instructions incl two coats of water proofing paint with aluminium finish on top complete all as specified. |
| 43 | Providing and fixing factory made uPVC white colour sliding glazed window upto 1.50 m in height dimension comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension of uPVC extruded glazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of holes for fixing hardware\"s and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes, wire mesh and silicon sealent shall be paid separately). Variation in profile dimension in higher side shall be accepted but no extra payment on this account shall be made. Note: For uPVC frame and sash extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable. |
| 44 | Three track three panels sliding window with fly proof S.S wire meshmade of (big series) frame 116 x 45 mm & sash 46 x 62 mm both having wall thickness of 2.3 ± 0.2 mm and single glazing bead / double glazing bead of appropriate dimension. (Area of window above 1.75 sqm). |
| 45 | Providing and fixing factory made uPVC white colour casement/ Casement cum fixed glazed door comprising of uPVC multi-chambered frame, sash and mullion (where ever required) extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), uPVC extruded glazing beads of appropriate dimension, EPDM gasket, zinc alloy (white powder coated) 3D hinges and one handle on each side of panels along with zinc plated mild steel multi point locking having transmission gear, cylinder with keeps and one side key, G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws, etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, mullion (if required) shall be also fusion welded including drilling of holes for fixing hardware\"s and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes shall be paid separately). Variation in profile dimension in higher side shall be accepted but no extra payment on this accoun shall be made.Note: For uPVC frame, sash and mullion extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable. |
| 46 | Casement door with 3D hinges made of (big series) frame 67 x 64 mm & sash 67 x 110 mm both having wall thickness of 2.3 ± 0.2 mm and single glazing bead / double glazing bead of appropriate dimension. (Area of door upto 2.00 sqm) |
| 47 | S&F sheet glass 4.8mm thick ordinary quality and glazing with oil putty in square exc 0.5 sq. m in each pane complete all as specified. |
| 48 | S&F sheet glass 5.5mm thick ordinary quality and glazing with oil putty in square exc 0.5 sq. m in each pane complete all as specified. |
| 49 | Surface excavation n.exc (not exceeding) 30 cm deep and averaging 15cm deep and getting out soft/disintegrated rock.Complete all as specified |
| 50 | M&L 100 mm thick PCC 1:4:8 tybe D-2 using 40mm stone aggregate as in subbase.Complete all as specified |
| 51 | M&L for providing and laying 60 mm thick factory made chamfered edge cement concrete paver block of M-35 grade with approved, design & pattern as in footpath , parks , lawns,drive ways or light traffic parking etc. of required strength , thickness & size/shape, made by table vibratory method using PU mould , laid in required colour & pattern over and including 50 mm thick compacted bed of fine sand , compacting and proper embedding/laying of interlocking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator,filling joints with sand andcutting of paver block as per required size and pattern,finishing and sweeping extra sand. Complete all as specified |
| 52 | M&L for screed bed or bedding layer of mortar 20 mm thick in cement mortar (1:6)for bedding of tilescomplete all as specified. |
| 53 | M&L for 22-25 mm thick chequered designer coloured tiles (matt/glass finish), size, colour and shape as approved by GE, set and jointed in neat cement slurry and pointed with coloured cement to match etc complete all as specified as directed. |
| 54 | Excavating in post holes (or similar holes) each n exc 0.5 cum, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm and getting out soft/loose soil complete all as specified. |
| 55 | M&L for cement concrete type B-1, 1:2:4 (40mm graded stone aggregate) as in foundations, filling and mass concrete complete all as specified. |
| 56 | S&F Steel work in tubular trusses including special shaped washer etc. complete using ERW or induction butt welded tubes conforming to I. S.1161- 1979 grade St.-240 complete all as specified. |
| 57 | S&F Plates (plain or chequered) channels,squarecutor notched (ordinaryand countersunk) forming holes, without any attachmentFe 410 -W (Gde E- 250) quality A all as specified. |
| 58 | S&F Pre- painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws as specified. |
| 59 | S&F Pre-painted galvalume aluminum zinc coating GI based Plain steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws as specified |
| 60 | E/M SCHEDULE |
| 61 | M&L for point wiring with two runs of FRLS PVC insulated unsheathed, 1100 V grade cable multi stranded copper conductor of Size 1.5 sqmm drawn through in and including concealedPVC conduit Size of not less than 20mm concecled in wall / surface including provn of pressed steel terminal boxof suitable Size with 3mm thick plastic laminated sheet cover / modular white cover plate with frame as required module & modular metal flush box as required module for mounting switch, socket and fan regulator along with earth wire of PVC insulated, unseathed,1100 V grade cable multi stranded copper conductor of Size 1.5 sqmm and making good, disturb surface as it is, all asspecified and directed for the following.Note :- Colour coding of cable should be Phase- Red, Neutral- Black and Earth- Green |
| 62 | One light pointcontrolled by one,one wayswitch. |
| 63 | One ceiling fan/exhaust fan/Air ciculator /bell point controlled by one way switch. |
| 64 | Socket 3 pin 5 Amps on the same board, complete all as specified. |
| 65 | Socket 3 pin 5 Amps on independent board , complete all as specified and directed. |
| 66 | M&L for point wiring with two runs of FRLS PVC insulated unsheathed, 1100 V grade cable multi stranded copper conductor of Size 2.5 sqmm drawn through in and including concealedPVC conduit Size of not less than 20mm concecled in wall / surface including provn of pressed steel terminal boxof suitable Size with 3mm thick plastic laminated sheet cover / modular white cover plate with frame as required module & modular metal flush box as required module for mounting switch, socket and fan regulator along with earth wire of PVC insulated, unseathed,1100 V grade cable multi stranded copper conductor of Size 2.5 sqmm and making good, disturb surface as it is, all asspecified and directed for the following.Note :- Colour coding of cable should be Phase- Red, Neutral- Black and Earth- Green |
| 67 | M&L for sub main wiring with two single core 2.5sqmm stranded copperconductor PVC insulated and unsheathed cable ISI- marked in 25 mm dia, medium grade, PVC conduit concealed in wall for sub main connection including 2.5 Sqmm PVC insulated unsheathedcopper conductor ISI- marked as earth wire complete all as specified and directed by Engr-in-charge. |
| 68 | S&Ffor socket outlet 5 Amps, 5 pin flush type, 240 volts, ISI marked with polycarbonate body. complete all as specified and directed.. |
| 69 | S&Ffor socket out let, 6 pin 5/15 Amps multi purpose 2 in 1 flush type, 240 volts,ISI marked with polycarbonate body.complete all as specified and directed. |
| 70 | S&Ffor switch piano flush type single pole one way 5 Amps 240 volts,ISI marked with polycarbonate body complete all as specified and directed.. |
| 71 | M&L for switch piano flush type singlepole two way 15 Amps 240 volts,AC 50 Hz ISI marked with polycarbonate body complete all as specified and directed.. |
| 72 | S&F For ceiling fan regulator stepped electronic type 300 watt rating, 230 volts,AC 50 Hz ISI marked with polycarbonate body complete all as directed. |
| 73 | M&L for ceiling rose 3phase/PVC 62x50 mm throw terminal polycarbonate isolated body complete all as specified and directed |
| 74 | Supply and fixing ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM withBEE star rated with brushless direct current motor complete. |
| 75 | Supply and fixing LED building light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection and L shape GI pipe bracket of 40 mm dia. complete. |
| 76 | S&F in replacement of MCB DB sheet enclosure load line Singlepole and neutral 240V with 200 Amp suitable Size plate and common neutral link all enclosed in standard steel sheet flush mounting type factory fabricatedAcrylic double door complete confirming to IP 43with enclosure blank plates for unusedway suitable for 4 way complete all as specified and directed : |
| 77 | S&F MCBs240/415 Volts 10 KA finger proof terminal, bi-connect termination, label holder, 35 mm² terminal capacity, insulated sliding shutter, large two position dolly, ISI markedto be fixed on DB . (DB will be measured and paid separately under respective items of sch A):- |
| 78 | (a) MCBC curve SPN 40 to 63 Amps. |
| 79 | (b) MCBB curve SP 5 to 40 Amps |
| 80 | Supply and fixLED lights fitting 1x 22W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable Size from ceiling rose completeall as specified and as directed .Make :- Phillips/ Bajaj/CG |
| 81 | Supply and fixLED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable Size completeall as specified and as directed .Make :- Phillips/ Bajaj/CG |
| 82 | M&L for earthing complete with galvanized mild steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 Mtr below ground level) with top edge of earth plate not less than 1.5 Mtrs below ground level connected to GI wire 4 mm Dia as earth lead by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, including PCC (concrete chamber) shall be PCC 1:3:6 type C-1 uSI-ng 20mm graded stone aggregate, with fair finish internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire gauge mesh, 80 mm thick RCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 uSI-ng 20 mm graded stone aggregate reinforced with XPM, JALLI and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I (2009) and specified includingproviSI-on 20 mm dia medium grade pipe and watering pipe shall be 20mm bore medium grade, and including all excavation andearth work & connecting the earthing to an earthing test point complete all as specified & directed . NOTE: (i) The concrete pit shall be PCC 1:3:6 type C-140 mm thick pre cast cover slab of RCC(1:2:4) type B-1 uSI-ng 20 mm graded stone aggregate reinforced with 8 mm TMT bars @ 10 cm C/C on both SI-des with suitable cast iron handle shall be provided in lieu of cost iron cover shown in the electrical plate No.3 of MES SSR Part -1 (ii) item includes the cost of 7.5 m GI pipe for protection of GI wire.(iii) PCC pits extra cost of addtional length of watering pipe,bends elbows etc.shall be deemed to be included in the quioted rate. (iv) Item includes the cost of 7.5 mtr length Galvisedwire 4 mm dia. |
| 83 | Supply , laying , jointing and testing XLPE armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 4 Sq mm 2 Core complete all as directed. |
| 84 | M & L boring of holes under road pavment hard standing by trenchless technology using ultra sound technique and necessary machine incl HDPE pipe of 50 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed by Engr-in-charge. |
| 85 | M&L for Excavation in trenches in soft/loose soil n.exc 1.5 m wide and n. exc 1.5 m in depth for foundation or shaft, wells,cespits, manholes, pier holes, cable laying, sewage/ water line etc complete all as specified and directed. |
| 86 | M&L for Removal of surplus soil to a distance n. exc 50 mtr and depositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified. |
| 87 | M&L for Returning filling in soft/loose soil including spreading,watering,leveling and well ramming in layers not exc 25 cm complete all as specified. |
| 88 | M&L for sand cushioning with a layer of sand 80mm thick before laying of cable and 150mm thick after laying of cable to trenches complete all as specified and directed |
| 89 | M&L for brick protection cover of UG cable by old size bricks common burnt clay building bricks sub class `B’ laid dry and flat abutting each other with width equal to length of brick and gap between adjacent brick not exceeding 10mm complete all as specified and directed |