Supply, Survey, Erection, Testing and Commissioning for Creation of 2 Nos 100 KVA pole mounted sub stations under JJM stage-I & Stage-II at Lower Maha Kund, and 2 Nos 100 KVA pole mounted sub stations under JJM stage-I & Stage-II at Surranda, Ramban under the Jurisdiction of Electric Division, JPDCL Batote- 1 Creation of 2 Nos 100 KVA pole mounted sub stations under JJM stage-I & Stage-II at Lower Maha Kund, Ramban 2 11/0.433KV, 3-phase Aluminium wound 100 KVA Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, , and with LV Cable Box having detachable Aluminium Gland plate 3 Gapless Surge Arrestor,9 KV ,10 KA ,LA with (polymer/porcelain) housing, Stn. Type 4 11 kV G.O AB Switch , 3-phase, 3 pole 200 Amp. Vertical type 5 11 kV Horn Gap Fuse Set 3 Phase3 pole, 200 Amp 6 185 mm²Cable, 1.1kV Grade, PVC Insulated Stranded Conductor FRLS type 7 9 Mtr. Long Pole( ST-540 SP33) 8 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm 9 GI Channel/Angle/Flat of sizes including clamps 10 Chainlink Fencing of Sub station Yard by way of mass concrete in foundations and chain link fenscing of 6 Ft Height. 11 Galvinized Nuts and Bolts. 12 Earthing of substation --Excavation of earth pit of dia 650 mm &depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 75 mmx10 mm & 50mmx6 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. 13 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm 14 LT Fuse set 15 Wedge Connectors / PG Clamps 16 Danger Plates with Clamps 17 GI Barbed Wire for Anti Climbing 18 Cement bottoming 1:2:4 mix as per REC standards .5cum /pole 19 Painting of Poles Red Oxide 20 Painting of Poles Aluminium Paint 21 Sundry items like aluminium lugs, Jumpers, binding Tape 22 Erection of HT line on 9 mtrs ST Poles with 30mmsq Conductor for Creation of 2 Nos 100 KVA pole mounted sub stations under JJM stage-I & Stage-II at Lower Maha Kund, Ramban 23 9 Mtr ST pole (ST-410 SP 33) 24 GI V Cross Arm with top bracket including Clamp 25 GIchannel x-Arm including Clamps and braces 26 11 KV Polymer Composite Pin Insulator 27 30 mm Sq ACSR Conductor 28 PG Clamps for 30 mm sq ACSR Conductor 29 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm 30 Galvanized Nuts and Bolts 31 Danger Plates with Clamps 32 Anti Climb Device With Clamp 33 Earthing of Poles complete by G.I pipe 40mm or GI Rod 20mm 2.5 mtr long through GI Strip 34 Red Oxide 35 Aluminnium Paint 36 Cement Bottomming 1:2:4 mix as per REC Standards 0.5cum per pole 37 Creation of 2 Nos 100 KVA pole mounted sub stations under JJM stage-I & Stage-II at Surranda, Ramban 38 11/0.433KV, 3-phase Aluminium wound 100 KVA Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, , and with LV Cable Box having detachable Aluminium Gland plate 39 Gapless Surge Arrestor,9 KV ,10 KA ,LA with (polymer/porcelain) housing, Stn. Type 40 11 kV G.O AB Switch , 3-phase, 3 pole 200 Amp. Vertical type 41 11 kV Horn Gap Fuse Set 3 Phase3 pole, 200 Amp 42 185 mm²Cable, 1.1kV Grade, PVC Insulated Stranded Conductor FRLS type 43 9 Mtr. Long Pole( ST-540 SP33) 44 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm 45 GI Channel/Angle/Flat of sizes including clamps 46 Chainlink Fencing of Sub station Yard by way of mass concrete in foundations and chain link fenscing of 6 Ft Height. 47 Galvinized Nuts and Bolts. 48 Earthing of substation --Excavation of earth pit of dia 650 mm &depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 75 mmx10 mm & 50mmx6 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. 49 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm 50 LT Fuse set 51 Wedge Connectors / PG Clamps 52 Danger Plates with Clamps 53 GI Barbed Wire for Anti Climbing 54 Cement bottoming 1:2:4 mix as per REC standards .5cum /pole 55 Painting of Poles Red Oxide 56 Painting of Poles Aluminium Paint 57 Sundry items like aluminium lugs, Jumpers, binding Tape 58 Erection of HT line on 9 mtrs ST Poles with 30mmsq Conductor for Creation of 2 Nos 100 KVA pole mounted sub stations under JJM stage-I & Stage-II at Surranda, Ramban 59 9 Mtr ST pole (ST-410 SP 33) 60 GI V Cross Arm with top bracket including Clamp 61 GIchannel x-Arm including Clamps and braces 62 11 KV Polymer Composite Pin Insulator 63 30 mm Sq ACSR Conductor 64 PG Clamps for 30 mm sq ACSR Conductor 65 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm 66 Galvanized Nuts and Bolts 67 Danger Plates with Clamps 68 Anti Climb Device With Clamp 69 Earthing of Poles complete by G.I pipe 40mm or GI Rod 20mm 2.5 mtr long through GI Strip 70 Red Oxide 71 Aluminnium Paint 72 Cement Bottomming 1:2:4 mix as per REC Standards 0.5cum per pole 73 Erection of LT line on 8 mtrs ST Poles with 30mmsq Conductor for Creation of 1 Nos 100 KVA pole mounted sub stations under Stage-II at Surranda, Ramban 74 8 Mtr ST pole (ST-410 SP 15) 75 Clamp for Shakle Insulator 76 30 mm Sq ACSR Conductor 77 16 kN Polymer Shakle Insulator 78 Galvanized Nuts and Bolts 79 Danger Plates 80 Anti Climb Device With Clamp 81 Earthing of Pole 82 Red Oxide 83 Aluminnium Paint 84 Cement Bottomming 1:2:4 mix as per REC Standard