Tender For Supplying And Installation Of Power Points And Industrial Power Sockets In Materials Science And Engineering Lab At A14 Block At North Campus. - Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. Supplying and drawing 3x2.5 sq mm of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit/Casing/Wall Trunk as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. Supplying and drawing 3x4 sq mm of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit/Casing/Wall Trunk as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. Supplying and drawing 6x4 sq mm of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit/Casing/Wall Trunk as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. Supplying and fixing 5/6 A switch modular switch on the existing modular plate & switch box including connections but excluding modular plate etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. Supplying and fixing 15/16 A switch modular switch on the existing modular plate & switch box including connections but excluding modular plate etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. Supplying and fixing 3 pin 5/6 A socket outlet modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. Supplying and fixing 6 pin 15/16 A socket outlet modular socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. Supplying and fixing 6 Module Modular base & cover plate on existing modular metal boxes etc. as required as per entire satisfaction and direction of Engineer-incharge including carriage of material in all leads and lifts. Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required Upto 450 mm sweep Providing and fixing 125 A,36KA,FPMCCB rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. Supplying and fixing of 12 way (4 + 36), Double door surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) Supplying and fixing Single pole 5 to 32 amps rating, 240/415 volts, C curve, miniature circuit breaker suitable for inductive load of Single pole, in the existing MCB DB complete with connections, testing and commissioning etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. Supplying and fixing Triple pole 32 amps rating, 240/415 volts, C curve, miniature circuit breaker suitable for inductive load of Single pole, in the existing MCB DB complete with connections, testing and commissioning etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A C curve,SP MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 30 A C curve, FPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of 35 sq. mm up to 95 sq mm (clamped with 25x3mm MS flat clamp) on cable Tray as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. Supplying and making end termination with brass compression gland and aluminium lugs for 3½ X 95 sq. mm (45mm) size of PVC insulated and PVC sheathed / XLPE copper conductor cable of 1.1 KV grade as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. Supply of Metal Body Exhaust Fan Sweep 300 mm ,Air Delivery 1050 m3/hr, Speed 1325 rpm, Power Input 63 W, suitable for operation on 230 V 50 Hz supply, etc as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. Cutting holes of required size in brick masonary wall for fixing of exhaust fan and making good the same etc. as per entire satisfaction and direction of Engineer-incharge including carriage of material in all leads and lifts. Supplying of 3.5 Core x 95 Sq. mm of 1.1 KV aluminium conductor XLPE Insulated,PVC inner-sheathed amoured, Extruded PVC Type ST2 Outer Sheathed, 650 V/1100 V Grade as per IS 7098 (Part 1) 1988 with upto Date Amendments as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. Supplying and fixing of 100 X 100 mm size of uPVC maxi trunking along with accessories including coupler, tee, elbow, internal bend, external bend etc. in surface as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. Supplying and fixing 6 Module PVC box to be fixed on Recess or in Open Surface as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts.