| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor singlecorecableinsurface /recessedmediumclassPVC conduit, with modular switch, modular plate, suitable GI box and earthingthepointwith 1.5sq.mm FRLSPVC insulated copper conductor single core cable etc. as required. |
| 2 | Group B |
| 3 | Wiringforlight/powerplugwith 2X4sq.mmFRLSPVC insulatedcopperconductorsinglecorecableinsurface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 4 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 5 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 6 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 7 | Supplying and fixingtwo module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 8 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 9 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 10 | Supplying and fixing 3pin, 5A ceiling rose on the existing junctionbox/woodenblockincludingconnectionsetc.as required. |
| 11 | Supplyingandfixingbrassbatten/angleholderincluding connection etc. as required. |
| 12 | Installation ,Testing,Commissioningofwallbracket/ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lampsperfitting,completewithallaccessoriesincluding connections etc. as required. |
| 13 | Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required. |
| 14 | Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 15 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. |
| 16 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. |
| 17 | Upto 450 mm sweep |
| 18 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar,din bar,interconnections,powderpaintedincluding earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 19 | 12 way , Double door |
| 20 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of followingpolesintheexistingMCBDBcompletewith connections, testing and commissioning etc. as required. |
| 21 | Single pole |
| 22 | Supplyingandfixingfollowingrating,doublepole, 240V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 23 | 40 A |
| 24 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet,with 2poleandearth,metalenclosedplugtop alongwith 20 A \"C\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 25 | EarthingwithG.I.earthpipe 4.5metrelong,40mmdia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 26 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 27 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 28 | Supplying of 9 watt B22 lamp Make: Havells Cat No. Panasonic Cool Day bulb or its equivalent to ISI standard. |
| 29 | Supply of metallic exhaust fan 200mm sweep of make: Havells DXW Celso or its equivalent to ISI Standard. |
| 30 | Supplying of 20W LED Bulk Head fittings of make Crompton bearing Id No. SKU-4044 complete or its equivalent to ISI Standard etc as required. |
| 31 | Supplying of 20W ultraslim LED Batten with LED tubes white CDL of make: Eveready or its equivalent to ISI Standard. |
| 32 | SupplyingBLDC ceiling fan 1200mm sweep,without remote of make: Automberg Renessa Prime or equivalent to ISI Standard. |
| 33 | Providing and erection of single phase metering box made out of SMC of size 250 x 250 x 155with hinged cover and locking arrangements, viewing glass etc. as required similar to Sintex Model No. GSMB 2525. |