| 1 | Dismantling the existing Electrical Fittings-fixtures by engaging Manpower [1(One)No Semi Skilled Electrician + 1 (One)No Helper Electrician] and Co\"s own tools & tackleswith proper care of electrical equipments and appliances as per direction of EIC and shifting of dismantling materials to the section offfice or section office to site if and whenever required |
| 2 | DBs,MCBsSupplying and fixing 415V,100/125A TPN with fuse on L&N Sheet steel Main Switches on angle iron frame on wall ( Make-Havells/Equivalent approved make as per direction of EIC) |
| 3 | Supplying and fixing 8 Way double door Vertical TPN MCB Distribution board for Up to 160A MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachmen [ Make - Legrand Enclosure (607914)/Schneider/Siemens ] |
| 4 | Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for 4/8 Way TPN DB vertical enclosure with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish with nuts bolts etc incl. provision for earthing attachment |
| 5 | Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection (80A-FP) (Make :- LEGRAND, ABB, SIEMENS, CRABTREE, SCHNIDER) |
| 6 | Supplying and fixing 6 Way double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachmen[ Make - Legrand Enclosure(607716)/Schneider/Siemens ] |
| 7 | Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for 6 Way TPN DB horizontal enclosure with IP-42/43 protection, embeded in wall & mending good the damages to original finish with painting etc incl. provision for earthing attachment |
| 8 | S&F double-door (2+12) Way SPN MCB Distribution Board with IP-42/43 protection,on wall. With the help of necessary fastening accessories[Make: Legrand Enclosure (607712) /PWD approved make as per direction of EIC] |
| 9 | S&F double-door (2+16) Way SPN MCB Distribution Board with IP-42/43 protection,on wall. With the help of necessary fastening accessories[Make: Legrand Enclosure (607713)/PWD approved make as per direction of EIC] |
| 10 | Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for (2+12) Way SPN DBenclosure with IP-42/43 protection,embeded in wall & mending good the damages to original finish with painting etc incl. provision for earthing attachment |
| 11 | Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for (2+16) Way SPN DBenclosure with IP-42/43 protection,embeded in wall & mending good the damages to original finish with painting etc incl. provision for earthing attachment |
| 12 | Supplying and fixing 240/415 V Isolator on din rail of existing DBs and necessary connection. [Make: Legrand/PWD approved make as per direction of EIC]240 V, 40A DP. |
| 13 | Supplying and fixing 240/415V,MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection.[Make: Legrand /PWD approved make as per direction of EIC] |
| 14 | 6A - 32A SP MCB. |
| 15 | 40A TP MCB |
| 16 | 63A TP MCB |
| 17 | Supplying and fixing FP 40A ,415 V change over(MCB module) ofon din rail of existing DBs/ enclosure and necessary connection.[Make: Legrand /PWD approved make as per direction of EIC] |
| 18 | Supplying and fixing Four Poles(Normaly Open contacts) 40A ,415 V power Contactor (MCB module) ofon din rail of existing DBs/ enclosure and necessary connection.[Make: Legrand Model No. CX3with Cat. No.- 4125 53/ Or Exact Equivalent as approved by the EIC] |
| 19 | Supplying and fixing 15A ,240 V 2 Module Key card switch and necessary connection.[Make: Legrand Model - Myrius with Cat. No.- 6792 53/ Or Exact Equivalent as approved by the EIC] |
| 20 | Supplying and fixing 15A ,240 V Key Fob for 2 Module Key card switch and necessary connection.[Make: Legrand Model - Myrius with Cat. No.- 6792 55/ Or Exact Equivalent as approved by the EIC] |
| 21 | Distribution WiringDistribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) + 1x22/0.3 (1.5 sqmm) for ECC single core stranded \"FR\" PVC insulated & unsheathed copper wire (Polycab/Havells/KEI or Brand approved by EIC) in suitable size PVC casing-capping (Precision make MMS) [for horizontal run & ceiling portion] and partly in 19mm bore, 3mm thick polythene concealed pipe [for vertical run embedded in wall only],incl. necy. fittings etc. to light/fan/call bell points with Modular type switch (Make:Legrand: Myrius White/As per Direction of EIC) fixed on Modular GI switch board with top cover plate and 2 no. suitable size “Ph, N & E” copper bar & earthing attachment flushed in wall incl. mending good damages to original finish [PVC casing-capping on Wall and ceiling ,vertical & switch box both concealed] |
| 22 | Average run 9 mtr |
| 23 | Distribution wiring in1.1KV grade 2x22/0.3 (1.5sqmm ) single core stranded \"FR\" PVC insulated & unsheathed copper wire (Polycab/Havells/KEI or Brand approved by EIC) partly in 20mmsize PVC rigid conduit \"FR\" (Precision make MMS) [for horizontal run & above false ceiling portion only] and in19 mm bore, 3 mm thick polythene pipe [for vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded \"FR\" PVC insulated & unsheathed copper wire for ECC, tolight/fan/cal lbel lpoints with Modular type switch(Make:Legrand: Myrius White/As per Direction of EIC) fixed on Modular GI switch board complete with 3 no. suitable size “Ph, N & E” copper bar with top cover plate making earthing attachment fixed onwall incl. mending good damages to original finish. [PVC Rigid Conduit only for horizontal run & above false ceiling and vertical run concealed] |
| 24 | On Board |
| 25 | Average run 9 mtr (Inverter Lines are included and the Colour of the Switches will be Black/Chocolate or as per direction of EIC) |
| 26 | Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded \"FR\" PVC insulated & unsheathed copper wire (Polycab/Havells/KEI or Brand approved by EIC) in 20mm size PVC rigid conduit \"FR\" (Precision make MMS), with 1x22/0.3 (1.5 sqmm) single core stranded \"FR\" PVC insulated & unsheathed copper wire for ECC, to light points with 2 no. 2 way Modular type switch (Make:Legrand: Myrius White/Brand approved by EIC) fixed on Modular GI switch board complete with 3 no. suitable size “Ph, N & E” copper bar with top cover plate making earthing attachment fixed on wall incl. mending good damages to original finish.[PVC Rigid Conduit only for horizontal run & above false ceiling and vertical run concealed]Average run 10 mtr |
| 27 | Cutting Channel of size (40 mm x 40 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge 19 mm, 3 mm thick Polythene pipe by means of anchoring chemical (Hilti/Sika) and GI \"U\" hooks of 8 SWG incl. supplying and drawing 18 SWG GI wire as Fish wire andmending good damages to original finish by using own tools and tackles [for vertical run embedded in wall ] 19 mm dia 3 mm thick polythene pipe without earth continuity wire |
| 28 | Supplying and fixing PVC Rigid Conduit \"FR\" [Precision Make] on wall, ceiling with saddles and other accessories as required and mending good damages to building works20 mm Size |
| 29 | 25 mm Size |
| 30 | Supplying and Drawing 1.1 KV single core stranded \"FR\" PVC insulated & unsheathed single core stranded copper wire ((Polycab/Havells/KEI or Brand approved by EIC)) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required3 x 22/0.3 (1.5 sqmm) |
| 31 | 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) as ECC. |
| 32 | 2 x 56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm) as ECC. |
| 33 | 2x84/0.3 (6 sqmm) + 1x56/0.3 (4 sqmm) as ECC |
| 34 | 3x80/0.4 (10 sqmm) + 2x84/0.3 (6 sqmm) as ECC |
| 35 | Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. 1.5 sqmm |
| 36 | 2.5sqmm. |
| 37 | 4.0sqmm. |
| 38 | 6 Sq mm |
| 39 | 10 Sq mm |
| 40 | Plug,Sockets,Inspection Box etc.Supplying & Fixing GI Modular Switch Board of the following sizes complete with top cover plate flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building work |
| 41 | a) 2 Module |
| 42 | b) 4 Module |
| 43 | Supply & Fixing 240 V 16 AModular type switch (Make:Legrand: Myrius White/As per Direction of EIC) on GI Modular type switch board having top cover plate and making necessary connections as required |
| 44 | Supply & Fixing 240 V, 4 nos. 6 A, 3 pin Modular type plug socket with 4 nos. 6A Modular type switch (Make:Legrand: Myrius White/As per Direction of EIC), 16A Modular switch type MCB (C-Curve) and Indicator without plug top on12 Module GI Modular type switch boardcomplete with three no. suitable size Copper bar with holes (for Ph,N & E) fixed on bakelite/Hard Rubber insulator over the MS welded chairs incl.12 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. |
| 45 | Supply & Fixing 240 V, Two nos 6 A, 3 pin Modular type plug socket (Make:Legrand: Myrius White/As per Direction of EIC) with Two Nos 6A Modular type switch, without plug top on 4 Module GI Modular type switch board with 3 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. |
| 46 | S&F 240 V, 16 A, 3 pin Modular type plug socket (Make:Legrand: Myrius White/As per Direction of EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plateflushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. |
| 47 | Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Make:Legrand: Myrius White/As per Direction of EIC), without plug top and switch, on existing GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc |
| 48 | Supply & Fixing 240V,25A, 3 pin Modular type plug top with indicator (Brand approved by EIC) & necy.Connections. |
| 49 | Supplying & Fixing folowing size sheet metal inspection box (16 SWG) of the following sizes flushed in wall by housing the same after cutting brick wall incl. making earthing attachment, painting and mending good damages to building works |
| 50 | 100 mm x 100 mm x 65 mm |
| 51 | 175 mm x 100 mm x 65 mm |
| 52 | Supply & Fixing bakelite / perspex top cover on existing following size switch boardby Brass screws after making housing for switch by cutting bakelite / perspex cover and making necessary connections as require |
| 53 | 100 mm x 100 mm x 65 mm |
| 54 | 175 mm x 100 mm x 65 mm |
| 55 | Light,Fan,Fittings etcSupply & Delivery of 240Vsurface mounted round LED downlight having following wattage, in white powder coated pressure die cast aluminium housing with glare free uniform illumination, with CCT (5700K-6500K) having minimum luminous efficiency of 100 Lm/ Watt or better & 50,000 LED burning hours or more. [Make-Crompton / Philips or manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] |
| 56 | 18 W[Make-Crompton-Pearl NIOS-LCDSPLN-R-18-CDL/ Philips or manufacturer with own NABL accredited lab with valid test certificate] |
| 57 | 25W [Make-Crompton-Pearl NIOS- LCDSPLN-R-24-CDL/ Philips or manufacturer with own NABL accredited lab with valid test certificate] |
| 58 | Supply & Delivery of 240Vrecess mounted round LED downlight having following wattage, in white powder coated pressure die cast aluminium housing with glare free uniform illumination, suitable for 2\" x 2\" grid ceiling/ fixed false ceiling with CCT (5700K-6500K) having minimum luminous efficiency of 100 Lm/ Watt or better & 50,000 LED burning hours or more. [Make- Crompton/Philips or manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] |
| 59 | 12W (Make- Crompton-PEARL ULTIMA-LSCRM-12W-CDL/Philips or manufacturer with own NABL accredited lab with valid test certificate] |
| 60 | 18W [Make- Crompton-PEARL ULTIMA-LSCRM-18W-CDL/Philips or manufacturer with own NABL accredited lab with valid test certificate] |
| 61 | S & D round wall lightfittings with intregated 10 W Cool White LED for bathroom miroor [Phillips:Meraki Model No: 582108/ equivalent make as per direction of EIC] |
| 62 | S & DSingle Arm Wall Lightincluding S/F1Nos. 12WE27 LED Lamps. [Phillips: Muziris - 31425 /Equivalent make as per direction of EIC] |
| 63 | Fixing only bulk head/Surface LED/Recess mounted LEDceiling fitting on wall /ceiling/False Ceiling by screws ,safety wires etc. |
| 64 | S & F of 240V,50Hz 9W LED lamps [Phillips/ Havells/ Crompton] |
| 65 | Supply and fixing of 50 MTRLED Rope/Strip light (Colour as per direction of EIC) with 120 LED/MTR [Make- Crompton- 65W Galaxy Rope Light/Philips make Marathon rope light /Equivalent as per direction of EIC] |
| 66 | S&D single 4ft LED commercial tube light fitting made of CRCA materilas(Philips-Cat.No. TMC502 1xLED 22W/Equivalent approved brand as per direction of EIC) including LED tube T8(Philips Cat. No 1200mm 18W865 T8 I-2100lm/Equivalent approved brand as per direction of EIC) suitable for 230 V 50HZ AC supply. |
| 67 | S&D double4ft LED commercial tube light fitting made of CRCA materilas(Philips-Cat.No. TMC502 2xLED 22W/Equivalent approved brand as direction of EIC) including LED tube T8(Philips Cat. No 1200mm 18W865 T8 I-2100lm/Equivalent approved brand as per direction of EIC) suitable for 230 V 50HZ AC supply. |
| 68 | Fixing only single/twin florescent light fitting complete with all accessories Directly on wall/ceiling with HW block and suitablesize MS fastener, Ceiling plate, nipples etc. as required |
| 69 | S & Fixing 240V AC/DC superior type Ding-Dong call bell (Anchor) on HW board incl. S&F HW board. |
| 70 | Supply & Delivery of 230V, 1-Ph, 1200 mm sweep BLDC ceiling fan having Wattage ≤ 35 Watt, R.PM ≤ 350, Air Delivery ≥ 220 C.M.M incl. all accessories (Without Remote). (Make- Orient-Hector 500 Pearl White/Topaz Gold/Crompton-Energion Groove,Colour-Onyx or Satin Sand/ Usha-Techno Air,Colour -White) [BEE 5 star rated] |
| 71 | Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire. |
| 72 | Supply And Delivery of14 SWG MS Down Rod 18\"\" |
| 73 | Supply & Fixing 240V, (2 Module) Modular Socket type fan regulator (0 - 4 Steps) on existing Modular GI switch board with top cover plate including making necessary connections etc. (Make:Legrand: Myrius White/As per Direction of EIC) |
| 74 | S & F 250 V 50 HZ, 80 watt,18\" (450 mm) high flo ( air delivery-- 4500 CFM, RPM-- 1400) non-oscillating type metal body Heavy Duty Wall Bracket fan with inbuilt regulator, double ball bearing, intergally cast LM6 impeller(Make -EPC-Tempest/Orient-Tornado Wall II/Crompton-WM SSTROM 2/Equivalent as per direction of EIC) |
| 75 | Fixing only cabin fan on wall/ceiling by S&F rag bolts, nuts & washers (6 mm dia x 62 mm long) or as reqd. incl. S&F 24/0.20 PVC insulated flexible copper wire 0.5 mt. length |
| 76 | Supply & delivery of 220 V 50 Hz Exhaust fan with folowing specifications: Sweep: 230mm; Power Input:40W, Speed: 380 rpm; Air Delivery:1120 CFM complete with all accessories.(Make -EPC/Orient/Usha) 23 cm (9\") as per direction of EIC |
| 77 | Supply & delivery of 220 V 50 Hz Exhaust fan with folowing specifications: Sweep: 300 mm (12\"), 4 Blade, RPM ≤ 1420 , Wattage ≤ 82 Watt, Sound level ≤ 56 dB, Air Displacement (In CFM) ≥ 1120(Make -EPC/Orient/Usha) as per direction of EIC |
| 78 | Fixing only exhaust fan after making hole in wall and making gooddamages and smooth cement finish etc. as practicable aspossible and providing necy. length of PVC insulated wire and making connection for exhaust of following diameter: 23 cm (9\") |
| 79 | 30 cm (12\") |
| 80 | Supply & Fixing louver shutter on wall with necy. bolts & nuts (6 mm dia x 62 mm long).For Al: 23 cm Exhaust fan (9\") |
| 81 | Supply & Fixing louver shutter on wall with necy. bolts & nuts (6 mm dia x 62 mm long).For Al:30 cm Exhaust fan (12\") |
| 82 | SITC of 25 Ltr Water Geyser of following specification and accessories: Closed water heater Class 1, 240V,50 Hz AC, BEE 4/% Star rating, Porcelain element with tubular technology 800 element copper and outer container should be of mild steel and water proof powder coating to protect from rust and corrosion with the facility of Red Indicator of \"Heating Neon light Indicator forworking of water heater and with polyurethane foam with safety of thrmostat,Thermal cut out, Multifunction valve and sacrificial anode and must be protected aginst galvanic corosion using Magnesium Sacrificial Anode manufactured in modern automated factory using European Technology [ Make: Crompton Arno Supremus, 2000W/Jaquar-ELENA MANUAL VERTICAL JAQUAR 25 Ltr/Raycold] as per direction of EIC |
| 83 | Compound Light & Glow LED Sign BoardSupply of2 Core 6 Sqmm XLPEInsulated & Sheathed Armoured stranded Aluminium Conductor cables for Working Voltage up to 1100 Volts [Make Polycab / KEI/ Havells or as approved by E.I.C] |
| 84 | Laying of cable upto 2 core 25 sqmm on wall/surface incl. S & FMS saddles with earthing attachment in 10 SWG GI (Hot Dip)Wire, making holes etc. as necy. mending good damages andpainting |
| 85 | Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on thetop of the cable with 8 (eight) Nos. bricks per metre, includingfilling the space between the brick & cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed |
| 86 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : 2 core 6 sq. mm. |
| 87 | Finishing the end of following XLPE/PVC armoured cables bycrimping method incl. supplying and fixing solderless socket(Dowels make), tapes, anticorrosive paste & jointing materials :2 core 6 sq. mm. |
| 88 | Supply & Delivery of 240V,70W LED street lights with optic lens and polycarbonate diffuser having following wattage, in white powder coated pressure die cast aluminium housing with IP 66 protection & incl. 10 kV SPD, with glare free uniform illumination with CCT (5700K-6500K) having minimum luminous efficiency of 110 Lm/ Watt or better & 50,000 LED burning hours or more. [Make-Crompton Model No- CRP-409-70-57-SL-GL-NSGwith 5 Yrs Warranty/Phillips or manufacturer with own NABL accredited lab with valid test certificate] [LED lamps & accessories shall have BEE certification] |
| 89 | Fixing onlyLED light Fitting with suitable tie clamps and MS plate for mounting on Pole/Tower or similar structure. |
| 90 | Fixing only outdoor / street light type fluorescent light fitting or MV light fitting complete with all accessories to be fixed /projected from the wall of the building incl. making holes/providing clamping arrangement & necy. GI reducer as required. S&F 40 mm GI pipe (ISI-Medium) quality 1.5 mts. average length having suitable bend S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages to wall incl. painting etc. |
| 91 | Supply & fixing Sintex loop box of size 250 x 200 x 105 (Syntex: GSJB-2520) with half round clamp on pole and supply & fixing a best quality 32A, 4-polebarrier terminal and 6A SP MCB inside it including all accessories. |
| 92 | S&F of 240V,50Hz Outdoor Decorative Post top 360° indirect LED light fitting having IP65 protection with inbuilt LEDs [Make-Crompton -Maple LPTO-40-CDL-M/Equivalent model of other approved brand as per direction of EIC] |
| 93 | SITC of Glowsign Board(Router cutting) with liquid Acrylic letters with adhesive on ACP Board of 3 mm Thick[Make-Aludecor/Alstone] of suitable size to accommodate all the matters/contains as approved by the authority to be made with 25x25x4 mm MS angle Iron,18 SWG square/Round Hollow bar,Base plate(10mm Thickness) requires for fixing the necessary Nuts,Bolts,Washers supporting angle Iron,Clamp etc.and ACP Sheet on front sides & edges only & back side to be covered by GI Sheet (with proper ventilation arrangement), All side to be moulded uniformly,Side fabricated by Aluminium L- channel, upon which elevated or box type letter made from imported liquid acrylic will befixed. The thickness of Acrylic will be 5 mm (for small letters), 8 mmm (for big letters) and 10 mm (For very big letters). The Back side of the letters is covered by 3mm thick ACP [Make-Aludecor/Alstone]. The inside of te letter of the letter Supplyingand Fixing of Best Quality LED Lighting arrangement of the water proof 10 nos. LED light fittings of 20 W (100 Lm/w). The letters are sealed by exterior grade Silicon. The back side of the Board Covered by 22 SWG GI sheet with nuts & Bolts(Signage 24 Sq ft/8ft x 3 ft) |
| 94 | Intensity: Same & Smooth uniform throughout without any dark patch |
| 95 | Visibility: Clear Upto 250 Meters for normal |
| 96 | The complete sign board would be fixed on roof of the building with providing necessary CC muffing, 1 no CI water proof 200 x 150 x 100 mm loop box,50 x 50x 6 mm Msfor supporting the board of required length by type doors in back side to have the inside access incl. mending goods the damages to original finish.nuts,bolts,washers etc. After drilling holes on the frame front facia. GSB would have 2 nos. hinge |
| 97 | Painting of any Steel/Iron surface of the above Glow sign board with no.of coats of paints as given below with ready mixed paint/ primer of approved make and brand incl. preparation of surface by sand paper/emery paper,cleaning etc. for receiving fresh coat of paint. |
| 98 | 1st coat of aluminium paint over one coat of RO priming |
| 99 | 2nd coat of aluminium paint over one coat of RO priming |
| 100 | SITC of AC MachinesSupply & delivery of Hi- Wall lnverter type Split Air havingfollowing specification- Cooling capacity (Kcal/Hr)-6000 Kcal/ Hr (2 TR)ISEER rating- 3 Star as per BEE/ BISIS compliance-IS 1391Refrigerant-R32/ R410ACompressor- Rotary/ ScrollEvaporator & Condenser Coil- CopperOperating ambient temperature- 50 degree centigradePower Supply- 240V, 50 Hz (Tolerance as per applicable standard)(Make-O-General -ASGG24CPAB-B (R32) / Hitachi-Model No. SPLIT AC 2.0 TR CLASS HITACHI IZEN 3400SXL 2.0 TR - RAS.G324PCCISS/Mitshubishi Electric -Inddor ModelNo.-MSY-RJS22VF & Outdoor Model No. MUY-RJS22VF) |
| 101 | S&D of BEE 2/3 Star rated,230 V, 50 Hz 1.5 Ton inverter split type air conditioner (Non Inverter R32/R410A) having colling capacity 5120 Watt (1.5 Ton) Maximum power Consumption 2650 Watt (CBU +1 IDU + 1ODU)Refrigerant-R32/ R410ACompressor- Rotary/ ScrollEvaporator & Condenser Coil- CopperOperating ambient temperature- 50 degree centigradePower Supply- 240V, 50 Hz (Tolerance as per applicable standard)(Make- O-General model no. ASGA18BUTA-B(R32)/Hitachi-Model No. SPLIT AC1.5TR CLASS HITACHI IZEN 3400SXLINVERTER-R32-RAS.G318PCCISS/Mitshubishi Electric -Inddor ModelNo.-MSY-RJX18VF & Outdoor Model No. MUY-RJX18VF) |
| 102 | Installation,Testing & Commissioning of 1/1.5/2/2.5 Ton AC macine complete with outdoor condensing unit on suitable size Iron angle/powder coated bracket & indoor cooling unit on wall with suitable bracket. Rate is inclusive of cutting wall, making holes and mending goodthe damages. |
| 103 | Supply and drawing 5/8\"\" & 1/4\"\" copper refrigerentpipes with 9mm thick nitrile rubber insulation along with all accessories on the surface of wall |
| 104 | Supply and drawing copper communication & controlling cable of following size 4 core 2.5 Sq mm PVC insulated copper cable(Make: Polycab/Finolex/Havells/KEI) |
| 105 | Supply and fixing 20 mm Hard PVC pipe(heavy type) for water drainage |
| 106 | Supply & Fixing 240 V, 50 Hz, 1ph OLP 3+ starter with digital display for Split AC machine (1.5/2 Ton) having rated current 21 A Voltage range 160V-270V, IP 20, and provision to display voltage , current, and any fault indication (Make- Electron) incl. necessary connection (incl. supply material like wire, lugs etc if required) and commissioning the same. |
| 107 | SITC of InverterSupply and Installation of 1050 VA Inverter (VDC - 24 Volt) sutable for voltage level(inverter mode):100V-300V UPS Mode:180V-260V ,Mains Mode: same as Input/UPS Mode:210+- 10%,50Hz+-0.1 ,Automatic from Mains to UPS and from UPS to mains with transfer time <16 ms[Make - Microtek Model: LUXE SW 1900(1650VA-24V)/Equivlent Luminious/APC asper direction of EIC] |
| 108 | Supply and delivery of 12 V,150 Ah Tall Tubular long life and less maintenance battery for support above mentioned Inverter[Make:Luminous/Exide/Microtek] |
| 109 | EarthingEarthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire, with an average depth of 3.65 Mts. below the ground level (For soft Soil: ISI-Medium GI pipe) |
| 110 | Excavation of soil for installation of Earth Electrode and filling & ramming. (Soft Soil) |
| 111 | Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe |
| 112 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required |
| 113 | Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages a) Solid GI wire---No. 6 SWG |
| 114 | Connecting the equipments body to earth busbar including S&F 20 mm x 3 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. |
| 115 | ADD GST @ 18.00% ON SUM OFAMOUNT Sl-01 to SL-82 i.e 18% on Rs. 1084672.00 |
| 116 | ADD Cess @ 1.00% ON SUM OFAMOUNT Sl-01 to SL 83 i.e @1% on Rs.1279913.00 |