Name of Work: SITC of Gas based Fire suppression system in all electrical panels at various locations, PGIMER, Chandigarh
Sl. No.
Item Description
1
Supply Installation & commisioning of 1 Kgcapacity FK-5-1-12 with UL approved 1.6 ltr water capacity non ferrous Seamless Cylinder(PESO & UL Approved) with a test pressure of 53 bar and maximum working pressure of 35bar, DLP Assembly with safety relief disc and isolation valve & UL Approved Pressure Gauge , push in connector for tube, UL approved 1kg FK-5-1-12 Gasref NFPA 2001 FK-5-1-12 , mounting bracket, End of Line adopter withweight measuring unit to indicate loss in weight in MCU & low pressure switch (UL Approved) to indicate loss in presure in MCU, both to be used for monitoring system activation or loss of agent.
2
Supply Installation & commisioning of 2 Kgcapacity FK-5-1-12 with UL approved 2.7 ltr water capacity non ferrous Seamless Cylinder(PESO & UL Approved) with a test pressure of 53 bar and maximum working pressure of 35bar, DLP Assembly with safety relief disc and isolation valve & UL Approved Pressure Gauge , push in connector for tube, UL approved 2kg FK-5-1-12 Gasref NFPA 2001 FK-5-1-12 , mounting bracket, End of Line adopter withweight measuring unit to indicate loss in weight in MCU & low pressure switch (UL Approved) to indicate loss in presure in MCU, both to be used for monitoring system activation or loss of agent.
3
Supply Installation & commisioning of 4 Kgcapacity FK-5-1-12 with UL approved 4.5 ltr water capacity non ferrous Seamless Cylinder(PESO & UL Approved) with a test pressure of 53 bar and maximum working pressure of 35bar, DLP Assembly with safety relief disc and isolation valve & UL Approved Pressure Gauge , push in connector for tube, UL approved 4kg FK-5-1-12 Gasref NFPA 2001 FK-5-1-12 , mounting bracket, End of Line adopter withweight measuring unit to indicate loss in weight in MCU & low pressure (UL Approved) switch to indicate loss in presure in MCU, both to be used for monitoring system activation or loss of agent.
4
Linear pneumatic heat Detection Tube :- UL Aproved Heat detection Tube, 4mm ID, 6mm OD, detection temprature 160 Deg celcius, mutlilayer, Water Absorbtion ≤ 1.5% @ 20ºC and 50% RH as tested per ISO62 with fittings and supports.
5
Master Control Unit for controlling each system along consisting Battery back for 24 hours at standby mode with atleast 1000 eventlog, complete with pressure switches, buzzers and electronic hooters, including all necessary accessories + electrical wiring to make each entire system functional.