| 1 | Supply only the following 1.1 KVgrade PVC insulated Al./A Cable as below:[Finolex/Havells/RR/PolyCab].i). 4 Core 150 Sq mm. [Ext. DG Room to New DG Room double run] |
| 2 | ii). 4 Core 35 Sq mm.[3Nos High Mast Feeder Box from nearset source] |
| 3 | iii). 4 Core 25 Sq mm.[4 Nos Timer Feeder Box for outdoor light] |
| 4 | iv). 4 Core 10 Sq mm. [Running Cable for all type pole light] |
| 5 | v). 4 Core 6 Sq mm. [Running Cable for Bollard & Post top] |
| 6 | Laying of cableon wall/surface incl. S & F MS saddles with earthing attachment in H.D Wire, making holes etc. as necy., mending good damages and painting. [F1:2b , 2c & 2e]i). above 3½ core 90 sqmm and upto 3½ core 150 sqmm in 2 x 10 SWG GI (Hot Dip) Wire. |
| 7 | ii). 3/3½ core 35 sqmm to 50 sqmm in 2 x 10 SWG GI (Hot Dip) Wire. |
| 8 | iii). upto 3/4 core 25 sqmm in 1 x 10 SWG GI (Hot Dip) Wire. |
| 9 | Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed. [F2:1a] |
| 10 | Laying of two cables above 35 sqmm & upto 185 sqmm in an underground trench in single tier formation (horizontal), the trench size : 680 mm x 760 mm average depth, with brick protection on the top of each cable 8 (eight) Nos. bricks per Mtr. & 4 (four) Nos. bricks per Mtr. as separator between the bricks & cables and also trench to be filled up with shifted soil, levelling up and restoring surface duly rammed[F2:2b] |
| 11 | Laying of cable as below, after cutting floor/pavement/wall/ and making holes incl., embedding the cable at an average depth as below and mending good the damages to original finish incl. removing the rubbish.i). From 2.5 sqmm to 35 sqmm at an average depth of 75 mm infloor/pavement/wall etc.[F3:5i] |
| 12 | ii). Above 95 sqmm at an average depth of 100 mm in floor /pavement/ wall etc. [F3:5iii] |
| 13 | Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support.[D14:34a(ii)]i). 300x50x1.25mm (18SWG) with 25x25x3mm angle iron support. |
| 14 | Supply & Fixing of perforated GI cable tray bend with perforation not more than 17.5% suspended from ceiling with two nos. suspenders & 25x25x3mm angle iron for supporting the cross member incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support.i). 300x50x1.25mm (18SWG) . [D15:b] |
| 15 | Laying of cable as below, on existing Cable Tray and binding with suitable size GI wire.[ For minning Building]i). Up to 50 sqmm.[F3:6i] |
| 16 | Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required.i) 40mm dia.[Outdoor Pole drop in & Drop out][F6:11c] |
| 17 | ii) 80mm dia. [Road Crossing minimum for 3nos cable I & O][F6:11f] |
| 18 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below :i). 4 Core 150 Sq mm. [F4:7c] |
| 19 | ii). 4 Core 35 Sq mm.[F4:7c] |
| 20 | iii). 4 Core 25 Sq mm.[F4:7c] |
| 21 | iv). 4 Core 10 Sq mm.[F4:7c] |
| 22 | v). 4 Core 6 Sq mm.[F4:7c] |
| 23 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials :i). 4 Core 150 Sq mm.[F5:8b(xx)] |
| 24 | ii). 4 Core 35 Sq mm. [F5:8b(xv)] |
| 25 | iii). 4 Core 25 Sq mm.[F5:8b(xiii)] |
| 26 | iv). 4 Core 10 Sq mm. [F5:8b(xi)] |
| 27 | v). 4 Core 6 Sq mm. [F5:8b(x)] |
| 28 | HIGH MAST INSTALLATION : |
| 29 | Supply & transpotation upto site with fixing of polygonal shape 16.00 mtr High mast pole (BAJAJ/TRANSRAIL/VALMONT/As per choice of EIC ) with its alliedincl. all accessories. Mast shaft shall be in two section, made from High Tensile Steel of grade BSEN10025,S355JO hot dip galvanised and suitable for wind speed 39mtr/Sec to 50mtr/Secas per IS 875. It should also included acc. for high mast including head frame structure at the top & socketting box etc., two continious stainless steel wire-rope 6 mm dia ( Grade AISI 316), Trailing cable (5 core x 2.5 to 4.0 sq.mm EPR PCP Round Copper) for mobile head, Compensating Disc, L-Stopper (3 Nos.), Manual operating handle, Mounting plates, Lightening Arrestor and earthling spikes (MS GI),double drum winch galvanised lantern carriage arrangement suitable for 2x6 nos. luminaries installation symmetrically and its control gear box, attached motor ,top Junction box, including foundation acc. the mast shall have an intigral power tools installed inside the base compartment for its operation. Luminaries wiring matrials including in the mast supply price.Technical Specification:Bottom dia 450 mm,top-150 mm , 4/3mm thickness (bottom and top both) section - 2nos, length 8250 mm, Baseplate 540 mm dia,baseplate thickness- 25 mm. hole dia- 26 mm, PCD-490 mm ,foundation bolt size 30 mm dia Bolt length 850 mm, No of hole 8 nos. Foundation bolt 8 nos. Wire rope 6mm SS 304 grade,luminary capacity 39m/Sec-50m/sec as 12 numbers. |
| 30 | Construction work of suitable shallow foundation with 1:2:4 or M20 grade concrete for the high mast pole / tower considering the safe soil bearing capacity at site as 10T-15T/sqm. At 2X2 meter with 2meter deep total RCC civil work incl. total excavation & labour charges to last finishing with all materials ,Pastaring works of2mm thickness andfoundation above structure of High mast pole after cleaning etc. for receiving fresh coat of paint & double coat primering work of basement structure.This reinforcement shall conform to IS:1786 latest edition. The foundation shall extend above sorrounding ground/driveway level for 450-500 mm and have slant 60-68mmdia. PVC sleeve cast insitu foundation for cable entry as per the drawing......Agency has to prepare Layout Drawing by his/her own cost & the same has to be Approved by EIC before the original work execution. |
| 31 | i.)Total Erection work to setup upto the 16.00meter high mast pole/tower on or above the above mentioned RCC basement with the help of modern engineering practices as specific tools & tackles, machineries, man power and Hydra/JCB/or Excavator with proper finishing the above work without any damages in original properties.as per direction of EIC. ii.)wiring of luminaires with all wiring materials like PVC insulated PVC sheathed flexible cable of suitable copper conductor and connection trailing cable. |
| 32 | S.I.T.C of Outdoor type Feeder Pillar Box of IP-54 protected as dust,vermin and moisture proof powder coated simens grey in colour over the double coat of primer,having waterproofing top canopy of 5mm thickness CRCA sheet, sides having Louvers for ventilation arrangement, feeder pillar box should be compartmentalized of suitable size made of 14 SWG thick M.S CRCA sheet body complete with the following accessories as required...............#[Make:All Item are LEGRAND/EIC Approved]#i) Hinged door open-able on front & rear side with heavy duty locking system.- 02 nos.ii) Base frame with detachable cover on all sides made out of 14 SWG steel sheet.iii) Legs of suitable length make out of 40mm x 40mm x 6mm angle iron i/c grouting the legs in 1:2:4(1 Cement 2 coarse sand 4 stone/pakur varity aggregate of 40 mm nominal size) CC foundation & total excavation work & plastering/punning etc. all finishing work as required regarding basement work .iv)Knock out holes at bottom for cable entry as per requirement.v) Earthing stud- 02 nosvi) 32 Amps main switch SFU unit with din type fuse -1 No.vii)63 Amps electrolyte CU busbar(R,Y,B,N) max 1.6 feet-1set. |
| 33 | viii)40A FP Air Contractor for lighting ckt operation-1no.ix)10Amps Contactor for forward and reversing operation-1set.x)250V,50Hz,16 Amp Digital time switches -1 noxi) 10 Amp SPMCB of 10 kA breaking capacity -4Nos.xii) 220 Volt AC LED Neon Indicator lamp(R,Y,B) -3 Nos.xiii) Auto /Manual timer by-pass switch(Toggle) -1 No.xiv) Circuit connector(R,Y,B,N)-2 Set.xv) Detachable gland plate-1 Set.xvi) Start/Stop push button for locally switching ON/OFF the luminaries - 1set.xvii)Extra Push button- 2Nos(For motor forw/reverse)xviii) 415 Volt Single phase preventer -1No.xix) Termination incoming/outgoing cables with suitable sizes of ferrules & compression gland.xx)E.I Danger Board of 15 cm x 10 cm (6\"x4\")-1Set. |
| 34 | Supply & Fixing of 250W,240V Warm White LED flood light made up of pressure die cast aluminum housing with toughened glass and high power LEDs and secondary lenses with IP66 protection. System efficacy ≥ 120LPW,10kV SPD included.fixture on High Mast Pole top fabricated on GI Structure .a) Electric load should be 250 W (± 5% for each set).b)Light temparature range 3000-4500k.c) Light output (Lumen) should be minimum 110 lm/watt.d) The light product having the third party test report of LM-79,LM-80 & IP-66.e) 3 years warranty period.[Make:Philips/Bajaj GLEAM-G F 300L WH NB-A5 PC SD /Wipro/ Eqv. EIC Approved ] |
| 35 | Supply and fixing lightning arrestor on High Mast top incl. Supply and fixing of LED aviation obstruction light (RED) Luminairies [Bajaj-110731] Integral LED aviation light comprising of aluminium housing with polycarbonate enclosure, 302 nos.LED are provided should be fixed at the top of the existing High Mast tower. |
| 36 | BEAUTIFICATION WORK |
| 37 | Supply & Delivery of 10W LED bollard light fittings of IP65 / IK 10 protected allied with all neccy. items.(with minimum 3years warranty)[CROMPTON- Liara LBLSN-10 WW Inverted Pyramid 360° Illumination / Equvalent Philips/Eqv. EIC Approved] |
| 38 | Fixing of LED bollard light fittings by providing necessary suitable size of base plate &3 or 4Nos.\"J\" bolts ,nuts etc. arrangement with erection by excavation & underground cement concreted structure (6:3:1)Circular/Squareneatly cemented finish (3mm thick) including holes & polythene piping for cable entry & exit arrangement & necessary connection with suitable size of copper wire by Furrel socketing(4 Socket) inside the Fixture with neccy. heat shrink joint.[Sample drawing should be approved from the EIC] |
| 39 | Supply & Fixing 30W,240V decorative Post Top LED gate light fitting for 360⁰ indirect lightning with IP65 protection on S/F of 2.5 inch dia,suitable length G.I(Hot-Dip) pipe with allied nuts, bolts, washer etc. on or above the top-basement of the gate pillar incl. neccy connection, necy. enamel painting as required as per site condition,CCT between 4500K - 6500K as per EIC direction. manufacturer\"s warrenty should not be less than three years.[Make:Philips/Crompton/Bajaj/Eqv. EIC approved] |
| 40 | Supply & Fixing of 240V Outer wall decoration light fittings of IP65 protected Extruded & die cast aluminium body ,mirror finish pure aluminium reflector & clear toughened glass cover mounting on surface of the outer wall ,graphite grey/anthracite grey/jet black in colour,CRI>80,Color temp. 2700K/4000K with 4kV surge protective device,beam angle 15°/25°/40° fixing by nuts,screw,washer,PVC CU connector etc. as per direction of EIC.K-LITE WALL CYLIN MINI-7898 2X6Watt LED/Philips/ Eqv. EIC Approved. |
| 41 | Supply & Fixing of 24w-50w LED PAR light fittings for highlighting the monument with neccesary basement of 8inch clear from the ground with color control of RGB, RGBW and tunable white with DMX512/RDM control options.[Make:Philips/Bajaj/Eqv. EIC Approved] |
| 42 | Supply and fixing of LED strip light with driver,connector and all other accessories. (Make-Philips BGC301 1100LM 3000K L5000/ Crompton/Bajaj) |
| 43 | Supply & laying of 3 core 4sq mm unarmoured copper cable for wall decoration light,Par light fitting & LED Chain wity necessary copper socketing at both end..(Havells/KEI/RR Kable) |
| 44 | OUTDOOR ILLUMINATION |
| 45 | Supply delivery of 9 Mtr Steel Tubular Pole ( PWD appvd ) as per specificationType 410- as overall length 9mtr& having diamention as per details given bellow:Out side dia & thickness of the Bottom section(139.7x 4.50) mm; Middle ( 114.3x 3.65) mm,Top Section(88.9x 3.25 ) mmwith fixing the suitable size base plate , necessary drill hole ete as per direction of EIC. |
| 46 | Supply & Erection of 80mm dia 2Mtr long GI(TATA/JINDAL) Pole with suitable size sole plate on the roof top of the building with necy.Drilling tapping and GI nut,bolt,washers and all fixing item and connecting wire entry hole incl making C.C muffing 2ft x2ftx 2.5ft in size by cement morter (6:3:1) incl neat cement finish(Without loopbox) and painting with anti corrosive paint (1st coat of red oxide & double coat of Al paint), Cable entry hole,earthing hole,nuts bolts etc.as per direction of EIC... |
| 47 | Supply & Fixing pole arm header assembly having 80-100mm dia, sleeve of 300mm long with pole cap duly welded with 1.5/2 mtr long (as per site requirement)of 40/42 mm dia GI pipe arm bracket detachable type at an angle 110deg. With the pole incl anti movement arranagement with necy. reducer, jam-nuts, bolts,washer,juts etc. as required with necy painting with anti-corossive paint(1st coat of red-oxide & double coat of aluminium synthetic paint) as per direction of E.I.C.i). Single Arm. |
| 48 | ii). Double Arm. |
| 49 | Supply & Fixing of LED outdoor street light fitting arm header, complete with all access. to beprojected from the wall of the building incl. making drilled holes & providing clamping arrangement & necy.GI reducer as required.with Supply & Fixing of 40 mm GI pipe (Make :TATA-Medium) 1.5 mts. average length having suitable bend & necy nuts/bolts etc to provide necy.arrangement to fix the whole clamp arrangement & S&F necy. length of 3x1.5 sqmm(Ph,N,E) PVC insulated single core multi stranded annealed copper wire and making connections as required and mending good damages to wall incl. necy. enamel oil painting etc as required...[C3:18] |
| 50 | Erection of Single Steel tubular pole of length as given below with/without sole plate & Cap etc. in CC foundation (Proportion and dimension indicated below), having 600x600x150 mm thick CC (4:2:1) base block below sole plate/pole with hard jhama metal including CC (6:3:1) muffing 0.30 mts. dia and 0.30 mts. above ground level including 3 mm thick neat cemented finish and GI earth bolt after making drilled holes etc. on pole & carriage of pole upto 1.6 Km from Store to work-site including filling up the excavated earth pit with shifted soil and ramming properly.i). Upto 9.0 mtr. Size 0.6x0.6x1.70 mts.[H1:1] |
| 51 | Extra on items 1 above, for providing CC (6:3:1) base block (around the pole) dimension 0.60x0.60x0.76 mt. above ground level, neatly cemented finish (3 mm thick), at the base pole (in lieu of CC muffing) incl. drilled hole in pole suitable for alkathene/polythene pipe entry, for street light wiring, without Loop Box.[H1:3b(i)] |
| 52 | Supply & Fixing of 240V Warm white LED street lightmade up of pressure die cast aluminium housing with high power LED as lighting source with toughened glass top cover. TOP Opening seperate driver compartment with IP66 protection and impact resistance of IK07 with 10KV Built-in Surge Protection Device & temparature range should be 4500K-5700K, System efficacy 140 lm/W .and manufacturer\"s warrenty should not be less than 3 years.i). 240V,250W(Philips urban edge + BRP505 LED322 CW R3C PSU S1/Eqv Bajaj or Klite Waco Make). |
| 53 | ii). 240V,120W(Philips urban edge + BRP503 LED168 CW R3C PSU S1/Eqv Bajaj or Klite Waco Make). |
| 54 | iii). 240V,70W(Philips urban edge + BRP501 LED098 CW R3C PSU S1/Eqv Bajaj or Klite Waco Make). |
| 55 | Supply and laying of 3x 1.5sqmm FR single core copper wire for connection from loopbox to fittings through 13 mm dia polythene pipe. (Make: Gloster / RR / Polycab) |
| 56 | Supplying & Fixing Stainless Steel(SS) waterproof type looping cable box size 250x250x100 mm deep having 4 mm thick with rain protection canopy attached body & comprising of 250 V,3/6/10A SP\"MCB(C/D curve),(quantity & rating as per site recuirement) on din channel (\"C\"-curve,legrand make),with 4way copper terminal stud and having lined with rubber gasketed top cover should be fixed on wall/Pole by pole clamps, screws, nuts, bolts, washers etc, with necy. \"cu\" bar (Ph,N,E) with \"cu\" socketting, rubber gasketted entry and exit as mending the good damages to the original finish as required for new pole and housing the same in pole muffing incl. addition and alteration to the existing CC muffing (6:3:1) after dismantling the damaged looping cable box etc. for existing pole where incl. necy. painting as required as per direction of EIC....[ 13 nos for posttop+3nos for sign board+4nos for ext pole+30nos. for mini pole+10 nos as other JB for bollard connection if required] |
| 57 | SITC of Outdoor type LT-Feeder Pillar Box of IP-66 protected, 415V, 3-Phase, 4 wire, 50Hz as suitable size, made with 3mm thick CRCA steel sheet(TATA/ JINDAL) body meterial & 5mm thick rainproof canopy fabricated on 40mmX40mmX6mm angle iron frame, cubical compart mentalized floor mounted, outdoor type dust and vermin proof powder coated,having front side & rear side openable hinged door with door handle and double pad locking arrangement.The enclosure exterior shall be painted with polyurathene paint (colour Light Gray & D.A Gray).There should be proper ventilation spout at the centre of the top edge on either side. The pillar box should be erected over suitable brick structure with plaster and neat cement finishand painting required with mending good the damages to the original finish as required as per direction of EIC.......[2nos at ground , 1nos at academic building & 1nos for vidya charcha bhavan)i). INCOMMER :-415V, 63 Amp TPN Switch Disconnector Fuse Unit with 3 nos. DIN type HRC fuse. (L&T) - 1No. |
| 58 | ii). Timer Circuit :-415V, 4 Pole, 63A FP Contactor(Make L&T MCX / Eqv Legrand) with auxilary NO/NC Contact & 1 No Digital type timer (24Hr) (Make L&T-67DDT0/Eqv. legrand) - 1 Set.iii). OUT GOING :- 415 Volt 100 Amp Bus bar of 4 Nos. 15mm x 3mm [copper Bar on heavy duty porcelain insulator with multi-color tapping & necessary drilled holes. -1 Set.415V, 25Amp FP MCB (L&T) on din rail - 5No.230V, 25Amp DP MCB (L&T) on din rail - 3No. |
| 59 | ELECTRICAL EARTHING WORK |
| 60 | Excavation of soil for installation of Earth Electrode and filling & ramming.For Morrum Soil. [G1:1b] |
| 61 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. Long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. Long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. Long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. Below the ground level as below:a) By TATA-Medium GI pipe. [G1:2a][9nos Highmast+2nos Sign board+8nos foe ext. feeder box+ 4nos for outdoor pole+7nos for bollard fixing] |
| 62 | Extra for treatment of soil by using salt & charcoal or coke forplate electrode.[G2:3b] |
| 63 | Supply & fixing earth busbar of galvanized (HD) MS flat on wall having clearance of 6 mm from wall incl. providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required.i) MS Flat of 40mm x 6mm. [G2:4b] |
| 64 | ii) MS Flat of 25mm x 6mm.[G2:4a] |
| 65 | Connecting the equipments to earth busbar including S&F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages. i). 6 SWG [G2:5ii] |
| 66 | ii). 8 SWG [G2:5iii] |
| 67 | Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe. [G2:3a] |
| 68 | LIGHTNING ARRESTER INSTALLATION |
| 69 | S & F Lightning Conductor Air Terminal made of 20 mm dia 1200 mm long GI pipe (ISI Medium) having five discharge prongs of 4 SWG GI (Hot Dip) wire at top duly soldered/welded with 7/16 stranded GI (Hot Dip) wire and 85 mm dia 6 mm thick GI base plate at bottom incl. neccy. holes etc. complete duly grouted on the parapet etc. in CC mortar ( 4:2:1), incl. thimble joints of 7/16 SWG wire and (25 x 6) mm GI strip with space insulator,SS nuts, bolts & washers.(P-J-2/Item-14 + NS)[Academic Building, Science Building, Vidyacharche Bhavan] |
| 70 | Supply & fixing of 25 mm x 6 mm thick GI (Hot Dip) flat / stripsfor Horizontal & Vertical run on wall / floor including drilling holes, bolts, nuts, washers, etc./ and mending good the damages to buildingworks . (Page : G-3/Item-5d). |
| 71 | Supply & fixing porecline (Sp-65) of electrical and electronic suitable for passing for earth conductor (approved by EIC) with teo nos of screw on wall and suitable arrangement for for fixing earth continuity wire. |
| 72 | Cutting cornices/ steps etc. including cutting recess in buildings etc. & supply & fixing 15 mm bore (ISI-Medium) GI pipe protection as below and mending good damages to the building works:i)Length upto 0.5 Mtr.(P:J-1/Item-4) |
| 73 | Hiring charges for scaffolding arrangement including dismantling at the end of work and carriage, for LC installation, per storey of building per vertical run. (P : J-1/Item-7) |
| 74 | Supply & Fixing of Testing Joints by 25 mm x 6 mm thick GI (Hot Dip) strip 125 mm long on wall after making suitable arrangement to establish a clearance of 50mm from wall for making junction connection with vertical conductor and conductor from earth electrode complete with S & F Epoxy insulator,GI bolts, nuts, check-nuts, spring washers etc. as required.(P:J-2/Item-13) |
| 75 | Earthing with 65 mm dia GI pipe (TATA-Medium)x 3.0 Mts. long and 1 x 19/10 stranded GI (Hot Dip) wire (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including socketing at both ends of stranded GI (Hot Dip) wire by crimping sockets/ thimbles and S & F 40 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts.(Page : G-1/Item-2b(c)) |
| 76 | Excavation of soil for installation of Earth Electrode and filling & ramming as to GS. (For morum soil)(Page : G-1/Item-1b) . |
| 77 | Supply, Laying & Fixing of 50mm x 6mm galvanized (Hot Dip) steel strip in underground trench for interconnection between the Earth Points by joining (As per item no 11). (P : K-3/Item -134 + G-1/Item-1a.) |
| 78 | Jointing for Horijontal & vertical run of GI strip through welded joint of (25 x 6) mm or (50 x 6) mm GI Strip to Lap joints/ \"T\" joints, etc. and painting the joints with 2 (two) coats of bituminous paint. (NS) |
| 79 | LED SIGN BOARD INSTALLATION |
| 80 | 1 No. ACADEMIC BUILDING ROOF TOOP : S.I.T.C of LED glow sign board Fabricated frame Rectangular shape M.S Structure & alumunium conposite pannel outdoor type (Make Aludecor) with ACRYLIC LED letters display board made of suitable size M.S. hollow square bar (size 40x5) by drilling hole incl. S/F nut,bolt, washer. The fabricated structure approx size as following. S/F 3mm trick A.C.P. outdoor type with M.S. frame for facia and setting the acrylic letters as per aproved design which is 2 inch projected from base or equal level of the board incl. acrylic letters fixed on A.C.P sheet will be bolted with by imported acrylic letters with proper branding, moulding & finishing with polishing arrangement. Backside cover by 3mm ACP board for protection of acrylic letters and elecrical connection & driver with extra strong M.S. frame incl. structure painted by 2 coats RO primer over a coats finish paints . All screws/nuts & bolts/clamps etc metals used inside the box should be of non ferrous metal/stainless steel. with Supply & fixing Appropriate size of MS Angle (40x40x5mm), nuts/bolts and clamps to be used outside for fixing the total sign board into the roof or wall permanently.*Terms & condition: If any defect is arrise within one year, contractor should repair (within 7 days) whole Sign board without any cost.i). 1 no Board of 22 Ft x 6 Ft [Academic building Rooftop] |
| 81 | Supply & Fixing special type of imported solid Acrylic letter.The 3mm ACP facial should be provided with Laser cutting 6mm thick acrylic letter out of which 3mm rising from tje suface of the ACP board .6mm letter should be fixed on another 3mm acrylic sheet on back portection should be covered by 1.5\" Aluminum channel as per direction of EIC. |
| 82 | 3D BACKLIT LED SIGNAGE : 2NOS GATE & 1NOS PORCH HEAD : S.I.T.C of LED glow signage metal steel letter (Size as per direction of EIC), letter should be fabricated on wall or roof top (as per site condition)by drilling hole incl. fastners , nut,bolt, washer. The fabricated structure approx size as following with proper branding, moulding & finishing with polishing arrangement in such a process to clearance of atlest 1 inchfor fixing the LED module for proper visiable for minimum distance of 100 meter. *Terms & condition: If any defect is arrise within one year, contractor should repair (within 7 days) whole Sign board without any cost.Letter size should be 1ft in length and width as per design. |
| 83 | Supply & Fixing of LED on acrylic letter from back side [Make: SAMSUNG/MEANWELL or equivalent] having the following specifications:• COLOUR: WHITE or as per the choice of EIC.• 3 Module in 1(One) Feet.• LIFE: 70,000 burning hours.• INTENSITY: Uniform without any bright/dark patches.• VISIBILITY: 100Mtrs at least for normal eye vision.• AMBIENT AIR: 0-50⁰ C ; 100% Relative HumidityPOWER CONSUMPTION: 1.5 Watt per module. (1 module consisting of 3Nos LED) [for 4Nos Signage] |
| 84 | Supply installation testing and commissioning of power supply unit inclusive of water tight gaskets fittedin stainless steel hinged door box also incl Supply & Fixing of Stainless Steel loopbox. Input : 240V AC, 5A; 50Hz.Output: 12V DC, 17-20A constant mode power supply.(Make: Philips/Samsung driver) [for 4Nos Signage] |
| 85 | SITC of iron structure for fixing the sign board at 2nos gate & 1nos at the roof top of the Academic building with MS angle of 40x40x6mm ,50x50x6mm, 75x75x8mm & 75mm x 50 mm x 8mm \"C\" Channel fixing by necessary welding process & by nuts, bolts, washers etc. & necessary double coat of enamel paint (as per direction of EIC).[For Academic Building Roof top Signage] |
| 86 | Scafholding Arrangement of 3nos 3D backlit signage fixing & dismantling at the end of work. (2nos gate & 1nos porch top of academic building] |
| 87 | MISCELLANEOUS ITEM |
| 88 | Supplying and fixing 63A, 415V, TPN SFU open execution in existing SS enclosure/ cubical with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating. (Make-L&T/Havells/Siemens). [set on existing spare location] |
| 89 | Supplying and fixing 63A, 415V, TPN SFU with sheet steel enclosure on flat iron/angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating.(Make-L&T/Havells/Siemens)[ For Fresh connection from exting LT panel Busbar] |
| 90 | Supplying and fixing Havells Make 415A, 415V, TPN on load front operated Changeover switch with Sheet Steel enclos on angle iron frame on wall with nuts bolts etc.[New DG Room from Existing DG connection backup][D2:3a] |