| 1 | Taking down cement or cement lime plaster including racking out joints, hacking for key & scrubbing down with water etc complete all as specified and directed by Engineer - in -Charge. |
| 2 | Taking down Chowkats or frames with shutters (without taking off shutters from the frame) exc 1.5 sqm but not exc 4 sqm each and removing from site complete all as specified and directed. |
| 3 | Demolition of brick work or stone/ boulder masonry, built in cement mortar or cement lime mortar including all quoins, arches, pillars etc but excluding ashlar facing dressed stone work and precast concrete articles complete all as specified and directed by Engineer-in-Charge. |
| 4 | M&L rendering 15 mm thick in CM 1:6 on fair face of brick masonry or concrete surfaces finished even and smooth without using extra cement complete all as specified and directed by Engineer-in-Charge. |
| 5 | M&L for preparing newly plastered surfaces and applying two coat distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gms/litre, of approved manufacturer, of required shade and colour complete, as per manufacturer\"s specification and including one coat of primer on surfaces complete all as specified and directed. |
| 6 | M&Lfor two coat of distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gms/litre, of approved manufacturer, of required shade and colour complete, as per manufacturer\"s specification.and including one coat of primer including complete removal of existing surfaceall as specified and directed. |
| 7 | S&F powder coated (Minimum thickness of powder coating 50 micron) Anodised aluminium frame for doors, windows, ventilators with one or more rebates including joining cleat for fixing etc. complete all as specified |
| 8 | M&L powder coated (Minimum thickness of powder coating 50 micron) Anodised aluminium door shutters, aluminium section weighing 0.55 kg/ m including necessary joining cleats, glazing clips, ruber neoprene packing, handles 2 Nos in each door, hinges, anodised aluminum snap beading screws etc. complete all as specified |
| 9 | S&F 5.5 mm thick Sheet glass, ordinary quality and glazing in Aluminium door,windows etccompleted all as specified and directed. |
| 10 | S&F for double action floor spring hydraulically regulated made up of minimum 1.25 mm thick aluminium alloy sheet foundation box, main body with stainless steel cover, governing pivot made of brass, other parts made of mild steel heavy duty and fixed complete all as specified and directed. |
| 11 | Taking down and re-fixing of aluminiumdoor shutterexc 1sqm but n. exc 2sqm eachfor necessary repair such as change of 5mm thick glass pane , wire mesh,guard frameandincluding necessary joining cleats, glazing clips, ruber neoprene packing, handles 2 Nos in each door, hinges, tower bolts, anodised aluminium snup beading screws etc,Complete all as specified. |
| 12 | Providing and fixing Powder coated aluminium (minimum thickness of powder coating 50 micron) work for doors, windows, ventilators and partitions (Fixed portions) with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS:1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing/ paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-Chief |
| 13 | S&F 6 mm thick aluminium composite (ACP) panels sheet, coloured with decorative choice, fixed to aluminium frame work as in doors/partitions, complete all as specified and directed. |
| 14 | M&L for 2mm thick PVC Anti staticESD Vinyl flooring alongwith cooper strip will be fixed on the existing floor as per manufacture instruction and make will be approved by GE.Fixing procedure of Anti static ESD Vinyl flooring will comprise the following steps: (i) Existing leveling floor to be prepared by grinding to handle unevenness, remove all the surface dust of floor before commencement of ESD flooring installation.(ii) Material should be placed on site for more than 24 hours to adopt to the temperature and humidity. (iii) Adhesive for ESD flooring is conductive type and adhesive can spread per sqm as per manufacture instruction. Use a trowel or scraper to apply conductive adhesive on the floor evenly.(iv) Lay the copper strip, normally the grid is 600mmx600mm oras per manufacture instruction under the ESD flooring including necessary groove cutting in existing floor and filling the surface with necessary material and connected the cooper strip to the earthing pits by making holes in the existing walls. (v) When adhesive is dry, choose a start point and lay the flooring. Ensure the sticking firm and seam between is straight. Cutting the tiles accordingly of corner and wall sides. (vi) Use a slofting machine to grove along the seams of tiles, the groove width is approx 3mm or according to the welding rod which will fix in it. Use manual or automatic welding gun to hot weld rod to the tiles, ensuring that welding rod color match the color of ESD Tiles. Allow welding rod to cool off and the use a blade to showel the extra part of rod.(vi) Test the electronic resistance of conductive tiles (ESD) as per manufacture instructions. |
| 15 | M&L for 2mm to 4mm thickness Vinyl flooring plank approved by GE and make will beSuprex Chorche or equivalanttofixing to existing floor as per instruction of manufacture. Fixing procedure of Vinyl flooring will comprise the following steps: (i) Proper cleaning of floor with water or with air blower, after dry of floor, uneveness of floor removed by putty work/cement work with proper smoothness and clean again with water/air blower as per requirements. Divide the room size accordingly fixing plank size with chalk. (ii) apply adhesive on the back side of plank and stay for dry as per manufacture instructions. (iii) Apply the Manufacturer recommended adhesive to sub floor with trowel, starting at the center point and working outword into the desired area. Allow the adhesive to set somewhat until it is tacky but still clouldy/hazy in color. (iv)Place the first plank with its shorts edge at the junction of the two chalk lines. continue the lay planks row by row, working along the parallel chalk line and ensuring the edge of each plank fit tightly against the neighboring plank. Trim the border planks as needed. (v) Glue down Vinyl plank flooring needs to be rolled with a floor roller after installation to firmly and evenly seat the Vinyl planks into the adhesive. Wipe away or knife to peel away any adhesive thats gets into the seams between planks. |
| 16 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded copper conductor, 11000 volts grade, of size 4 core 10 sq mm. |
| 17 | M&L in replacement for earthing complete with copper earth plate electrode 60cm x 60cm X3.15mm thick, buried directly in ground (earth pit not less than 3.0 mtr deep beliow ground level) with top edge of the plate not less than 1.5 mtrs below normal ground level,connected to and including copper earth strip size 20x3mm as earthing stripby means of bolts,nut check nut and washers of galvanised iron all as shown inin electrical plate No 5 of MES SSR Part I and testing on completion including excavation and earth work in any type of soil,PCC (1:3:6) type C1 chamber ,MS frame and cover 6 mm thick in cement concrete (1:2:4) type B1 reinforced with welded steel wire fabric or XPM (weight not less than 4 Kg per Sqm) with cast iron frame,funnel with wire mesh,GI watering pipe 20 mm dia medium grade and lugs complete all as specified and directed with earth resistance not more than 1.0 Ohms. Writing of details on the surface of the pit with paint complete all as specified and as directedby Engr-In-Charge. Note:- On testing ,after completion ,if the earth resistance below 1 Ohms is not obtained ,earthing will rejuvenated at no extra cost till the desired earth resistance is obtined. |
| 18 | S & F copper earth strip size 20x3 mm with shadel and screw,nut,bolt complete all as specified. |
| 19 | S&FSub main wiring with two single core cable PVCinsulated unsheathed of copper multi strandard conductor FR-LSH cable of size4.0 sqmm, 1100 votls grade drawing through PVC conduit 20 mm diamedium duty including acessories such as Tee, bend, Elbow etc, ISI marked with and including PVC insulatedsqmm unsheathed multistranded FR-LSH copper conductor cable for earth continuity and connected to common earth dolly including cutting chasing of wall, if required and making good disturbed surface in CM (1:3) and finishig the surface to match with existing surface, etc complete all as specified and directed by Engineer-in-charge. (Note:- Three lengths of 4.0 Sqmm cable and PVC conduit will be measured as one length). |
| 20 | S&F modular metal flush box 4 module complete all as specified and directed by Engineer-in-Charge. |
| 21 | S&F modular switch 1way5 pin, 16 amp 240 voltcomplete all as specified. |
| 22 | S&F modular Socket 6A/16A - 2/3 pin combined 2 module complete all as specified. |
| 23 | S & F modular White cover plate with frame, 4 module complete all as specified and directed by Engineer-in-Charge. |
| 24 | Supply and fixing VTPN DB double door sheet metal enclosuremade out of CRCA mild steel sheet concealed surface mounting TPN, 4 way,including MCCB 125 amp, 440 Volt, with 200 rated bus bar complete all as specified and directed. |
| 25 | Supply and fixing SPN DB 12 way double door sheet metal enclosuremade out of CRCA mild steel sheet concealed surface mounting , 240 Volt, with 200 rated bus bar complete all as specified and directed. |
| 26 | S&FSub main wiring with two single core cable PVCinsulated unsheathed of copper multi strandard conductor FR-LSH cable of size2.5 sqmm, 1100 votls grade drawing through PVC conduit 20 mm diamedium duty including acessories such as Tee, bend, Elbow etc, ISI marked with and including PVC insulated 2.5 sqmm unsheathed multistranded FR-LSH copper conductor cable for earth continuity and connected to common earth dolly including cutting chasing of wall, if required and making good disturbed surface in CM (1:3) and finishig the surface to match with existing surface, etc complete all as specified and directed by Engineer-in-charge. (Note:- Three lengths of 2.5 Sqmm cable and PVC conduit will be measured as one length). |
| 27 | S&FSub main wiring with two single core cable PVCinsulated unsheathed of copper multi strandard conductor FR-LSH cable of size6.0 sqmm, 1100 votls grade drawing through PVC conduit of suitable size ofmedium duty including acessories such as Tee, bend, Elbow etc, ISI marked with and including PVC insulatedsqmm unsheathed multistranded FR-LSH copper conductor cable for earth continuity and connected to common earth dolly including cutting chasing of wall, if required and making good disturbed surface in CM (1:3) and finishig the surface to match with existing surface, etc complete all as specified and directed by Engineer-in-charge. (Note:- Three lengths of 6.0 Sqmm cable and PVC conduit will be measured as one length). |
| 28 | S&F PVC rectangular box type switch sockit combination 5 pin, 15 amp 240 voltcomplete. |
| 29 | Supply and fixing SPN DB 8 way double door sheet metal enclosuremade out of CRCA mild steel sheet concealed surface mounting , 240 Volt, with 200 rated bus bar complete all as specified and directed. |
| 30 | Supply and fixing SPN DB 4 way double door sheet metal enclosuremade out of CRCA mild steel sheet concealed surface mounting , 240 Volt, with 200 rated bus bar complete all as specified and directed. |
| 31 | Supply and fixing TPN DB double door sheet metal enclosuremade out of CRCA mild steel sheet concealed surface mounting TPN, 4 way, 440 Volt, with 200 rated bus bar complete all as specified and directed. |
| 32 | S&F in MCB TPN/FP 40 to 100 Amps \"B\" curves MCB repturing capacity 10 KA etc complete all as specified and directed by Engineer-in-Charge. Make:-Indoasian/Anchor/Legrand/ABB |
| 33 | Supply and fixing miniature circuit breaker (MCB) of single poles and Neutral(SPN) ,current carrying capacity 40 to 63 AMP, 240V, 10 KA \"B\" curve in the MCB DB Complete with connection testing and commissioning. |
| 34 | Supply and fixing 240V, 10 KA \"B\" curve miniature circuit breaker (MCB) of single poles and current carrying capacity 5 to 32 AMP, in the MCB DB Complete with connection testing and commissioning. |
| 35 | M & L Earthing complete with galvanised\steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0 sqmm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completionall as specified and directed by Engineer-in-Charge. |
| 36 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 1100 volts grade, of size 4 core 16 sq mm.all as specified and directed by Engineer-in-Charge. |