| 1 | M & L for comprhensivemaintenaceof Fire alarm system installed at various Tech Bldgs of 2 Wing. comprehensive maintenancethe following worksincludingcomplete all as specified and directed.Note:-(i) The maintenance cost offire alarm system shall deemed to comprises of cost of labour employed for the purpose, T&P used and other petty items such as batteriessand other cleaning materials etc. (ii) Servicing shall be carried out authorised dealer of manufacturer i.e. OEM.(iii)Non attending the complaint with in 3 days @ Rs. 500.00/day shall be recoveredfor the fourth day by the contractor.(iv)Keeping the complaint pending after fourth day @ Rs. 1000.00/day shall be recoveredfor the fourth day by the contractor.(v) The complaint shall be generated by Telephonically/Verbally by concern JE E/M or Engr-Incharge. |
| 2 | (vi) Servicing of quaterly basis of fire alarm system installed in following Bldgs including first hand repairs, consisting of normal repairs andcleaning of all components such as smoke detectors/manual call point/sounder/translator/expendor / input/output module etc of any type installed in Bldgs using proper method and tools , replacement of unserviceable Battries of connected system , tightening of all connections as required including replacements of defectivespares andrequired calibration of control pannel and connected items check and maintain the system for efficent functiong of intire system,including troubleshooting and clearance of all faults from the panel.Testing of EachFire alarm systemin presence of User and MES Repandgive quaterly basis servicibility report duly signed by user and Engr-in-Chargecomlete all as specified & directedin all respect. Note :MajorItems ifrequired forRepairshall be measured &paid separately underrespective item.(a)Base Ops (b) FSS (avoinic lab)(c) Tech Fly Hanger (d)30 Sqd Hanger(e) JTF Hanger(f)20 Sqd Hanger(g) 31 Sqd Hanger(h) RT Cabin(j) GCA Bldg(k)Logistic Bldg(l) SRE Tower(m) SMC(n)SSC(o) LDP Lab Bldg(p) Simulator (q) PTT (r)Fire Stn(s) Guruth complex (t)PAR Bldg (u) 2402SqnNote:Expert / Technician should report/rectify the defect as per site requirement irrespective of visits carried out. |
| 3 | Taking down exising Fire Alarm system panelrepair/replacement unserviceable part including mother board , display,power supply & battery of microprocessor based networkable Analogue Addressable fire Alarm control panelcomplete all as specified and directed . |
| 4 | Taking down exising Fire Alarm system panel in replacementS&F Addressable Fire alarm control panel complying with BS EN 54 Twoloop panel of capacity from 99 detectors & 99 modules upto 200 detector and modules including battery, display,key pad,buzzer etc complete all as specified and directed . |
| 5 | Taking down exising Beam Detectorin replacementS&F Supply, Installation, Testing and Commissioning of Approved Projected Beam Detector Complete set with required all control and associated module,the detector shall be of range 100 mtsShould be Microprocessor based complete all as specified and directed .• Signal strength LED\"s• Should Provide linear protection• Automatic compensation for signal drift or dirty lens• Minimum Three field adjustable sensitivity settings• Form A alarm and Form B trouble contacts• Calibrated filters shall be vailable to verify sensitivity• Emitter and Receiver type |
| 6 | Taking down exising Manual Call point in replacementS&F Supply, Installation Testing & Commissioningof Analogue Addressable Manual Call Point with Integral Short Circuit Isolator, Analogue Addressable Protocol having,Bi-coloured status LED (red for alarm, amber for (short-circuit), Non-frangible element fitted as standard (conforms to EN54), pulsing/non-pulsing can selectable via panel, Electronically addressed complete all as specified and directed . |
| 7 | Taking down exising Wall sounder in replacement Supply, Installation, testing and commissioning of Intelligent loop powered wall Sounder which provide a range of tones and volumes with a maximum output of up to 102dB(A) (±2dB(A)) with low current consumption, 51 user selectable tones (all tones EN54-3 compatible) complete all as specified and directed . |
| 8 | Taking down exisingMulti sensor detectorin replacementS&F Supply, Installation Testing & Commssioningof Analogue AddressableMulti- Sensor detector which is fully compatible with Analogue Addressable Protocol,having removable high performance chamber with Twin fire LED\"s allow 360 degree veiwing, User selectable sensitivity modes 1% to 4.5% obs/m, Incorporate Optical and dual Heat elements, lock mechanism ( sensor to base), Electronically addressed, Pulsing/non-pulsing controlled from panel complete all as specified and directed . |
| 9 | Taking down carefully from trench/wall/roof/trench of hanger/buildingloose/hanging/deshaped of any size unserviceable cable etc complete all as specified and as directed. |
| 10 | Material and labour for supply and fix armored fire cable copper conductor of size 2 Core 1.5 sqmm two core FRLS in Red colour fixed on wall / roof with GI saddle complete all as specifed and directed by Engineer-in-Charge at site |
| 11 | Taking down old unserviceable/damage from roof & wall of the hanger/building in replacementSupply, Installation, Testing and Commissioning of Hybrid Wireless Optical Smoke Sensor with Bi-directional wireless communication,Self optimising wireless amplitude and frequency, in-built magnet test, operating on 865-868 MHz with communication range up to 1000 m in open air, 95% RH (non condensing),Primary & Secondary Power Supply LPCB Approved, Approved to EN54-7 & 25B complete all as specified and directed . |
| 12 | Taking down old unserviceable/damage from roof & wall of the hanger/building in replacementSupply, Installation, Testing and Commissioning of Compatible Batteries for above type of detectors to be used in existing system installed. complete all as specified and directed . |
| 13 | Taking down old unserviceable/damage from roof & wall of the hanger/building in replacementSupply, Installation, Testing and Commissioning of Hybrid Wireless Translator Module with Bi-directional wireless communication,Self optimising wireless amplitude and frequency, Loop Powered, allows the connection of up to 126* radio field devices to an addressable fire detection loop, Incorporates a Loop Short Circuit Isolator and an OLED display, operating on 865-868 MHz with communication range up to 1000 m in open air, 95% RH (non condensing), RED compliant, LPCB Approved, Approved to EN54-17, 18 and 25. complete all as specifed and directed by Engineer-in-Charge. Make:- Hochiki to be compatible with Existing Fire Alarm System |
| 14 | Taking down old unserviceable/damage from roof & wall of the hanger/building & Supply, Installation, Testing and Commissioning of Hybrid Wireless Expander Module with Bi-directional wireless communication,Self optimising wireless amplitude and frequency,Up to 126 Expander Modules may be configured to any one Translator Module, Supports MESH communications, operating on 865-868 MHz with communication range up to 1000 m in open air, 93% RH (non condensing), RED compliant, LPCB Approved, Approved to EN54-18 and 25 complete all as specified and directed . |
| 15 | Taking down old unserviceable/damage from roof & wall of the hanger/building & Supply, Installation, Testing and Commissioning of Hybrid Wireless Manual Call Point with Bi-directional wireless communication, Self optimising wireless amplitude and frequency, Resettable Element, fully addressable and intelligent monitoring functionality operating on 865-868 MHz with communication range up to 1000 m in open air, 95% RH (non condensing), Up to 10 year battery life Dependant on operational usage, Primary & Secondary Power Supply, LPCB approved, Approved to EN54-11 & 25. complete all as specifed and directed by Engineer-in-Charge. Make:- Hochiki to be compatible with Existing Fire Alarm System |
| 16 | Taking down old unserviceable/damage from roof & wall of the hanger/building & Supply, Installation, Testing and Commissioning of Hybrid Wireless Sounder with Bi-directional wireless communication, Self optimising wireless amplitude and frequency, 4 Tone Settings, fully addressable and intelligent monitoring functionality operating on 865-868 MHz with communication range up to 1000 m in open air with Max. sounder output 93 dB(A) @ 1 metre, 95% RH (non condensing), Up to 10 year battery life Dependant on operational usage, Primary & Secondary Power Supply, LPCB approved, Approved to EN54-3 and 25 complete all as specified and directed . |
| 17 | Taking down old unserviceable/damage from existing Fire Alarm system panel andSupply & Installation, Testing and Commissionig of Sealed lead Acid Battery CS 7-12, 12 V, 7 AH Chrge parameters, Constant Voltage Charge with voltage reguation (27 degree C) stanby use 13.6V -13.8V, cycle use -14.1 V-14.4V, Max initia current 1.4 A suitabe for Existing fire Alarm panel complete all as specified and directed . |
| 18 | Dismantling cross-arms of M.S. channel or angle sections, clamps, nut bolts etc. complete all as specified and directed. |
| 19 | Dismantling / taking out insulator of any size / type from existing electric LT lines complete all as specified and directed . |
| 20 | Dismantling of existing stay assembly any type / size from its stay rod, cutting stay rods (above ground portion) dismantling MS clamps, nuts, bolts, stay bow, loop insulators, stay wire etc complete all as specified and directed . |
| 21 | Dismantling / taking out existing ACSR conductor any size from existing over head lines incl disconnection complete all as specified and directed . |
| 22 | Taking down Old unserviceableLT UG cable of service connection or distribution systemof any size and removing from site complete all as specified and directed ..( Excavation and earth work will be measured seperately) |
| 23 | M&L for scrapping of old alum paint of steel tubular pole 9/11 mtr by means of emery paper for preparation of smooth surfaces andpainting with two coats of alum paint on pole , brackets old junction boxes channels etc inclalternate 30 cm wide white andblue strip painting up to 1.5 Mtr height from ground level complete all as specified and directed . |
| 24 | Material & Labour forpainting to feeder pillar box / LT panel & duct coveretc, including angle iron frame with two coat of grey synthetic enamel paint includingwelding of door with proper size new hinges of suitable size and locking arrangementswhere required complete all as specified and directed . |
| 25 | Supply & fix line separator suitable for LT OH line of 3 phase and neutral conductor complete all as specified and directed . |
| 26 | All as per item No.24 above but single phase and neutral conductor complete all as specified and directed . |
| 27 | Cutting/trimming of treesupto 150 mmgirth including cutting of upper portion of branches above poleclearance up to 10 mtrs and disposal ofsame at a distance not exc 50 mtr and clearing of site complete all as specified and directed .(Note:Tools/ladder required for cutting/trimming of trees will be provided by the contractor at no extra cost and cost of the same be deemed to be included in the quoted rate.)Note:Each Span will be measured from one pole to another pole |
| 28 | Removing LT over head conductor from insulator where ever required and restretching the same without any kink / bend upto premissible sag, binding it on insulator by means of binding wire including fixing line seprator at 3 places where required and directed and testing LT over head line on completion and complete all as specified and directed . |
| 29 | Provn ofservices for cable fault locationfor LT UG cable, XLPE insulated 1100 Volts, of any size with fault detector machine complete all as specified and as directed. |
| 30 | Material and labour for straight through jointing kits heat shrinkable type LT UG XLPE cable heavy duty armoured sheathed including excavation in any strata, taking out cable, and making disturbed surface after relaying the cable making joints suitable for aluminium conductor of size given below complete all as specified and directed . |
| 31 | 25 to 50 sqmm 3.5 core complete all as specified and directed . |
| 32 | 70 to 150 sqmm 3.5 core complete all as specified and directed . |
| 33 | 185-240 sqmm 3.5 corecomplete all as specified and directed . |
| 34 | 300-400 sqmm 3.5 core complete all as specified and directed . |
| 35 | Supply and fix GI Pipe Light gradewith all connected accessoriesof sizes100 mm complete all as specified and directed . |
| 36 | Supply and fix GI Pipe Light gradewith all connected accessoriesof sizes80 mm complete all as specified and directed . |
| 37 | Supplying and erecting ( in true vertical position) steel tubular swaged poles complete with cast iron base plate final taper plug, bolts nuts and screws all as specified of type 410-SP-31 (9.0 mtr length) complete all as specifed in IS 2713 (part-II) 1980 including one coat or red oxide primer and two coats of aluminium paint to exposed surfaces and with blach bituminous paint for embedded portion of pole complete all as specified and directed . |
| 38 | Material and labour for cross arms, bracing supports, clamps and back plates fabricated from structural steel sections, including nut bolts, washer welding bending cold/ hot, drilling holes for bolts in any shape or size as indicated or directed and inclusive of one premer coat of red oxide primer, one under coat and one finishing coat of aluminium paint complete all as specified and directed . |
| 39 | Material and labour for replacement of old broken ACSR with aluminium conductor steel reinforced streching without kinks / bends and binding with insulators on street poles complete all as specified and directed . ( Taking down shall be paid under separate item of BOQ) |
| 40 | S&F shackle type insulator vitreous procelain white / brown / greenwith and including galvanised mild steel straps, washer insulator, bolts and nuts, insulator of size 100mm height and 115 mm max dia with working pressure 1100 volt and galvanised steel straps 3 to 5 mm size and suitable size nut and bolts complete all as specified and directed . |
| 41 | M&L for providing pin type procelain white / brown / green / insulator including galvanised mild steel spindle, two galvanised iron.Washer and one galvanised iron nut, 100mm height 65 mm dia for 1100 volts grade complete all as specified and directed . |
| 42 | M& L for danger notice plate 1.6 mm thick mild steel sheet vitreous enamelled white with letter figures and conventional skull and tongue in signal red colour and fixed with MS clamps bolts nuts of approved size LT, 20x15cm complete all as specified and directed . |
| 43 | M&L for cement concrete (1:4:8) type D2 in foundation filling and mass concrete using 40mm graded stone aggregate for pole/stay foundation or as required on siteetc complete all as specified and directed . |
| 44 | M&L for cement concrete (1:3:6) type C2 in foundation filling and mass concrete using 40mm graded stone agg for pole/stay foundation or as required on siteetc complete all as specified and directed . |
| 45 | M&L for cement concrete (1:2:4) type B1 in foundation filling and mass concrete and coping of poles incl necessary form work using 20 mm graded stone aggregate etcor as required on siteetc complete all as specified and directed . |
| 46 | Supplying, spreading & leveling stone aggregate size of 40 mm grade to the existing sub station or complete all as specified and directed . |
| 47 | Supplying ,Laying, jointing, testing and commissioning of LT under ground cable 1100 volts grade XLPE(cross linked polythene ) armoured with galvanised round steel wire or steel strip , electric power cable heavy duty, with multi stranded aluminium conductor, laid in trenches, ducts fix on walls/poles with proper size saddles and clamp laid under roads/path/ drain /colverts or enclosed in GI pipe/ fix complete all as specified and directed for following size:- |
| 48 | 16 sqmm 4 core |
| 49 | 25 sqmm 3.5 core |
| 50 | 35 sqmm 3.5 core |
| 51 | 50 sqmm 3.5 core |
| 52 | 70 sqmm 3.5 core |
| 53 | 95 sqmm 3.5 core |
| 54 | 150 sqmm 3.5 core |
| 55 | 300 sqmm 3.5 core |
| 56 | 16 sqmm 2 core |
| 57 | 10 sqmm 4 core |
| 58 | Excavation in trenches not exc 1.5 m wide andnot exc 1.5 m in depth and getting it out for laying of cable / pole etc.complete all as specified and directed . |
| 59 | Soft/loose soil |
| 60 | Hard/dense soil |
| 61 | Soft/disintegrated rock |
| 62 | Returning/ Refilling of excavated soil including spreading levelling and well ramming in layers for any type of soil complete all as specified and directed . |
| 63 | Removing the surplus spoil to a distance not exceeding 50 mtrs from the starting point and depositing at a height not exceeding 1.5 m above ground level complete all as specified and directed . |
| 64 | Material and labour for stone dust sand cushioning to under ground cable, provided with a layer 8 cm before and 15 cm after laying and stretching jointing and testing the cable complete all as specified and directed .[Note : Measuremenet will be done after punning] |
| 65 | M&L for brick protection covers laid over cables of sub class\"B\" bricks old size complete all as specified and directed . |
| 66 | Supply and fix in repair / replacement of MCCB FP 630 Amps Adjustable type with breaking capacity50 KAincluding connections and testing for proper functioningincl taking out unserviceablecomplete all as specified and directed. |
| 67 | Supply and fix in repair / replacement of MCCB FP 400 Amps Adjustable type with breaking capacity36 KAincluding connections and testing for proper functioning incl taking out unserviceablecomplete all as specified and directed. |
| 68 | Supply and fix in repair / replacement of MCCB FP 250 AmpsAdjustable type with breaking capacity36 KAincluding connections and testing for proper functioning incl taking out unserviceable complete all as specified and directed. |
| 69 | Supply and fix in repair / replacement of MCCB FP 200 AmpsAdjustable type with breaking capacity36 KAincluding connections and testing for proper functioning incl taking out unserviceablecomplete all as specified and directed. |
| 70 | Supply and fix in repair / replacement of MCCB FP 160 AmpsAdjustable type with breaking capacity36 KA including connections and testing for proper functioning incl taking out unserviceable complete all as specified and directed. |
| 71 | Supply and fix in repair / replacement of MCCB TP 200 Amps Adjustable type with breaking capacity36 KAincluding connections and testing for proper functioning incl taking out unserviceable complete all as specified and directed. |
| 72 | Supply and fix in repair / replacement of MCCB TP 160 Amps Adjustable type with breaking capacity36 KAincluding connections and testing for proper functioningincl taking out unserviceablecomplete all as specified and directed. |
| 73 | Supply and fix in repair / replacement of MCCB TP 100 Amps Fixed type with breaking capacity 16 KAincluding connections and testing for proper functioning incl taking out unserviceablecomplete all as specified and directed. |
| 74 | Supply and fix in repair / replacement of MCCB TP 63 AmpsFixed type with breaking capacity16 KAincluding connections and testing for proper functioningincl taking out unserviceablecomplete all as specified and directed. |
| 75 | Taking down old LT panel and Supply install, test and commissioning of Powder coated LTpanel cubical Outdoor type double door, free standing type compartmentalized in construction fabricated from CPRI approved manufacturer specified in particular specification and made out of 3 mm thick CRCA sheet & suitable size to accomodate all accessories / fittings, to accommodate incoming MCCB/ACB and TPN Copper bus bars , incomer ACB/MCCB and outgoing feeders with MCCB/MCB.The TPN bus bars shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator. Thecubicle shallhavefree standing bottom frame/stand of height 700mm & dimension as required for panel & shall be made out of equal angle iron of size 50mm x 50mm x 6mm. A detachable predrilled gland plate of thickness not less than 3 mm thickpowder coated should be used at thebottom for entry of armoured cableof adequate size with glands.The above panel shall be front & back openable lockable /openable by key from both side. Copper extension link shall be provided at incomer & outgoing end of MCCB of rating 63 Amps & above. The panel shall be powder coated with 7 Tank Process of approved thickness complete including CTs, control wiring by 1.5Sqmm Wire, including taking down of old unsv panel after disconnecting Existing cable & Reconnecting the cables to new panels including providing cable glands, lugs, nut bolts etc, grouting bolts, the panel shall comprise of following and including demolition of existing PCC foundation and making good as per existing, complete all as specified & directed. |
| 76 | With the following acessoriesa) Copper bus bar 630Amps for 4 Poleb) MCCB FP 400 Amps 415 Volt36 KA,Ics =100% Icu - 1 Nosc) MCCB TP 250 Amps 415 Volt25 KA,Ics =100% Icu - 2 Nos. d) MCCB TP 63 Amps 415 Volt16 KA,- 1 Nosf) RYB Indicators - 1 Set and g)Digital 3 Phase Amp Meter and Voltmeter with selector switch - 1 Set h)ML-2 Contactor-1 No i)Digital street light timer-01 Nosj) Auto Manual Selector switch- 01 Nos k) TPN 40 Amp connector-02 Nosl)MCB TPN 40 Amps- 1NosNote - (i) The lay out drawing of the panel shall be got approved by the contractor before panel fabrication.(ii) Cost of PCC foundation 1:2:4 below GL 30cm & above 30cm is deemed to be included in the quoted rate.(iii) The panel shall be gotfabricated from CPRI approved makes given in Particular specifications.(iv) Panels Manufactured from channel partner shall not be accepted. |
| 77 | All as per item no 57.00 but with the following acessoriesa) Copper bus bar 250Amps for 4 Poleb) MCCB FP 160 Amps 415 Volt25 KA,Ics =100% Icu - 1 Nosc) MCCB TP 63 Amps 415 Volt16 KA,- 1 Nosf) RYB Indicators - 1 Set and g)Digital 3 Phase Amp Meter and Voltmeter with selector switch - 1 Set h)ML-2 Contactor-1 No i)Digital street light timer-01 Nosj) Auto Manual Selector switch- 01 Nos k) TPN 40 Amp connector-02 Nosl)MCB TPN 40 Amps- 1NosNote - (i) The lay out drawing of the panel shall be got approved by the contractor before panel fabrication.(ii) Cost of PCC foundation 1:2:4 below GL 30cm & above 30cm is deemed to be included in the quoted rate.(iii) The panel shall be gotfabricated from CPRI approved makes given in Particular specifications.(iv) Panels Manufactured from channel partner shall not be accepted. |
| 78 | Supply and fixing SP 5 To 32 Amps rating 240V, 10KA \"C\" curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the MCB DB complete with connection testing andcommissioning complete all as specified and directed . |
| 79 | All as per item no 58 above butSPN 32 Amps complete all as specified and directed . |
| 80 | All as per item no 58 above butTP 25 to 63Amps 415 Volts complete all as specified and directed . |
| 81 | Earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6mm as earthing lead buried directly in ground vertically to a depth not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below normal ground level connected to and including galvanised iron strip 25 X 4 mm as earthing lead by means of bolts, nuts, check nuts & washers etc made of GI and connected to earthing test point all as shown in electrical plateNo. 5 of SSR Part I of 2009 & as specified or indicated and testing on completion including excavation/earth work in any type of strata PCC ( 1:3:6 ) type C1 earthing chamber, pre cast slab cover 50 mm thick in cement concrete ( 1: 2 : 4 ) type B 1 ( reinforced with welded steel wire fabric (XPM) weight not less than 4 Kg / Sqm),funnel with wire mesh, watering pipe of 20 mm bore medium grade, including galvanised iron strip 25X4 mm with GI protection pipe of 40 mm medium grade up to 7.5 meter length, etc complete all as specified. |
| 82 | S & F GI earth continuity conductor or main earthing lead of size 25x4 mm fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for earthing etc. as required complete all as directed. |
| 83 | Opening/disconnecting the electrical connection of defective/burnt out underground LT Cable of any size 2 to 4 core from main switch/DB/ junction box / LT panel /LT OH line etc. Taking out the required length of cable from existing loop, cutting the defective portion of cable, providing required thimbles/ connectors at cable end and reconnecting the cable in previous location with existing main switch/ DB/Junction box /LT Panel/ OH line etc complete all as directed. |
| 84 | Material and labour forgetting out removing of grass and vegetation grown around the electrical installations like transformers, LT panels, 2 pole structure, HT panels and complete area inside the fencing all as specified and directed by Engr-in-Charge Note : Item may be measured and paid more than one time as per site requirement to clean the E/M Installations |
| 85 | Monthlymaintenance / servicing ofSewage Treatment Plant as per regulation and Sewage Pumping House at various lacations as mentioned below :-Note : i. Unit rate quoted by tenderer is inclusive of checking of system monthly by skill mechanic (must have experience in respective field)with helper and necessary servicing & repair greasing,oilng of plant equipment ,filter back wash. the register will be maintained to that effect.ii. In addition to above, specific emergency complaints from time to time shall be attended after receiving the same.iii.In addition to above supervisor will provide instructions to operator for smooth operatoion and proper treatment of STP. |
| 86 | N.P. Area STP (capacity-1600 KLD) complete all as specified and directed . |
| 87 | MAP Pocket 1 Sewage Pump House complete all as specified and directed . |
| 88 | Viman Nagar STP (Capacity-600 KLD) complete all as specified and directed . |
| 89 | Latiff Hall Sewage Pump House complete all as specified and directed . |
| 90 | Chandan Nagar STP (MAP Pocket 3) (capacity- 190 KLD) complete all as specified and directed . |
| 91 | Akash Nagar STP (MAP Pocket 4) (Capacity -165 KLD) complete all as specified and directed . |
| 92 | Material and labour for Cleaning of sewage well of STP Plant of following Capacity 1600KLD,600KLD,190KLD,165KLDdescribed below:- (i) Dewatering with submersible / sludge pump to empty the sump/tank upto base level. (ii) Removing sludge from sump wall and bottom with the help of special sludge pump and remaining dirt which may have hidden in rough slots of the bottom manually with brush.(iii) After cleaning the sump apply bleaching powder for disinsfection of sump (iv) write cleaned on date and next clean in blue PVC sheet with white letter afte cleaningcomplete all as specified and directed . |
| 93 | Receving Sump |
| 94 | Equalization Tank (Reactor Tanks ) |
| 95 | Tube Settler |
| 96 | CCT, FFT, TWT |
| 97 | UG sump 1.5 lakh gln (treated water Sump) |
| 98 | UG sump 1.0 lakh gln (treated water Sump) |
| 99 | M & L for Repairsto Air Blowerincluding replacement of thefollowing worn out spare parts andtesting complete all as directed by Engineer-in-charge.(as Per existing Make) |
| 100 | Gear Assembly as per existing make and capacity |
| 101 | Slight Glass Assembly as per existing make and capacity |
| 102 | Bearing Set (each Set =4 Nos) as per existing make and capacity |
| 103 | Oil Seal & Oil Ring as per existing make and capacity |
| 104 | V Beltas per existing make and capacity |
| 105 | Oil for Blower as per existing make and capacity |
| 106 | Replacementof DMF( Dual Media Filter) Media replacing the worn out spare parts and overhauling the same incl testing complete all as directed by Engineer-in-charge.(as Per existing Make)(a)Filtering Sand (as per existing size) |
| 107 | Supply of ACF (activated Carbon Filter) Media replacing the worn out spare parts and overhauling the same incl testing complete all as directed by Engineer-in-charge.(as Per existing Make)(a)Activated Carbon |
| 108 | Taking up or Down unserviceable Heavy duty flexible Kanaflex pipe and replace with newalong with MS clamps and nut bolts with all fiiting complete all as specified and directed by Engr-in-Charge |
| 109 | 50 mm dia |
| 110 | 80 mm dia |
| 111 | 100 mm dia |
| 112 | 150 mm dia |
| 113 | Material and labour for reparing/maintenance of existing electrical panel boards of pump sets by replaing worn out spares as cable glands/ lugs pin type,U type,burn wire and connectorsetc, cleaning of panel board, tightening of cable connection to avoid sparking, insulating bus bars bracket portion of conductor and to ensuring proper function of the panel board complete all as specified and directed . |
| 114 | S & F Indicator Lamp LED Type complete all as specified and directed . |
| 115 | S & F Selector switchfor Ammeter/volt meter complete all as specified and directed . |
| 116 | S & F Selector switch for Auto manual complete all as specified and directed . |
| 117 | S & Fof voltmeter of 0 to 500 Volts suitable for existing panel board and taking outof old unserviceable volt meter complete all as specified and directed . |
| 118 | S & F ammeter 0 to 30 Amps suitabletopanel boardand and taking outof old unserviceable ammetercomplete all as specified and directed by Engr-in-Charge. |
| 119 | S & F MCCB of rating 125 Amp to 160A ,35kA topanel boardand taking outof old unserviceable MCCB complete all as specified and directed . |
| 120 | S & F MCCB of rating 80 to 100 Amp,35ka topanel boardandtaking outof old unserviceable MCCB complete all as specified and directed . |
| 121 | S & F MCCB of rating 40A to63 Amp,topanel boardandtaking outof old unserviceable MCCB complete all as specified and directed . |
| 122 | Supply and fixing in replacement of MCBTPN 63 Amp, 4 pole with rupturing capacity 10 KA C curve complete all as specified and directed . |
| 123 | Supply and fixing in replacement of MCB 32Amp, 4 pole withrupturing capacity10 KA C curvecomplete all as specified and directed . |
| 124 | S & F in replacement of 3 pole power contactor heavy duty with contineous current rating of upto 25 Amp AC 3, 415 Volt complete all as specified and directed . |
| 125 | S & F in replacement of 3 pole power contactor heavy duty with contineous current rating of upto 32 Amp AC 3, 415 Volt complete all as specified and directed . |
| 126 | S & F in replacement of 3 pole power contactor heavy duty with contineous current rating of 40 to 70 Amp AC 3, 415 Volt complete all as specified and directed . |
| 127 | S & F in replacement of thermalover load relay 20 to 32 Amp,415 Volt complete all as specified and directed . |
| 128 | S & F in replacement of thermalover load relay 10 to 16 Amp, /415 Volt complete all as specified and directed . |
| 129 | S & F in replacement of thermalover load relay 2.5 to 4 Amp, / 415 Volt complete all as specified and directed . |
| 130 | Supply and replacing single phase preventor suitable forsubmersible mud pump sets complete all as specified and directed . |
| 131 | M & L for taking down induction motor 3 phase, 415 Volt capacity 2/3 HP, incoming disconnection electric connections, dismantling slots and rewinding the motor with super enameled copper wire as per existing size including insulating material and varnishing, replacing worn out bearing as per existing size, painting with super enameled paint as per colour coat assembling the motor after rewinding and mounting at its ownposition, replacing the old nut,bolts and testing complete all as specified and directed by Engr-in-Charge. |
| 132 | M & L for taking down induction motor 3 phase, 415 Volt capacity5 HP, incoming disconnection electric connections, dismantling slots and rewinding the motor with super enameled copper wire as per existing size including insulating material and varnishing, replacing worn out bearing as per existing size, painting with super enameled paint as per colour coat assembling the motor after rewinding and mounting at its ownposition, replacing the old nut,bolts and testing all as directed. |
| 133 | M & L for taking down induction motor 3 phase, 415 Volt capacity 7.5 HP to 12.5 HP, incoming disconnection electric connections, dismantling slots and rewinding the motor with super enameled copper wire as per existing size including insulating material and varnishing, replacing worn out bearing as per existing size, painting with super enameled paint as per colour coat assembling the motor after rewinding and mounting at its ownposition, replacing the old nut,bolts and testing all as directed. |
| 134 | M & L for taking up and Repairs to open well type submersible mud /non clog motor of electric driven of any type make and capacity upto 5 HP incl rewinding of the motor with same gauge and weightof suoer enameled copper conductor incl renewal of thrust plate, reassembling, testing and commissioningcomplete all as specified and directed . |
| 135 | M & L for taking up and Repairs to open well type submersible mud/non clog motor of electric driven of any type make and capacity 7.5 HP to12.5 HP incl rewinding of the motor with same gauge and weightof super enameled copper conductor incl renewal of thrust plate, reassembling, testing and commissioning complete all as specified and directed . |
| 136 | Supply and fix of spares for pumps of up to capacity up to 5 hp, Including all the spares i.e impeller,shaft replacement and macining work of shaft,balancing of rotor, oil seal ,bearing,replacing of lubcricant oil etc complete all as specified and directed . |
| 137 | Supply and fixing ofspares for pumps of up to capacity 7.5HP to12.5 HP, Including all the spares i.e impeller,shaft replacement and macining work of shaft,balancing of rotor, oil seal ,bearing,replacing of lubcricant oil etc complete all as specified and directed . |
| 138 | Surface excavation n.exc (not exceeding) 30 cm deep and averaging 15 cm deep and getting out in soft / loose soil for cleaning surface area and cutting shurbes/grass & bushes and remove the material at various installation at site. all as directed by Engr-in-charge. |
| 139 | M & L forSurfaces painting of I STP plant of various capacity (1600 KLD,600KLD,165KLD,190KLD) and equipments including preparing of all surface any description by scrapping old paint and white wash of various tanks over width or girth,colour coding as discribe by Engineer in charge |
| 140 | M& L forspraying ofglyphosate 41% SL Glykol Herbicide to remove vegatation from E/M Installations complete all as specified and directed . |
| 141 | Supply specified acclimated BIO CULTURE of microbial culture of enzymatically breaking down of a broad range of organic compound,phosphate and ammonical nitrogen in sewage and waste water, used in reduction of BOD ,COD,Ammonical nitrogen and phosphorus and eliminating of foam,odour in waste water for used in Aeration tank of STP (MBBR/MBR/SBR/ASP),purity 99.99% powder form having shelf life of 24 months complete all as specified and directed . |
| 142 | Supply and fix in replacement of submercible rubber PVC 2.5 Sqmm, 8 core copper cable HR 120 deg C, 1100 volts conforming IS 694:1990 complete all as specified and directed by Engr-in-Charge . Make: HAVELLS/RR Kabel/Polycab. |
| 143 | Supply only Calcium Hypo Chlorite 65%chlorine content (Calcium based granular)complete all as specified and directed . |
| 144 | Taking down old unserviceable existing flood lights fitting and S&F (in Replacement) energy saving and environmental frindlylong life exclusive innovative flood ight luminaries 70 W 230 V AC outdoor type with thermal management in multiple optics and equipped with IP-66 protection, with impact and corrosion resistant with LEDs as light source and lens embedded PC cover/toughened glass and impact resistance of IK07 and electronic driver fixed on high mast pole or any other place as required on site incl making all necessary arrangement for fixing complete with MS flat iron clamps (clamp shall be 40x50 mm MS flat), nuts and bolts and washers complete all as specified |
| 145 | All as above item Ser No 102 but 170/180 Wcomplete all as specified and directed. |
| 146 | All as above item Ser No 102 but300 Wcomplete all as specified and directed. |
| 147 | Taking down old unserviceable existing street light fitting and S&F (in Replacement) energy saving and environmental frindlylong life LED light fitting, 35 W 230 V outdoor type with high pressure die cast aluminum housing and heatresistant complete with impact and corrosion resistant including thermal management in multiple optics IP 65/IP66 road way luminaries with LEDs as light source and lens embedded PC cover/toughened glass and impact resistanceof IK07 and electronic driver fixed on pole with and including suitable dia size bracket as per manufacturer recommendation, bracket 1.5 m long complete with MS flat iron clamps (clamp shall be 40x50 mm MS flat), nuts and bolts and washers painting the clamps with coat of aluminum paint over a coat of red oxide primer including connection complete all as specified and directed . |
| 148 | All as above item Ser No 105 but 70 Wcomplete all as specified and directed. |