| 1 | Supply and fixing of Microprocessor based multi-loop , true peer-to-peer networkable adressable fire alarm control panel with minimum 80 character LCD display, 4000 event plus alarm log history events, QWERTY keypad for programming . The panel should be equiped with sufficient numbers of loops considering 20% spare capacity in each loop . Each loop shall have a capacity of minimum 300 analog addressable devices . The panel shall work in degrade mode in case of CPU failure. Four access levels , flash EPROM, 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and 30 mins in alarm condition . Designed to meet UL864, 10th edition & FM approved including 8 multicriteria detector , MCP-4 Nos , hooter strobe 4 nos complete all as specified and directed . |
| 2 | Supply and fix GSM auto dialer unit for communication purposesuitable for fire alarm panelcomplete all as specified and directed. |
| 3 | Supply and fix sealed probe type heat detector with PESO approved expulsion proof enclosure 65 degree celsius temperature setting including monitor module complete all as specified and as directed . |
| 4 | Supply and fix addressable manual call point break glass type , flame proof , weather proof suitable class IIA/IIB application , PESO approved including mointor module and all other required mounting accessories complete all as specified and as directed . |
| 5 | Supply and fixing conventional flame proof , weather proof minimum 90DB sounder with strobe suitable for class IIA/IIB lication , PESO approved including monitor module and all other required mounting accessories complete all as specified and as directed . |
| 6 | Supply & fix addressable control/relay module ,Module shall provide supervised NAC output rated at 24V DC , 2A or potential free contact . Device shall have an LED which shall blink in normal state & get steady on activation to monitor the health status of the devices and adressing shall be with user friendly rotary decimal switches complete all as specified and as directed . |
| 7 | Supply & fix addressable monitor module for sprinklers, panic inputs bars& other third party inputs. The monitor module shall monitor potential free contacts and the device shall have an LED which shallblink in normal state & get steady on activation to monitor the health status of the devicesand adressing shall be with user friendly rotary decimal switchscomplete all as specified and as directed . |
| 8 | Supply and fix Isolators module for isolating short/dewired/loose circuits with automatic resetting arrangement,with provision ofisolators base . The device shall be have an LED which shall blinkin normal state & get steady on activation to monitor the health status of the device and module shall be supplied with mounting plate from OEM for ease of Installation and maintenancecomplete all as specified and as directed . |
| 9 | Supply and fix Flameproof outdoor horizontal double mounting three phase 400/440 V , 2800 RPM 50 Cycle per seconds flame proof motorised siren 3.5 KM range along with control panel complete all as specified and as directed . |
| 10 | Supply and fix multi spectrum (UV/IR) fire and flame detector with pneumatic cleaning complete with the following accessories and specifications :-(a) Mounting accessories included(b) Operating Voltage- 24 Vdc nominal (18-32 Vdc) regulated(c) Communication RS-485 , Modbus protocol(d) Enclosure type 4X, IP66 and NEMA 4(e) Enclosure Materials - Copper free powder coated Aluminium (f) CERTIFICATIONS : ATEX/IECEx : II 2 Ex db IIC T4 (Ta : -40 to +100 degree celsius) , II 2 D Ex tb IIIC T135 degree celsius /PESO /ISI/ UL(g) SENSITIVITY : Switch Selectable - Very high (60m) , high (45m) , medium (30m) and low (15m) (h) RESPONSE TIME : 3-5 seconds to 0.1 sqm (1 sqft) n-heptane fire at 30 m (100ft) , 3-10 seconds to 0.1 sqm (1 sqft) n-heptane fire at 60 m (200m)(k) SPECTRAL SENSITIVITY : Ultraviolet 185-260 nanometres(l) With Canopy : Near Band IR: 0.7 - 1.1 microns and Wide Band IR: 1.1-3.5 microns |
| 11 | Supply and fixing 1.5 Sqmm , 2 core FRLS rated armoured cable including all necessary fixing accessories for the FAS loop cable , red colour complete all as specified and as directed . |
| 12 | Supply and install UPS 1KVA for fire alarm control panel complete all as specified and as directed . |
| 13 | Labour only for connecting ,testing and commissioning all spares of fire alram system including submission of layout plan of fire alram system of entire Refuelling sectionby deploying One Service Engineer, One Electrician and two helper complete all as specified and as directed .Note : (i) For Item Srl No. 1 to 13 , all items to be executed through OEM or OEM certified agencies as approved by GE and as per OEM recommendation and OEM authorisation certificate to be submited to the dept before commencement of work .(ii) Complete layout plan for installation of fire alarm system is to be submited to the dept as mentioned in Item srl 13 . |