| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.(Group-B) |
| 2 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. (2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire) |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. (2 X 4 sq. mm + 1 X 4 sq. mm earth wire) |
| 4 | Supplying and fixing of following sizes of medium class PVC Conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (50 mm) |
| 5 | Supplying and fixing6 Module (200mmX75mm)GI box alongwith modular base & cover plate for modular switches in recess etc as required. |
| 6 | Supplying and fixing8 Module (125mmX125mm)GI box alongwith modular base & cover plate for modular switches in recess etc as required. |
| 7 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 8 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 9 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 10 | Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required. |
| 11 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) (16 way , Double door) |
| 12 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Single pole) |
| 13 | Supplying and fixing 40amp rating, four pole, 415 V, isolatorin the existing MCB DB complete with connections, testing andcommissioning etc. as required. |
| 14 | Supplying and fixing 40Amp rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 15 | Supplying, Installation, testing & Commissioning of4\"long 20 watt LED batten (make Havells-Lumeline- LUMILINEBS20W LED865SPCWH)/ similar model of Crompton/ Philips / Havells/ SYSKA /Wipro) directly on ceilling / wall including connection with 1.5 sq mm FRLS PVC insulated copper conductor single core cable, earthing etc. as required. |
| 16 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor(Make: Havells-Efficiencia Neo (BLDC 26 W) or equivalent model of Usha/CG/etc) class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 17 | Supplying, Installation, testing & Commissioning of60 Watt rating LED street light luminaire, out door type with pressure die cast aluminium housing with heat resistant glass, IP66 protection, suitable for single phase, 50 Hz AC (MAKE crompton-ORION NEO Model-LST-60-CDLM), including connection with 1.5 sq mm FRLS PVC insulated copper conductor single core cable, earthing, Supplying and fixing of 32 mm dia X 0.50 metres long G.I. pipe (medium class) bracket for mounting of LED street light fitting directly on wall, bending the pipe to the required shape, 2 nos suitable size flat iron clamps with nuts, bolts and washer etc. as required. |
| 18 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 19 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. |
| 20 | Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required. |
| 21 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) |
| 22 | Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required. |
| 23 | Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required. |
| 24 | Supplying and Laying of aluminium conductor, XLPE Insulated, PVC Innersheathed, armoured power cable of 1.1 KV grade of 3.5×70 sq. mmsize direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering.(Make Havells/Polycab/Universal/CCI/ Plaza/RRKable) |
| 25 | Fabrication, Supplying , Installation, Testing and commissioning of out door type, double door totally enclosed weather proof feeder pillar with sloping canopy top of suitable size (minimum size 1200mm x 1500mm x 450mm) to accommodate following switchgears and accessories, fabricated from 3 mm thick CRCA/ MS sheet suitable for 415/500 volts, 50 Hz A.C. supply with gland plate, hinged front openable double leaf doors and locking arrangement, suitable size 100 amps TPN Aluminium busbar including providing and fixing followingswitchgears and accessories, treated with 7 tank process, powderpainted with approved shade, including connection / interconnections with FRLS PVC insulated copper conductor single core cable of suitable sizeetc. complete as required.The feeder pillar shall be supplied with suitable pedestal of 50mm x 50 mm x 6 mm angle iron frame with 600 mm long legs . The feeder pillar shall be mounted on suitable brick / cement concrete foundation 30 cms. below ground level and 30 cms. above ground including finishing etc. complete as required. (drawing of the panel shall be approved by the Deptt.). 1) Fabrication of Feeder pillar size 1200mm x 1500mm x 450mm FP made of 3 mm thick MS sheet i/c welding,painting,locking arrangement with Alluminume bus bar. 2) 100 amps,TP, 415 V, 16 KA, MCCB, C&S/HPL/Havells/L&T -04 Nos. 3)32 Amp ,MCB DP 10 KA, C series, C&S/HPL/Havells/L&T -02 Nos . 4)10 Amp ,MCB SP 10 KA, C series, C&S/HPL/Havells/L&T -02 Nos .5)20 Amp ,MCB SP 10 KA, C series, C&S/HPL/Havells/L&T -02 Nos.6)6.0 sqmm FRLS copper conductor wire (RR /Polycab/Havells) |
| 26 | SITC of 4.5 Kg CO2 type fire extingusher made from seamless cylinder conforming to IS:7285 ISI marked controlled valve, discharge adaptor with 1 mtrs hose and PVC bend horn complete with initial gas charged with charing handle and wall mounting bracket suitable for operating between -30° C to +55° C, complete in all respect. |
| 27 | Supplying and Laying of aluminium conductor, XLPE Insulated, PVC Innersheathed, armoured power cable of 1.1 KV grade of 3.5×35 sq. mmsize direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering.(Make Havells/Polycab/Universal/CCI/ Plaza/RRKable) |
| 28 | Supplying & Fixing of Onload Changeover Switch - 125 Amp 4 Pole(on SS Enclosure) , 415V AC, 50 Hz on exisiting wall. Havells Euroload make cat No IHCNFE0125/ C& S/HPL socomec make including connection etc. as required. |