| 1 | Works Details |
| 2 | [23.1.6.1]COPPER WIRING IN MS CONDUIT (SURFACE/RECESS) 6.1. Wiring main ,sub mains and Circuit wiring in twosingle core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in MS Conduit etc as required. 1 run of Size 1.50 Sqmm(1/1.40mm) [Through Rate] |
| 3 | [23.1.6.2]COPPER WIRING IN MS CONDUIT (SURFACE/RECESS) 6.2. Wiring main ,sub mains and Circuit wiring in twosingle core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in MS Conduit etc as required. 1 run of Size 2.50 Sqmm(1.1.80mm) [Through Rate] |
| 4 | [23.1.6.3]COPPER WIRING IN MS CONDUIT (SURFACE/RECESS) 6.3. Wiring main ,sub mains and Circuit wiring in twosingle core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in MS Conduit etc as required. 1 run of Size 4 Sqmm(1/2.24mm) [Through Rate] |
| 5 | [23.1.6.4]COPPER WIRING IN MS CONDUIT (SURFACE/RECESS) 6.4. Wiring main ,sub mains and Circuit wiring in twosingle core for phase and neutral wire and one single core for earth wire PVC insulated Copper conductor cable 1100 Volts grade in MS Conduit etc as required. 1 run of Size 6 Sqmm(1/2.80mm) [Through Rate] |
| 6 | [23.11]Making suitable hole in the wall suitable for exhaust fan up to 450 mm sweep including finishing the same and fixing of Stainless steel wire mesh 2 mm thick having about 50 meshes per inch at exhaust sidecomplete as required [Through Rate] |
| 7 | [23.12]Providing and fixing outdoor duty Ply of 12 mm thick frame suitable for exhaust fan up to 450 mm sweep etc complete as required [Through Rate] |
| 8 | [23.2.1.2]COPPER WIRING WITH MODULAR SWITCHES IN MS CONDUITS (SURFACE/RECESS) 1.2. Wiring for Light/Fan/call bell point with modular type switch/socket and GI box, Modular type face plate etcin 1.5 sqmm FRLS PVC insulated copper conductor cable in 1.6 mm thick MS conduit pipe. Group B [Through Rate] |
| 9 | [23.2.2.2]COPPER WIRING WITH MODULAR SWITCHES IN MS CONDUITS (SURFACE/RECESS) 2.2. Wiring for Twin control light point with 2 nos , 2-ways, 5 amp. Modular switch GI box and modular face platein 1.5 sqmm FRLS PVC insulated copper conductor cable in 1.6 mm thick MS conduit pipe. Group B [Through Rate] |
| 10 | [23.2.3.2]COPPER WIRING WITH MODULAR SWITCHES IN MS CONDUITS (SURFACE/RECESS) 3.2. Wiring for Light/Fan/call bell point in 1.5 sqmm FRLS PVC insulated copper conductor cable in 1.6 mm thick MS conduit pipe, without separate control switch , Modular type Switch/sockets wiring Group B [Through Rate] |
| 11 | [23.2.4.2]COPPER WIRING WITH MODULAR SWITCHES IN MS CONDUITS (SURFACE/RECESS) 4.2. Wiring in MS conduit system for 3-pin 5amp. Plug point by using 2 no 1.5 sqmm FRLS copper wire and 1 no 1.5 Sqmm FRLS copper wire , including providing 1 no 5/6 Amp 3/5 pin Modular type socket and 1 no 5/6 Amp Modular type switch required GI Box ,modular face plate etc complete as required Group B [Through Rate] |
| 12 | [23.2.5.2]COPPER WIRING WITH MODULAR SWITCHES IN MS CONDUITS (SURFACE/RECESS) 5.2. Wiring in MS conduit system for 3-pin 15amp. Plug point by using 2 no 4 sqmm FRLS copper wire and 1 no 4 Sqmm FRLS copper wire for earthling , including providing 1 no 15/16 Amp 3/6 pin Modular socket and 1 no 15/16 Amp Modular switch required GI Box , modular face plate etc complete as required Group B [Through Rate] |
| 13 | [23.20]Fixing of LED Tube light/ 2*2 ft square panel fitting directly on wall /ceiling or false ceiling including making connections etc as required [Through Rate] |
| 14 | [23.21]Fixing of LED Down lighter 7 to 28 Watt on ceiling or in false ceiling , including cutting/making hole in ceiling including making connections etc as required [Through Rate] |
| 15 | [23.22.4.7]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 4.7. Supply and erection of double door sheet steel enclosure distribution board suitable for MCBS and ELCBS etc. recessed in wall including bonding to earth with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-Charge of the work. TPN DBHorizontal type Double Door 8 way ( 8 incoming 3phase*8 outgoing) [Through Rate] |
| 16 | [23.22.4.8]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 4.8. Supply and erection of double door sheet steel enclosure distribution board suitable for MCBS and ELCBS etc. recessed in wall including bonding to earth with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-Charge of the work. TPN DBHorizontal type Double Door 12 way ( 8 incoming 3phase*12 outgoing) [Through Rate] |
| 17 | [23.22.5.1]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 5.1. Supply and erection of miniature circuit Breaker240/415 V in the existing distribution board including making necessary connections:- 6 amp. to 32 amp Single Pole [Through Rate] |
| 18 | [23.22.5.8]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 5.8. Supply and erection of miniature circuit Breaker240/415 V in the existing distribution board including making necessary connections:- 40 amp to 63 amp. MCBs FOUR POLE [Through Rate] |
| 19 | [23.22.6.2]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 6.2. Supply and erection double pole/Four pole Residual (RCCB/ELCB) on 240/415V, 5Hz. AC supply installed in existing sheet steel enclosures including making necessary connections and bonding to earth with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-Charge of the work. DP RCCB 30ma sensitivity , 40 A [Through Rate] |
| 20 | [23.22.6.3]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 6.3. Supply and erection double pole/Four pole Residual (RCCB/ELCB) on 240/415V, 5Hz. AC supply installed in existing sheet steel enclosures including making necessary connections and bonding to earth with all labour and material required to complete the job in all respect up to the entire satisfaction of the Engineer-in-Charge of the work. DP RCCB 30ma sensitivity , 63 A [Through Rate] |
| 21 | [23.22.7]MCCB ,DISTRIBUTION BOARDS, MCB`s, RCCB`s, CHANGE OVER etc. 7. Supply and erection of blanking sheet in existing distribution board. [Through Rate] |
| 22 | [23.23.2.2]MISCELLANEOUS 2.2. Supply of GI pipe (B-Class) for suspension rod of ceiling fan including threading if required. 20 mm dia [Through Rate] |
| 23 | [23.23.5.4]MISCELLANEOUS 5.4. Supply and erection of U- PVC Trunking/Channel of following size including cost of fixing on wall, floor and ceiling etc. with required material complete the job in all respectup to entire satisfaction of the Engineer-in-charge of work. 50x50 mm [Through Rate] |
| 24 | [23.23.8.1]MISCELLANEOUS 8.1. Supply and laying of multicore telephone cable conductor size 0.51 mm bright annealed copper conductor PVC insulated and sealed in existing pipe/channel and making necessary connection complete in all respect up to the entire satisfaction of the Engineer-in charge of the work. 2 pair telephone wire [Through Rate] |
| 25 | [23.23.9]MISCELLANEOUS 9. Supplying and drawing of 1 no UTP 4 pair CAT 6 LAN Cable in the existing surface/recess MS/PVC conduit as required [Through Rate] |
| 26 | [23.6.6.1]MS CONDUIT PIPE ONLY (SURFACE OR RECESSED) FOR ELECTRICAL POINTS 6.1. Supply and erection of MS conduit pipe 1.6 mm thick , ISI marked surface/recessed in slab/wall/ceiling etc. including cost of MS bends, inspection box and all other material required to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work. MS Pipe of 20 mm dia. [Through Rate] |
| 27 | [23.6.6.2]MS CONDUIT PIPE ONLY (SURFACE OR RECESSED) FOR ELECTRICAL POINTS 6.2. Supply and erection of MS conduit pipe 1.6 mm thick , ISI marked surface/recessed in slab/wall/ceiling etc. including cost of MS bends, inspection box and all other material required to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work. MS pipe of 25 mm dia. [Through Rate] |
| 28 | [23.7.6.1]PVC CONDUIT PIPE ONLY (SURFACE OR RECESSED) FOR ELECTRICAL POINTS 6.1. Supply and erection of PVC CONDUIT ISI marked (Medium) recessed in wall/ceiling etc. including the cost of PVC bends, inspection boxes, iron hooks and cement concrete etc. complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. PVC pipe of 20 mm dia. [Through Rate] |
| 29 | [23.7.6.2]PVC CONDUIT PIPE ONLY (SURFACE OR RECESSED) FOR ELECTRICAL POINTS 6.2. Supply and erection of PVC CONDUIT ISI marked (Medium) recessed in wall/ceiling etc. including the cost of PVC bends, inspection boxes, iron hooks and cement concrete etc. complete in all respect up to the entire satisfaction of Engineer-in-Charge of work. PVC pipe of 25 mm dia. [Through Rate] |
| 30 | [23.8.10.1]FITTING AND ACCESSORIES 10.1. Providing and fixing GI concealed sheet metal boxes with inner and outer face plate including concealing the box in wall and fixing in position with inner plate and face plate with all labour and material required for the job complete in all respects. 1 & 2 Modules including combined plate for Telephone and data [Through Rate] |
| 31 | [23.8.11.10]FITTING AND ACCESSORIES 11.10. Providing and fixing modular type accessories of approved make in existing box including fixing and making necessary connections, complete in all respect. Blanking plate [Through Rate] |
| 32 | [23.8.11.11]FITTING AND ACCESSORIES 11.11. Providing and fixing modular type accessories of approved make in existing box including fixing and making necessary connections, complete in all respect. RJ 45 Computer DATA socketoutlet for CAT 6 or CAT6e cable Modular type [Through Rate] |
| 33 | [23.8.11.6]FITTING AND ACCESSORIES 11.6. Providing and fixing modular type accessories of approved make in existing box including fixing and making necessary connections, complete in all respect. Bell Push [Through Rate] |
| 34 | [23.8.11.7]FITTING AND ACCESSORIES 11.7. Providing and fixing modular type accessories of approved make in existing box including fixing and making necessary connections, complete in all respect. step type Fan Regulator 2 modules 300 watt [Through Rate] |
| 35 | [23.8.11.8]FITTING AND ACCESSORIES 11.8. Providing and fixing modular type accessories of approved make in existing box including fixing and making necessary connections, complete in all respect. Telephone Socket outlet modular type [Through Rate] |
| 36 | [23.8.11.9]FITTING AND ACCESSORIES 11.9. Providing and fixing modular type accessories of approved make in existing box including fixing and making necessary connections, complete in all respect. T.V. Socket outlet modular type [Through Rate] |
| 37 | [23.8.4]FITTING AND ACCESSORIES 4. Supply and erection of 10.5 cm dia M.S.Fan box including 8 mm dia 30 cm long M.S. Road made into suitable suspension hook and erected in R.C.C. slab for the erection of fan complete with all labour and material required to complete the job. [Through Rate] |
| 38 | [23.9]Erection of exhaust fan in existing opening ,complete with necessary earthling of fan including carriage from PWD store to the site of work. [Through Rate] |
| 39 | [24.1.1]EARTHING AND LIGHTENING ARRESTOR 1. Earthing with GL earth pipe 4.5 m long and 40 mm dia with masonry enclosures on the top etc. (but without charcoal or coke and salt) as required. [Through Rate] |
| 40 | [24.1.13]EARTHING AND LIGHTENING ARRESTOR 13. Providing and fixing 4.00 mm dia G1. Wire on surface or in recess for loop earthing as required. [Through Rate] |
| 41 | [24.1.2]EARTHING AND LIGHTENING ARRESTOR 2. Extra for using salt and char coal/coke for pipe earth electrode as required. [Through Rate] |
| 42 | [24.1.3]EARTHING AND LIGHTENING ARRESTOR 3. Earthing with G.I. earth plate 600 mmx 600 mm x 6 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt) complete as required. [Through Rate] |
| 43 | [24.1.5]EARTHING AND LIGHTENING ARRESTOR 5. Extra for charcoal or coke and salt for G.I. plate or copper plate earth electrode. [Through Rate] |
| 44 | [24.1.7]EARTHING AND LIGHTENING ARRESTOR 7. Supplying and laying 25mm x 3 mm G.I. strip in 40 mm dia,GI pipe as/from earth electrode including soldering etc. as required. [Through Rate] |
| 45 | [24.1.8]EARTHING AND LIGHTENING ARRESTOR 8. Providing and fixing 25 mm x 3mm G.I. strip on surface or in recess for connections etc. as required with all labour and material. [Through Rate] |
| 46 | Supplying and drawing co-axial TV cable RG-6 grade, 0.7mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC Sheath in the existing surface / recessed steel / PVC Conduit as required. |
| 47 | Suppling and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2Nos. 3 pin 5/6A modular socket outlet and 2Nos. 5/6A modular swtich, connections etc. as required. |
| 48 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess,including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB , `C` curve including connections, painting etc. as required. |