Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 07-04-2025 | Notice about opening bids | Other | 09-04-2025 |
| 2 | 07-04-2025 | Amendment to scope of work. | Other | 09-04-2025 |
| 3 | 05-04-2025 | Electrical and FPS Query Response | Other | 09-04-2025 |
| 4 | 01-04-2025 | Pre Bid Meeting Online Link | Other | 09-04-2025 |
| Sl. No. | Item Description |
| 1 | CIVIL AND STRUCTURALWORKSINCLUDING EXTERNAL WORKS |
| 2 | 2.6.1Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.All kinds of soil |
| 3 | 2.26.1 Extra for every additional lift 1.5 m or part there of in excavation / banking excavated or stacked materials.All kinds of soil 1.5 to 3m |
| 4 | 3 to 4.5 m |
| 5 | 2.25 Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m. |
| 6 | 4.12 Providing , laying spreading and compacting graded stone aggregate ( size range 53 mm to 0.075 mm) to wet mix macadam (WMM) specification including premixing the material with water at OMC in mechanical mix plant, carriage of mixed material by tipper to site, for all leads & lifts, laying in uniform layers with mechanical paver finisher in sub - base / base course on well prepared surface and compacting with vibratory roller of 8 to 10 tonne capacity to achieve the desired density, complete as per specifications and directions of Engineer - in- Charge. |
| 7 | ODProviding pre construction anti termite treatment for new buildings: Providing, applying and Injecting for pre construction anti termite treatment to wall trenches bottom of excavation, foundations, vertical walls, top surface of plinth filling wall and floor junctions, joints, conduits and external perimeter of the building (IS 8944 Chloripyrifos E.C./ IS 632 Lindane E.C.)with a hand operator pressure pump at applicable areas as per site condition in various stages as per IS: 6313-2003 (Par-II), the plinth area of the building ( slab area outer to outer of walls for Cellars ) shall be taken for purpose of payment and finished item including all costs, conveyances etc. complete as per Technical Specification, drawings and as directed by Client or Engineer in charge.NOTE: 1. Contractor to provide Safety data sheet (SDS), Manufacturer and Registered vendor warranty certificate.2.IS Codal Reference IS 6313(Part1):2013 for Anti-Termite Measures in Buildings-Constructional Measures (Reaffirmed 2020)and , IS 6313(Part2):2013 Anti-Termite Measures in Buildings- Pre constructional Chemical Treatment Measures (Reaffirmed 2018).3.The contractor has to furnish the guarantee for 10 (ten) years from the date of completion of work, stating that in case of reappearance of termites within the building area due to defective materials or workmanship or due to any other reasons, the contractor will carry out the necessary post constructional treatment to keep the entire area free from termite, once again, without any extra cost to the Owner during the guarantee period. |
| 8 | 4.1.8Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size) |
| 9 | 5.33.1Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is payable or recoverable separately.All work upto plinth level |
| 10 | 5.33.2Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is payable or recoverable separately.All work above plinth level upto floor V level |
| 11 | 5.34.1Extra for providing richer mixes at all floor levels. Note:- Excess/less cement over the specified cement content used is payable/ recoverable separately.Providing M-30 grade concrete instead of M-25 grade BMC/RMC. (Note:- Cement content considered in M-30 is @ 340 kg/cum). |
| 12 | 5.22.6Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete below plinth level.Thermo-MechanicallyTreated barsofgrade Fe-500D or more |
| 13 | 5.22A.6Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete above plinth level.Thermo - Mechanically Treated bars of grade Fe-500D or more |
| 14 | 5.9.1Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete |
| 15 | 5.9.6Centering and shuttering including strutting, etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts |
| 16 | 5.9.5Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers |
| 17 | 5.9.3Centering and shuttering including strutting, etc. and removal of form for:Suspended floors, roofs, landings, balconies and access platform |
| 18 | 5.9.7Centering and shuttering including strutting, etc. and removal of form for:Stairs, (excluding landings ) except spiral - staircases) |
| 19 | 5.9.2Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. |
| 20 | OD Grouting (under the base plates/shoe plates including grouting of sleeves and pockets) shall be done with non-shrink grout having compressive strength (28 days) not less than 40 N/sq.mm non shrink grout shall be of free flow premix type and of approved quality and make. It shall be mixed with water in proportion as specified by the manufacturer. Ordinary 1:2 cement/sand mortar grout shall be used . The thickness of grout shall be as shown on the drawings but not less than 25 mm nor more than 40 mm in any case etc., complete as per technical specification, drawings as directed by client or Engineer in charge. |
| 21 | 10.16.1Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete.Hot finished welded type tubes |
| 22 | 13.61.1Painting with synthetic enamel paint of approved brand and manufacture to give an even shade:Two or more coats on new work |
| 23 | OD Providing and fixing 250x250mmplain G.S. sheet gutter of 0.5mm thick ,with iron brackets 40x3 mm size, bolts, nuts and washers etc., including making necessary connections wit rain water pipes etc., complete as per technical specification , drawings and as directed by Client or Engineer In charge.Note :- 0.80 mm thick with zinc coating not less than 275 gm/m2 |
| 24 | OD Supply and installation of 25mm thick Joint Filler Board shall be pre-moulded, high performance joint filler board. should have closed cell and of cross-linked structure. It needs to possess excellent recovery of 95% (after compression up to 50%). It should be an exclusive product specially designed to be used as expansion joint filler in concrete, brick, block work and isolation joints. It should be rot free and it should not contain bitumen, gap shall be provided with backer rod and polysulphide sealant etc., completeas per Technical Specification, Drawings and as directed by client / Engineer In charge.Note Following Properties should be mandatory.Density, kg/m3 -100.00 Service Temperature, °C- 40 to 70 Recovery after compression (up to 50%), % -95 Chemical Resistance - Very Good Water Absorption, % - 1 – 1.5 |
| 25 | OD Supply and Fabrication of ISA 65x65x6mm angles with Anchor lugs where ever necessary at expansion joints etc., complete as per technical specifications, drawings and as directed by client / Engineer in charge. |
| 26 | OD Supply and Installation of R25 Dowel bars @ 300mm c/c along expansion joint , Bars to be provided with PVC pipe 40dia 375 leg filled with compressible fillers etc., complete as per technical specifications, drawings and as directed by Client or Engineer in charge. |
| 27 | OD Providing Saw cut groove of size 35x5mm for gradeslab and filled with approved joint sealant |
| 28 | OD Proving Construction joint as required by installing R25 dowel bars of 800mm length @ 300mm c/c etc., complete as per technical specifications, drawings and as directed by client or Engineer In charge. |
| 29 | 50.6.7.2Laterate masonry with neatly dressed laterate stone of size 40x20x15cm or nearest size in cement mortar 1:6 for super structure above plinth level up to floor two level including all cost of materials, labour charges etc. |
| 30 | OD Laterate masonry with neatly dressed laterate stone of size 40x20x15cm or nearest size in cement mortar 1:6 for super structure above plinth level up to floor two level including all cost of materials, labour charges etc. (Laterate shall be cut from the site premises and the same shall be neatly dressed tomeet the exact size required as directed by the Engineer in Charge ) |
| 31 | 22.23.2Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI-212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineerin- charge. The product performance shall carry guarantee for 10 years against any leakage.For horizontal surface one coat @1.10 kg per sqm. |
| 32 | 22.5Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/sqm. This layer will be allowed to air cure for 4 hours. b) Second layer of slurry of cement @ 0.242 kg /sqm mixed with water proofing cement compound @ 0.126 kg/ sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry. |
| 33 | 22.23.1Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservoir, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI-212-3R-2010 i.e. by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineering- charge. The product performance shall carry guarantee for 10 years against any leakage.For vertical surface two coats @0.70 kg per sqm |
| 34 | 4.7.1Providing and fixing up to floor five level precast cement concrete solid block, including hoisting and setting in position with cement mortar 1:3 ( 1 cement : 3 coarse sand), cost of required centering, shuttering complete:1:1.5:3 ( 1 cement : 1.5 coarse sand (Zone III): 3 graded stone aggregate 20 mm nominal size) |
| 35 | 13.1.112 mm cement plaster of mix:1:4 ( 1 cement : 4 fine sand) |
| 36 | 13.2.115 mm cement plaster on the rough side of single or half brick wall of mix:1:4 (1 cement :4 fine sand) |
| 37 | OD Providing, & fixing PVC rungs inside tanks embedded in concrete , Rungs shall be of Heavy duty , size and shape all as per approval, placed at 300mm c/c etc. all complete as per technical specifications, drawings and as directed by Client or Engineer-in-charge.Note : - Size (270x170x25mm) -12mm Rod |
| 38 | OD Providing, Supplying, Loading, Unloading on site Factory made R.C.C Precast drain cover slab, for trench (Inside Dimensions-L x B X H as approved in drawings drawing. The drain shall be of M20 grade concrete including reinforcement Fe500D Grade or HD Wire of IS:432 Part II, OPC 53 Grade Cement. The surface finish shall be smooth finish, with special in built insert, sleeves as per specified in drawing for fixing and lifting, rate shall include mechanical means, loading, transportation at site including all leads, lifts., complete as per technical specification, drawings and as directed by client or Engineer In charge.Note :- Covers shall have MS lift hooks for Easy operations |
| 39 | OD Providing & installation of double panel automatic sliding doors with all the necessary operators, sensors etc. The door shall comprises of frames and side partitions shall be single rebate frame profile of size 125mm x 55mm made out of 1.60mm (16 Gauge) minimum thick galvanized steel sheet. sliding door leaf shall be fully glazed with minimum of 60 x 85 mm profile step box section for taking glass element with minimum 1.2mm (18 Gauge) minimum thick galvanized steel sheet. and door frames shall be with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening including the supports and studs required for mounting the system from top as per design requirement. The Operator unit shall comprises of control unit with adjustable parameters for opening & closing speed, activators, motion safe radar systems, program switch with key etc. The glass shall be fire rated, integrity with light transmission of minimum 92%, all doors and frames shall be finished with pure polyester powder coat. The rate includes cost of all labour, materials, tools & tackles, machineries, transportation, lead, lift, loading, unloading, storage, electricity charges, water charges, protection till handover etc., complete as per specification , drawing, and as per Client / Engineer in charge. |
| 40 | OD Providing & installation of single panel automatic sliding doors with all the necessary operators, sensors etc. The door shall comprises of frames and side partitions shall be single rebate frame profile of size 125mm x 55mm made out of 1.60mm (16 Gauge) minimum thick galvanized steel sheet. sliding door leaf shall be fully glazed with minimum of 60 x 85 mm profile step box section for taking glass element with minimum 1.2mm (18 Gauge) minimum thick galvanized steel sheet. and door frames shall be with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening including the supports and studs required for mounting the system from top as per design requirement. The Operator unit shall comprises of control unit with adjustable parameters for opening & closing speed, activators, motion safe radar systems, program switch with key etc. The glass shall be fire rated, integrity with light transmission of minimum 92%, all doors and frames shall be finished with pure polyester powder coat. The rate includes cost of all labour, materials, tools & tackles, machineries, transportation, lead, lift, loading, unloading, storage, electricity charges, water charges, protection till handover etc., complete as per specification , drawing, and as per Client / Engineer in charge.SD2 - Single panel Sensor Sliding glass door -1200x2400mm |
| 41 | OD supply and installation of 30 mm thick factory-made moulded PVC door (Wood free) with single panel sensor-based operation as per drawing approved by Engineer-in-charge.SD3 - Single panel Sensor Sliding glass door -750x2400mm |
| 42 | 9.20.1Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of I sty class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters.35 mm thick including ISI marked Stainless Steel butt hinges with necessary screwsSingle flush door D2 -1200x2400mm |
| 43 | 9.20.1Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of I sty class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters.35 mm thick including ISI marked Stainless Steel butt hinges with necessary screwsDouble flush door D3 -1800x2400mm |
| 44 | Double flush door D4 -2100x3000mm |
| 45 | OD Providing and fixing Single sliding clear anodized 50mm thick aluminium frame and 12mm thick glass and hardware includes roller, brackets, stoppers, guide running in bottom of the door, upper track, end caps etc. Complete as per drawing, technical specification and a directed by Client/Engineer in charge.SD- 1500x3000mm |
| 46 | OD Providing and fixing Single sliding clear anodized 50mm thick aluminium frame and 12mm thick glass and hardware includes roller, brackets, stoppers, guide running in bottom of the door, upper track, end caps etc. Complete as per drawing, technical specification and a directed by Client/Engineer in charge.SD 4- 1200x2400mm |
| 47 | OD Providing & fixing double leaf glass door mounted over patch fitting. The shutter to be formed out of 12mm thick toughened glass with frosting of approved make. The glass shutter should be polished on the edges. The Shutter should be mounted over top & bottom patch fitting with floor lock patch. Hardware: Floor spring with (SS cover plate ) spindle,bottom patch, top patch, bottom patch lock, floor mounted SS door buffer, Door Handle-SS matt finish 300mm long 2 Nos for each leaf . Door hardware\"s are to be Dorma or any equivalent brandsubject to approval of the same from Client before installation. The rate includes cost of all labour, materials, tools & tackles, machineries, transportation, lead, lift, loading, unloading, storage, electricity charges, water charges, protection till handover etc., complete as per technical specification, drawings, and as per Client / Engineer in charge.GD- 1500x2400 |
| 48 | 9.120.2Providing and fixing factory made panel PVC door shutter with louvers consisting of frame made out of M.S. tubes of 19 gauge thickness and sized of 19 mm x 19 mm for styles and 15x15 mm for top & bottom rails. M.S. frame shall have a coat of steel primers of approved make and manufacture. M.S. frame covered with 5 mm thick heat moulded PVC \"C\" channel of size 30 mm thickness, 70 mm width out of which 50 mm shall be flat and 20 mm shall be tapered in 45 degree angle on both side forming styles and 5mm thick, 95 mm wide PVC sheet out of which75 mm shall be tapered in 45 degree on th inner side to form top and bottom rail and 115 mm wide PVC sheet out of which 75 mm shall be flat and 20 mm shall be tapered on both sides to form lock rail. Top, bottom and lock rails shall be provided both side of the panel. 10 mm (5 mmx2) thick, 20 mm wide cross PVC sheet be provided as gap insert for top rail & bottom rail. panelling of 5 mm thick both side PVC sheet to be fitted in the M.S. frame welded /sealed to the styles & rails with 7 mm (5 mm + 2 mm ) thick x 15 mm wide PVC sheet beading on inner side, and joined together with solvent cement adhesive. An additional 5 mm thick PVC strip of 20 mm width is to be stuck on the interior side of the \"C\" Channel using PVC solvent adhesive30 mm thick pre laminated PVC door shutters, etc. complete as per direction of Engineer -in-charge, manufacture\"s specification & drawing.D1\" - 750x2400mm |
| 49 | OD Providing and fixing double leafpowder coated 120minfire rated metal door with 100x57mm doublerebate frame made of 1.2mm thick GI sheet and infill rockwool insulation having minimum density of 96kg/cum all the hardware materials as below- SS ball bearing hinges- Exposed door closer with STD. Arm- Single point locking panic bar- 6 pin Euro profile half cylinder- Micro switch- SS D type pull handle on pull side only- Half dome door stopper- 1mm thick SS304 Kick plate- Automatic door bottom seal, concealed- 6mm thick 120min Fire rated clear glass-HRD-H Fasteners- Smoke seal in frame- Intumescent fire seal in frame.Etc, complete as per technical specification, drawing and as directed by Client/Engineer In charge. |
| 50 | OD Providing and fixing sliding clear anodized 50mm thick aluminium frame and 12mm thick glass window hardware includes roller, brackets, stoppers, guide running in bottom of the door, upper track, end caps etc. Complete as per drawing, technical specification and a directed by Client/Engineer in charge.W1 -2400x2100mm @ 3m |
| 51 | OD Providing and fixing sliding clear anodized 50mm thick aluminium frame and 12mm thick glass window hardware includes roller, brackets, stoppers, guide running in bottom of the door, upper track, end caps etc. Complete as per drawing, technical specification and a directed by Client/Engineer in charge.W2 - 2400x1500mm@ 2.4m |
| 52 | 9.147B.1Providing and fixing factory made uPVC white colour fixed glazed windows/ventilators comprising of uPVC multi-chambered frame and mullion (where ever required) extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), uPVC extruded glazing beads of appropriate dimension, EPDM gasket, G.I fasteners 100 x 8 mm size for fixing frame to finished wall, plastic packers, plastic caps and necessary stainless steel screws etc. Profile of frame shall be mitred cut and fusion welded at all corners, mullion (if required) shall be also fusion welded including drilling of holes for fixing hardware\"s and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge.Note: For uPVC frame, sash and mullion extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable.Variation in profile dimension in higher side shall be acceptedbut no extra payment on this account shall be made.9.147B.1 Fixed window / ventilator made of (small series) frame 47 x 50 mm & mullion 47 x 68 mm both having wall thickness of 1.9 ± 0.2 mm and single glazing bead of appropriate dimension.(Area up to 0.75 sqm.) V -600mm high |
| 53 | ODProviding and fixing of Hollow metal door at all levels fromISO 9001-2000 certified Manufacturer. The metal doors should be made from high grade galvanised steel stretched level sheet flush, with vision panel, louvers etc. Single /Double leaf to required sizes and approved make shakti met-dor or equivalent which consists of frame, shutter, infill and finish as detailed below and conforming to IS 277. Door frame shall be single rebate profile of size 100 x 57 mm made out of 1.20mm minimum thick galvanized steel sheet (18 gauge ). Frames should be mitered and field assembled with self tabs. Door frames should be prepared for suitable hardware as scheduled and should have necessary reinforcement to withstand regular wear and tear. All provision should be mortised, drilled and tapped for receiving the hardware. Rubber door silencers should be provided on the striking jamb. All door frames should be provided with backplate and anchor fasteners for installation on a finished plastered masonry wall opening. Once the frame is installed it should be grouted with cement & sand slurry.Door leaf should be 46mm thick flush double skin door with vision panel of suitable size. Door leaf shall be manufactured from 0.8mm (22 guage) minimum thick galvanised steel sheet. The internal construction of the door should be rigid with steel stiffeners/ pads and reinforcement. The infill material shall be resin bonded honeycomb core. All doors should be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, shaft locks, flush pull and tower bolt etc. The edges should be interlocked with lock seam. For pair of doors astragals will be provided as required. 450x750mm Vision lite wherever applicable should be of size fixed with rubber beeding. The glass should be 4mm clear toughned glass. All doors and frames shall be finished with polyurethane aliphatic grade powder coating minimum of 50 microns of approved colour. The door leaf and frame shall have passed minimum 500 hours of salt sprey test. Rate should include supply and installation of door and hardware as a complete assembly as mentioned in the door and hardware schedule. Steel Door TD2 Single leaf 900x2100mm with 450x750mm vision panel with frame on Four sides & hardware set . Hinges 3090 F, 5 Knl, 2 Ball bearing butt hinges size 4\" x 3\" x 3mm SS 304. Mortice Shaft Dead lock with Allen key 8681, SSS. Flush Pull Handle 1208, OVAL, SSS |
| 54 | ODProviding & fixing powder coated Aluminium framed louvered glass ventilators , Louvre blades are made of single pane, tempered or partially pre-stressed safety glass in thickness of 6 , 10 or 12 mm ( overall depth for 12mm glass= 60mm ) . The glass edges are polished all around . The upper and lower edges of the louvre blades have a 30deg bevel , frame shall be made of non insulated or insulated extruded aluminium profiles with a frame depth of either 50 or 60 mm. the opening fitting are hidden. The window is opened either using a hand crank handle , an articulated winding shaft , a pneumatic cylinders or an electric servomotor ( 24V DC or 230V AC ) . EPDM seals ensure a tight fit , The profiles are anodised , powder coated or wet paint coated to RAL as approved by Client and Architecture etc complete as per the technical specifications drawings and as directed by client or Engineer in charge. |
| 55 | 13.43.1Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface:Water thinnable cement primer |
| 56 | 13.26Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete. |
| 57 | 13.60.1Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade:Two or more coats on new work |
| 58 | 13.45.1 Finishing walls with textured exterior pint of required shade:New work (Two or more coats applied @ 3.28 ltr/ 10 sqm ) over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm |
| 59 | OD Providing and Installing HPL partition panel for toilet is a structure with a thickness of maximum 18mm, made of 2 x 4 mm thick (sandwich panel of 4mm thick laminate on either sides and insulation in between pressed with high pressure) external HPL panels and internal insulation. The 4 mm thick HPL panel has a transparent finish on both external sides that protects the decorative layer below. Solid, structured, unpainted material (the colour is part of the material). Antistatic and antibacterial given the nature of the product itself, HPL is used extensively in controlled contamination environments.Accessories * SS \"U\" Channel* Aluminium H Section Top Rail with Wall Bracket* SS Coat Hook* SS Privacy Thumb turn c/w Occupancy Indicator.* SS Doorknob* SS Spring Loaded Butt Hinges with Cover* SS Shoe Box Leg 18mm - 316 Grade* Rubber Lining for Groove* S.S. Screws 304 G & P.V.C Wall PlugsComplete as per technical specifications, drawing and as directed by Client/Engineer In charge |
| 60 | OD Providing and fixing Single Glazed Glass partition of minimum 10mm thk. (Or thickness mentioned in detailed drawing) Toughened Glass using Dorma or equivalent approved system to a height as per drawing. The glass to be fixed using anodized / powder coated to detail aluminium Profiles at Top & Bottom size to be 100x25MM to be fixed on to the floor/wall/ ceiling as per the drawing. H Junction profile to be used at all Glass-to-Glass vertical joints, 90 Deg L Junction Profiles and T Junction profiles necessary as per design. Profiles shall be suitable for Glass thickness of 10/12/13. 52mm.The Profile shall be matt natural anodized / powder coated, the Profile Manufacturer to supply all the necessary seals, and fixing accessories for the system.Approved Manufacturer: Profiles/Frames: Dorma or equivalent, Glass: Saint Gobain/Asahi. All the necessary shop drawings/ certificates and other submittals to be approved by Architect prior to execution at site. All exposed edges to be tapered while glass shall be machine polished the rate of glass shall be inclusive of chamfering, cutting of glass, necessary fixing arrangement of approved quality and make, joint filling, octroi, loading - unloading, delivery on site and taxes thereon. etc. The contractor shall be paid for the partition area up to the false ceiling bottom only, however the rate quoted should be inclusive of framework for the partition above false ceiling and up to RC ceiling level. |
| 61 | 9.105.5Providing and fixing 66mm overall thickness partition using 8mm thick double skin multipurpose cement board reinforced with cellulose fibre manufactured through autoclaving process (High pressure steam cured) as per IS : 14862 with suitable fibre cement screws 66 mm overall thickness partition using 8 mm thick double skin multipurpose cement bonded wood particle board manufactured as per IS: 14276 with suitable cement bonded board screws |
| 62 | 9.105.2Providing and fixing partition up to ceiling height consisting of G.I. frame and required board, including providing and fixing of frame work made of special section power pressed/ roll form G.I. sheet with zinc coating of 120 gms/sqm(both side inclusive), consisting of floor and ceiling channel 50mm wide having equal flanges of 32 mm and 0.50 mm thick, fixed to the floor and ceiling at the spacing of 610 mm centre to centre with dash fastener of 12.5 mm dia meter 50 mm length or suitable anchor fastener or metal screws with nylon plugs and the studs 48 mm wide having one flange of 34 mm and other flange 36 mm and 0.50 mm thick fixed vertically within flanges of floor and ceiling channel and placed at a spacing of 610 mm centre to centre by 6 mm dia bolts and nuts, including fixing of studs along both ends of partition fixed flush to wall with suitable anchor fastener or metal screws with nylon plugs at spacing of 450 mm centre to centre, and fixing of boards to both side of frame work by 25 mm long dry wall screws on studs, floor and ceiling channels at the spacing of 300 mm centre to centre. The boards are to be fixed to the frame work with joints staggered to avoid through cracks, Galvanised M.S. fixing channel of 99 mm width (0.9 mm thick having two flanges of 9.5 mm each with zinc coating of 120 gms/sqm(both side inclusive)) to be provided at the horizontal joints of two boards, fixed to the studs using metal to metal flat head screws, including jointing and finishing to a flush finish with recommended jointing compound, jointing tape, angle beads at corners (25 mm x 25 mm x 0.5 mm), joint finisher and two coats of primer suitable for board as per manufacture\"s specification and direction of engineer in charge all complete. |
| 63 | OD Laying and finishing of Anti skid Vitrified flooring 600mmx600mmx12mm thick of approved color and make to pattern overbed of required thickness (to make up required finished floor level)Cement Mortar of 1 : 4 mix including pointing with the matching grout, acid washing, including spacers/joint at required interval etc. complete with all leads and lifts ( work at all levels), including protective layers, removal and cleaning up of debris, waste material after work at the locations agreed. Cost to be inclusive of protection of the laid tile flooring till the handover to client etc. complete as per technical Specification, drawings and as directed by Client/ Engineer in charge.Note:-Supply of Tiles will be under Client scope |
| 64 | 11.26.1 Kota stone slab flooring over 20 mm ( average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1:4 (1 cement : 4 coarse sand)25 mm thick |
| 65 | ODlaying Polished Granite stone flooring 1200x1200mm in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and provided with brass joints both ways with pigment of matching shade including rubbing , curing and polishing Granite stone slab . etc. all complete as specified and as directed by the Engineer-in-Charge.Note :- Brass Joint beading quantity will be measured seperately |
| 66 | ODBRASS JOINT FOR GRANITE FLOORING, Providing and fixing brass joint beading of 2-3mm thick for flooring ( granite floor ) and neatfinish etc., complete as per drawing details, Technical specifications and as directed by Client or Engineer in charge. |
| 67 | 11.33.225 mm wooden planking, tongued and grooved in flooring, including fixing with iron screws complete with Second class deodar wood |
| 68 | OD Providing and fixing wooden deck flooring as per below following descriptionProfile Code : SW-1005.Dimension : 145mm x 23mm.Standard Length : 2.44 mts / 8\"Standard colour : Wenge, Walnut.Special Colour : Red, Black, Teak, Beach White.Surface Finishes: Sanding, Brushing, Wooden Effect.The standard size for decking boards typically ranges from 5.5 inches to 6 inches in width and 1 inch to 1.5 inches in thickness. These dimensions provide a balance between stability, aesthetics, and ease of installation. A gap of 2 mm is essential between two joists and 5 mm between two decking boards. This is a precautionary measure where temperature difference is huge from weather to weather. After fixing the joist to the ground, decking board is placed on the joist in crisscross manner or at right angle. Decking board is fixed with clamp and screw to the joist. |
| 69 | OD Supply and Installation of Tile Profile Roofing sheet with Below the tile roofing provide Cement Board. |
| 70 | OD Laying and finishing of Vitrified tiles of size 1200x600mm of thickness 12mm.Tiles shal be fixed with cement based high polymer modified quick set tile adhesive (water based) conforming to IS : 15477 , in average 6-10 mm thickness, including grouting of joints (Payment for grouting of joints to be made separately). |
| 71 | 11.48.2Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg). including filling /grouting and finishing complete as per direction of Engineer-in-charge.Size of Tile 600x600 mm |
| 72 | OD Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg). including filling /grouting and finishing complete as per direction of Engineer-in-charge. Size of Tile 600x1200mm |
| 73 | 12.26.1 Providing and fixing plain Multipurpose Cement board (High Pressure steam cured) as per IS : 14862, with suitable screws for fibre cement board in ceiling etc. complete (frame work to be paid separately) :6 mm thick cement board |
| 74 | OD Providing and Installing 4\"x8\" Panel Wood false ceiling fixed on 3\"x2\" frame at 4\" centre to centre using mentioned fixing accessories etc. Completed as per technical specifications, drawing and as directed by Client/Engineer in charge. |
| 75 | 12.45.1Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/ sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37 mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25 mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5x25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound, jointing tapes, finishing with jointing compound in 3 layers covering up to 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer\"s specification and also including the cost of making openings for light fittings, grills, diffusers, cut-outs made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with:12.5 mm thick tapered edge gypsum plain board conforming to IS : 2095-Part 1 |
| 76 | OD Providing and fixing of the 1\"x1\" terracotta panels on 2\"x2\" Aluminium frame using tounge and groove joints. Complete as per drawing, technical specification and as directs by Client/Engineer in charge |
| 77 | 25.1Providing and supplying aluminium extruded tubular and other aluminium sections as per the architectural drawings and approved shop drawings , the aluminium quality as per grade 6063 T5 or T6 as per BS 1474,including super durable powder coating of 60-80 microns conforming to AAMA 2604 of required colour and shade as approved by the Engineer-in-Charge. ( The item includes cost of material such as cleats, sleeves, screws etc. necessary for fabrication of extruded aluminium frame work. Nothing extra shall be paid on this account). |
| 78 | 25.3 Providing, assembling and supplying vision glass panels (IGUs) comprising of hermetically-sealed 6-12- 6 mm insulated glass (double glazed) vision panel units of size and shape as required and specified, comprising of an outer heat strengthened float glass 6mm thick, of approved colour and shade with reflective soft coating on surface # 2 of approved colour and shade, an inner Heat strengthened clear float glass 6mm thick, spacer tube 12mm wide, desiccants, including primary seal and secondary seal (structural silicone sealant) etc. all complete for the required performances, as per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineer-in-Charge. The IGUs shall be assembled in the factory/ workshop of the glass processor. (Payment for fixing of IGU Panels in the curtain glazing is included in cost of item No.26.2) For payment, only the actual area of glass on face # 1 of the glass panels (excluding the areas of the grooves and weather silicone sealant) provided and fixed in position, shall be measured in sqm. (i) Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, + 12mm Airgap + 6mm Heat Strengthened clear Glass of approved make having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement |
| 79 | 8.26.1 Providing and fixing in wall lining flat pressed three layer (medium density) 12 mm thick particle board or graded wood Pre-laminated one side decorative lamination and other side balancing lamination Grade I, Type II, IS : 12823 marked, including priming coat on unexposed arrangement and screws etc. complete as per drawing, technical specification and as directs by Client/Engineer in charge |
| 80 | OD Providing and fixing in position metal sheet panelling on framework made of 50 x 25/ 50.8 x 25.4mm, 16swg (1.626mm thick and consider the tolerance range of 1.60 ~1.65mm) aluminium tube section framework. The aluminium sections shall be placed at 2\" 0\" c/c both ways and rigidly connected together using 3mm thick aluminium L- cleats fixed/ fastened to aluminium section with double screws as per the detail drawings and Architects\" instructions. The frame work shall be cladded with 12mm thick plywood, all the exposed plywood surface shall be finished with 1mm thick brush finish stainless steel sheet using silicone adhesive as directed by the project design consultants/PMC. Shop drawing & prototype sample shall be approved before execution of work at site. Make of SS Sheet & box section Make shall be of Stellora/ Naman Steels/Big Essentials/Progress Profile. |
| 81 | OD Providing and fixing of skylight polycarbonate sheets of thickness 25mm with co-extruded UV coating of 40 microns with light transmission of not less than 85% . The sheets are having anti glare - white diffuser colour with 100% light dispersion ratio. The sheets should confirms ASTM Standards D2240 for Hardness Shore A, D412 for Tensile Strength & Elongation Break, D624 for Tear Strength, D573 for heat resistance (Change in Hardness, Tensile Strength & Elongation), D395 for compression set and D1171 for ozone resistance. The Polycarbonate sheets should confirms fire test as per EN13501. Sheet should not show breakage due to loss of impact strength / weathering effect when tested as per ISO 6603/1-1985(E). Roof light extruded corrugation profile should match with main roof profile for a leak proof assembly. The sheet installation shall be carried out as per complete as per drawing, technical specification and as directs by Client/Engineer in charge |
| 82 | OD Suppyand Installationof the glass panels and frame, including all necessary scaffolding, tools, and equipment. Ensuring proper alignment, sealing, and weatherproofingetc complete as per drawing, technical specification and as directed by Client/Engineer in charge. |
| 83 | OD Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). |
| 84 | OD Providing and fixing Standoff railing consists of three parts: glass fastener, 3/8\" tempered glass panel, and handrail, 2\"x2 1/2\" SS standoff bracket pin system consists of glass panels held up by 2” round metal pins Each weighs about 4 pounds and is made from 2205 duplex stainless steel, etc complete as per drawing, technical specification and as directed by Client/Engineer in charge. |
| 85 | 8.2.2.2Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias, wall claddingand similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. |
| 86 | OD Providing and Fixing with sealing of mesh frames to existing window openings and louvers ensuring alignment and no gaps using silicone sealant and other necessary accessories etc complete as per drawing, technical specification and as directed by Client/Engineer in charge. |
| 87 | ODProviding and fixing laser cut perforated MS metal sliding gate consisting 50x50x6mm MS Hollow section, 25mm MS square bars @125mm c/c welded to MS frame, roller made out of 75x50 dia solid cylinder and 10mm thick plate with Zinc Chromate primer with enamel paint etc, complete as per technical specification, drawings and as directed by client or Engineer In charge. |
| 88 | 2.6.1 Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains(not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m |
| 89 | 4.1.A.2 Construction of granular sub-base by providing graded Material, mixing in a mechanical mix plant at OMC, carriage of mixed Material to work site, spreading in uniform layers with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per clause 401Grading-II - Plant Mix Method |
| 90 | 2.27Supplying and filling in plinth with Jamuna sand under floors, including watering, ramming consolidating and dressing complete. |
| 91 | 4.19.1.1Providing and laying in position ready mixed plain cement concrete, using fly ash and cement content as per approved design mix and manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for plain cement concrete work, including pumping of R.M.C. from transit mixer to site of laying and curing, admixtures in recommended proportions as per IS: 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer - in-charge. Note : 1) Excess/less cement used than specified in this item is payable/recoverable separately. 2) Fly ash conforming to grade I of IS 3812 (Part-1) only be used as part replacement of OPC as per IS: 456. Uniform blending with cement is to be ensured in accordance with clauses 5.2 and 5.2.1 of IS : 456-2000 in the items of BMC and RMC.All works upto plinth level :M-15 grade plain cement concrete (cement content considered @ 240 kg/cum) |
| 92 | 16.68.Providing and laying 60 mm thick factory made cement concrete interlocking paver block of M - 30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 50 mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of Engineer-in-charge. |
| 93 | 16.78.1Construction of granular sub- base by Providing close graded Material conforming to specifications, mixing in a mechanical mix plant at OMC, Carriage of mixed material by tippers to work site, for all leads & lifts, spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per specifications and directions of Engineer-in- Charge.With Material conforming to Grade - I ( size range 75 mm to 0.075 mm) having CBR Value- 30 |
| 94 | 16.79Providing , laying spreading and compacting graded stone aggregate ( size range 53 mm to 0.075 mm) to wet mix macadam (WMM) specification including premixing the material with water at OMC in mechanical mix plant, carriage of mixed material by tipper to site, for all leads & lifts, laying in uniform layers with mechanical paver finisher in sub - base / base course on well prepared surface and compacting with vibratory roller of 8 to 10 tonne capacity to achieve the desired density, complete as per specifications and directions of Engineer - in- Charge. |
| 95 | 2.27.Supplying and filling in plinth with Jamuna sand under floors, including watering, ramming consolidating and dressing complete. |
| 96 | 4.19.1.1Providing and laying in position ready mixed plain cement concrete, using fly ash and cement content as per approved design mix and manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for plain cement concrete work, including pumping of R.M.C. from transit mixer to site of laying and curing, admixtures in recommended proportions as per IS: 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer - in-charge. Note : 1) Excess/less cement used than specified in this item is payable/recoverable separately. 2) Fly ash conforming to grade I of IS 3812 (Part-1) only be used as part replacement of OPC as per IS: 456. Uniform blending with cement is to be ensured in accordance with clauses 5.2 and 5.2.1 of IS : 456-2000 in the items of BMC and RMC.All works upto plinth level :M-15 grade plain cement concrete (cement content considered @ 240 kg/cum) |
| 97 | 16.91.2 Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge.80 mm thick C.C. paver block of M-30 grade with approved color design and pattern. |
| 98 | 2.27Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains(not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m |
| 99 | 4.19.1.1Providing and laying in position ready mixed plain cement concrete, using fly ash and cement content as per approved design mix and manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for plain cement concrete work, including pumping of R.M.C. from transit mixer to site of laying and curing, admixtures in recommended proportions as per IS: 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer - in-charge. Note : 1) Excess/less cement used than specified in this item is payable/recoverable separately. 2) Fly ash conforming to grade I of IS 3812 (Part-1) only be used as part replacement of OPC as per IS: 456. Uniform blending with cement is to be ensured in accordance with clauses 5.2 and 5.2.1 of IS : 456-2000 in the items of BMC and RMC.M-15 grade plain cement concrete (cement content considered @ 240 kg/cum) |
| 100 | 4.1.A.2Construction of granular sub-base by providing graded Material, mixing in a mechanical mix plant at OMC, carriage of mixed Material to work site, spreading in uniform layers with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per clause 401Grading-II - Plant Mix Method -GSB 300MM THICK |
| 101 | 16.79Providing, laying, spreading and compacting graded stone aggregate (size range 53 mm to 0.075 mm ) to wet mix macadam (WMM) specification including premixing the material with water at OMC in for all leads & lifts, laying in uniform layers with mechanical paver finisher in sub- base / base course on well prepared surface and compacting with vibratory roller of 8 to 10 tonne capacity to achieve the desired density, complete as per specifications and directions of Engineer-in-Charge. WMM - 250MM THICK |
| 102 | 5.4.1 Providing and laying dense bituminous macadam with 80-100 TPH HMP producing an average output of 75 tonnes per hour using crushed aggregates of specified grading, premixed with bituminous binder (VG 30) @ 4.0 per cent by weight of total mix and filler, transporting the hot mix to work site, laying with a hydrostatic paver finisher with sensor control to the required grade, level and alignment, rolling with smooth wheeled, vibratory and tandem rollers to achieve the desired compaction as per MoRTH specification clause No. 505 complete in all respects.Grading - I (37.5 mm Nominal Size)-Bituminous Concrete- 50MM THICK |
| 103 | 5.6.1.aProviding and laying bituminous concrete with 80-100 TPH hot mix plant producing an average output of 75 tonnes per hour using crushed aggregates of specified grading, premixed with bituminous binder( NRMB) @ 5.2 per cent of mix and filler, transporting the hot mix to work site, laying with a hydrostatic paver finisher with sensor control to the required grade, level and alignment, rolling with smooth wheeled, vibratory and tandem rollers to achieve the desired compaction as per MORTH specification clause No. 507 complete in all respectsFor Grading - I ( 19 mm nominal size ) - Bituminous Concrete- 30MM THICK |
| 104 | 5.1.a Providing and applying primer coat with bitumen emulsion ( SS) on prepared surface of granular Base including clearing of road surface and spraying primer at the rate of 0.70 - 1.0 kg/sqm using mechanical means |
| 105 | 5.2.a Providing and applying tack coat with bitumen emulsion( RS) using emulsion pressure distributor at the rate of 0.20 - 0.30 kg per sqm on the prepared bituminous surface cleaned with mechanical broom. |
| 106 | 8.2.AConstruction of cement concrete kerb with channel with top and bottom width 115 and 165 mm respectively, 250 mm high in M 20 Grade PCC Using Concrete Mixer on M10 grade foundation 150 mm thick, kerb channel 300 mm wide, 50 mm thick in PCCM20 grade, sloped towards the kerb, kerb stone with channel laid with kerb laying machine, foundation concrete laid manually, all complete as per clause 409 |
| 107 | ODPainting of Kerb stone with 2 or more coat of synthetic enamel paint of approved brand and manufacture to give an even shade of alternate yellow and black color. The rate includes primer, paint,lead, lift etc complete as per Technical Specification, drawings and directed by Client / Engineer in charge. |
| 108 | 2.25Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m. |
| 109 | 4.1.A.2Construction of granular sub-base by providing graded Material, mixing in a mechanical mix plant at OMC, carriage of mixed Material to work site, spreading in uniform layers with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per clause 401Grading-II - Plant Mix Method |
| 110 | 4.19.1.1Providing and laying in position ready mixed plain cement concrete, using fly ash and cement content as per approved design mix and manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for plain cement concrete work, including pumping of R.M.C. from transit mixer to site of laying and curing, admixtures in recommended proportions as per IS: 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer - in-charge. Note : 1) Excess/less cement used than specified in this item is payable/recoverable separately. 2) Fly ash conforming to grade I of IS 3812 (Part-1) only be used as part replacement of OPC as per IS: 456. Uniform blending with cement is to be ensured in accordance with clauses 5.2 and 5.2.1 of IS : 456-2000 in the items of BMC and RMC.M-15 grade plain cement concrete (cement content considered @ 240 kg/cum) |
| 111 | 5.33.1Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is payable or recoverable separately.All work up to plinth level |
| 112 | 5.9.1Centering and shuttering including strutting, propping etc. and removal of form work for : |
| 113 | 5.22.6Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth level Thermo - Mechanically Treated bars of grade Fe-500D or more |
| 114 | 10.2Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 115 | OD Providing, Supplying, Loading, Unloading on site Factory made steam cured R.C.C Precast drain cover slab, for drain (Inside Dimensions-L x B X H as approved in drawing. The drain shall be of M25 grade concrete including reinforcement Fe500 Grade or HD Wire of IS:432 Part II, OPC 53 Grade Cement. The surface finish shall be smooth finish, with special in built insert, sleeves at appropriate location as specified in drawing for fixing, lifting including mechanical means, loading, transportation at site including all leads, lifts etc., complete as per technical specification and as directed by Client or Engineer in charge.690x700x75mm |
| 116 | OD Providing, Supplying, Loading, Unloading on site Factory made steam cured R.C.C Precast drain cover slab, for drain (Inside Dimensions-L x B X H as approved in drawing. The drain shall be of M25 grade concrete including reinforcement Fe500 Grade or HD Wire of IS:432 Part II, OPC 53 Grade Cement. The surface finish shall be smooth finish, with special in built insert, sleeves at appropriate location as specified in drawing for fixing, lifting including mechanical means, loading, transportation at site including all leads, lifts etc., complete as per technical specification and as directed by Client or Engineer in charge.550x690x75mm |
| 117 | 2.25Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m. |
| 118 | 4.1.A.2Construction of granular sub-base by providing graded Material, mixing in a mechanical mix plant at OMC, carriage of mixed Material to work site, spreading in uniform layers with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per clause 401Grading-II - Plant Mix Method |
| 119 | 4.19.1.1Providing and laying in position ready mixed plain cement concrete, using fly ash and cement content as per approved design mix and manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for plain cement concrete work, including pumping of R.M.C. from transit mixer to site of laying and curing, admixtures in recommended proportions as per IS: 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer - in-charge. Note : 1) Excess/less cement used than specified in this item is payable/recoverable separately. 2) Fly ash conforming to grade I of IS 3812 (Part-1) only be used as part replacement of OPC as per IS: 456. Uniform blending with cement is to be ensured in accordance with clauses 5.2 and 5.2.1 of IS : 456-2000 in the items of BMC and RMC.M-15 grade plain cement concrete (cement content considered @ 240 kg/cum) |
| 120 | 5.33.1Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is payable or recoverable separately.All work up to plinth level |
| 121 | 5.9.1Centering and shuttering including strutting, propping etc. and removal of form work for : |
| 122 | 5.22.6Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete up to plinth level. |
| 123 | 10.2Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 124 | 2.25Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m. |
| 125 | 4.19.1.1Providing and laying in position ready mixed plain cement concrete, using fly ash and cement content as per approved design mix and manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for plain cement concrete work, including pumping of R.M.C. from transit mixer to site of laying and curing, admixtures in recommended proportions as per IS: 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer - in-charge. Note : 1) Excess/less cement used than specified in this item is payable/recoverable separately. 2) Fly ash conforming to grade I of IS 3812 (Part-1) only be used as part replacement of OPC as per IS: 456. Uniform blending with cement is to be ensured in accordance with clauses 5.2 and 5.2.1 of IS : 456-2000 in the items of BMC and RMC.M-15 grade plain cement concrete (cement content considered @ 240 kg/cum) |
| 126 | 5.33.1Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is payable or recoverable separately.All work up to plinth level |
| 127 | 5.9.1Centering and shuttering including strutting, propping etc. and removal of form work for : |
| 128 | 5.22.6Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete up to plinth level. |
| 129 | 2.25Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m. |
| 130 | OD Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1:2 (1 cement : 2 coarse sand) to match the existing floor:With Chlorpyriphos/Lindane E.C. 20% with 1% concentration |
| 131 | 4.19.1.1Providing and laying in position ready mixed plain cement concrete, using fly ash and cement content as per approved design mix and manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for plain cement concrete work, including pumping of R.M.C. from transit mixer to site of laying and curing, admixtures in recommended proportions as per IS: 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer - in-charge. Note : 1) Excess/less cement used than specified in this item is payable/recoverable separately. 2) Fly ash conforming to grade I of IS 3812 (Part-1) only be used as part replacement of OPC as per IS: 456. Uniform blending with cement is to be ensured in accordance with clauses 5.2 and 5.2.1 of IS : 456-2000 in the items of BMC and RMC.M-15 grade plain cement concrete (cement content considered @ 240 kg/cum) |
| 132 | 5.33.1Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is payable or recoverable separately.All work upto plinth level- Tank-Base raft,Walls,Slab |
| 133 | 5.33.2 Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is payable or recoverable separately.All work above plinth level upto floor V level WTP ROOM-Column, Beams,Slab |
| 134 | 5.34.1Extra for providing richer mixes at all floor levels. Note:- Excess/less cement over the specified cement content used is payable/ recoverable separately.Providing M-30 grade concrete instead of M-25 grade BMC/RMC. (Note:- Cement content considered in M-30 is @ 340 kg/cum). |
| 135 | 5.9.1Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete: Raft and base |
| 136 | 5.9.2Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. :Walls |
| 137 | 5.9.3Centering and shuttering including strutting, etc. and removal of form for:Suspended floors, roofs, landings, balconies and access platform:slab |
| 138 | 5.9.6Centering and shuttering including strutting, etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts :Columns |
| 139 | 5.9.5Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers: beams |
| 140 | 5.9.3Centering and shuttering including strutting, etc. and removal of form for:Suspended floors, roofs, landings, balconies and access platform:slab |
| 141 | 5.22.6Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete up to plinth level. |
| 142 | 6.47Providing and laying autoclaved aerated cement blocks masonry with 150mm/ 230mm/300 mm thick AAC blocks in super structure above plinth level up to floor V level with RCC band at sill level and lintel level with approved block laying polymer modified adhesive mortar all complete as per direction of Engineer-in-Charge. (The payment of RCC band and reinforcement shall be made for seperately). |
| 143 | OD ACCESS DOOR :- supply and installation of 30 mm thick factory-made moulded PVC door (Wood free) with single panel sensor-based operation as per drawing approved by Engineer-in-charge. |
| 144 | OD Providing, & fixing PVC rungs inside tanks embedded in concrete , Rungs shall be of Heavy duty , size and shape all as per approval, placed at 300mm c/c etc. all complete as per technical specifications, drawings and as directed by Client or Engineer-in-charge.Note : - Size (270x170x25mm) -12mm Rod WTP Tanks |
| 145 | OD Providing, Supplying, Loading, Unloading on site Factory made R.C.C Precast drain cover slab, for trench (Inside Dimensions-L x B X H as approved in drawings drawing. The drain shall be of M20 grade concrete including reinforcement Fe500D Grade or HD Wire of IS:432 Part II, OPC 53 Grade Cement. The surface finish shall be smooth finish, with special in built insert, sleeves as per specified in drawing for fixing and lifting, rate shall include mechanical means, loading, transportation at site including all leads, lifts., complete as per technical specification, drawings and as directed by client or Engineer In charge.Note :- Covers shall have MS lift hooks for Easy operations |
| 146 | 22.23.1Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservoir, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI-212-3R-2010 i.e. by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineering- charge. The product performance shall carry guarantee for 10 years against any leakage.For vertical surface two coats @0.70 kg per sqm |
| 147 | OD Supply, Fabrication and installation of prefabricated portable cabins with the dimensions of 2.4mm x 2.4mm. The cabin shell shall be fabricated from tested quality steel duly welded comprising of base frame, peripheral structure, self draining roof, entry doors and of windows (as per the requirement). The top corners of the cabin shall be sufficiently strengthened to facilitate transportation, lifting & placing. 1. Exterior walls shall be made up of 18 swg (Minimum) MS vertically corrugated sheet whereasthe interior walls shall be with PUF insulation of minimum 50mm thick (from valley) with 1.2mm thick prepainted galvanized steel sheet of approved colour coating confirming to RAL Colours.All gaps will be sealed at edges, seams and bottom etc to prevent ingress of moisture. 2. The flooring shall be of PVC vinyl flooring of 2mm thick laid over BWR grade plywood of required thickness confirming to IS: 303-1960 using rubber based adhesives for optimum adhesive nature. Metallic edge strips may be used and should be securely fastened to the subfloor to protect the edges of flooring. 3. Ceiling shall be of gypsum boards of thickness 12mm of approved.4. Additional supports, perimeter channels, ceiling sections shall be provided for cut outs for light fitting, AC etc. Panels shall be finished with smooth finish including jointing and finishing to a flush finish of tapered and squared edges of the board with recommended jointing compound, jointing tapes Etc. 5. Doors shall be of single leaf solid aluminium panel door with aluminium frame 1.2 - 1.5mm thickness and windows shall be of aluminium powder coated sliding interlocking shutter window with 3 track aluminium frame with safety grill and 2 window shutter with fixed glass of required thickness including mosquito net with locking mechanism and the required ironmongery.6. Providing and fixing of 10W LED Lights, 6/16 AMP Switch sockets & wall mounted fans and necessary electrical works.Rate shall include cost of required civil works (foundations), cost of labour, tools & tackles, loading/unloading at site etc complete as per manufacturers details and as directed by client or Engineer - in - charge. |
| 148 | 2.27Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains(not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m |
| 149 | 2.25Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m. |
| 150 | 4.19.1.1Providing and laying in position ready mixed plain cement concrete, using fly ash and cement content as per approved design mix and manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for plain cement concrete work, including pumping of R.M.C. from transit mixer to site of laying and curing, admixtures in recommended proportions as per IS: 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer - in-charge. Note : 1) Excess/less cement used than specified in this item is payable/recoverable separately. 2) Fly ash conforming to grade I of IS 3812 (Part-1) only be used as part replacement of OPC as per IS: 456. Uniform blending with cement is to be ensured in accordance with clauses 5.2 and 5.2.1 of IS : 456-2000 in the items of BMC and RMC.M-15 grade plain cement concrete (cement content considered @ 240 kg/cum) |
| 151 | 5.33.1Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is payable or recoverable separately.All work upto plinth level-Electric pole pedestal |
| 152 | 5.34.1Extra for providing richer mixes at all floor levels. Note:- Excess/less cement over the specified cement content used is payable/ recoverable separately.Providing M-30 grade concrete instead of M-25 grade BMC/RMC. (Note:- Cement content considered in M-30 is @ 340 kg/cum).-Electric pole pedestal |
| 153 | 5.9.1Centering and shuttering including strutting, propping etc. and removal of form work for : Foundations, footings, bases of columns, etc for mass concrete: Raft and base |
| 154 | 5.22.6Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete up to plinth level. |
| 155 | 26.80.1Providing & Grouting of dowel tubes / Shear keys / Joints of precast members with M-60 grade cementitious grout (Non Shrink) of approved make by suitable means ( Free flowing /pump),curing etc. Complete as per directions of Engineerin-charge. (The payment shall be made on the basis of actual weight of approved grout injected.)Stirrer mixed cementitious grout (non shrink) of approved make in dowel tubes / Shear keys / Joints of precast members. |
| 156 | od104726/2024_2025Clearing and grubbing including uprooting rank vegetation, grass, bushes, shrubs, saplings and trees girth up to 300 mm, removal of stumps of trees cut earlier and disposal of unserviceable materials and stacking of serviceable material to be used or auctioned, up to a lead of 1000 metres including removal and disposal of top organic soil not exceeding 150 mm in thickness In area of light jungle - ByMechanical Means |
| 157 | od101288/2024_2025Excavation in all kind of soil with hydraulic excavator of 0.9 cum bucket capacity including cutting and loading in tippers, transporting to embankment site within all lifts and lead upto 1000 m, trimming bottom and side slopes in accordance with requirements of lines, grades and cross sections. |
| 158 | 16.70.1Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts , bolts and washers as required complete as per the direction of Engineer-in- charge.Made of G.I. wire of dia 4 mm |
| 159 | 10.1Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 160 | 2.8.1Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil |
| 161 | 2.25Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m. |
| 162 | 4.1.3Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:2:4 (cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) |
| 163 | 4.1.2Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:1/2:3 (cement : 11/2 coarse sand : 3 graded stone aggregate 20 mm nominal size) |
| 164 | 5.33.1Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is payable or recoverable separately.All work upto plinth level |
| 165 | 5.22.6Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more |
| 166 | 5.9.2Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. |
| 167 | 2.8.1Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil |
| 168 | 2.25Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m. |
| 169 | 4.1.3Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:2:4 (cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) |
| 170 | 5.9.2Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. |
| 171 | 5.33.1Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is payable or recoverable separately.All work upto plinth level |
| 172 | 5.22.6Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more |
| 173 | 50.6.7.2Laterate masonry with neatly dressed laterate stone of size 40x20x15cm or nearest size in cement mortar 1:6 for super structure above plinth level up to floor two level including all cost of materials, labour charges etc. |
| 174 | ODLaterate masonry with neatly dressed laterate stone of size 40x20x15cm or nearest size in cement mortar 1:6 for super structure above plinth level up to floor two level including all cost of materials, labour charges etc. (Laterate shall be cut from the site premises and the same shall be neatly dressed tomeet the exact size required as directed by the Engineer in Charge ) |
| 175 | 13.10Providing and laying of Filter media with granular materials/stone crushed aggregates satisfying the requirements laid down in clause 2504.2.2. of MoRTH specifications to a thickness of not less than 600 mm with smaller size towards the soil and bigger size towards the wall and provided over the entire surface behind abutment, wing wall and return wall to the full height compacted to a firm condition complete as per drawing and Technical Specification. |
| 176 | od101314/2024_2025Supplying and fitting 75mm dia 6kgf/cm2 PVC weep holes as per drawing and direction of Engineer In charge |
| 177 | od103593/2024_2025Providing, laying in position Non-Woven Geotextile – all works as per the directions of Engineer-incharge. 100 to 200 GSM |
| 178 | 2.25Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m. |
| 179 | PLUMBING AND SANITARY FIXTURES (PHE) |
| 180 | OD Fixing, testing and commissioning of European water closet (EWC) wall hung type with soft close seat cover & 06 litre concealed PVC/ Vitreous flushing cistern with all internal parts of cistern-Concealed type (CP Dualflush). CP / copper / SS connecting pipe to cistern with end nuts.Cast-iron chair or cantilever bracket with CP Push plate, CP wall Flanges , Angle valve cantilever bracket with CP bolt & Nut, Flush tank -20 mm Día Concealed/ Exposed type as applicable with all necessary fittings & fixtures required for fixing of EWC wall hung type Silicon-based sealants for leak-proof connections, especially around the joints between the WC and drainage pipe.. etc. complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 181 | OD Fixing water closet squatting pan (Indian type W.C. pan) with 100 mm Sand Cast Iron P or S trap, 10 litter low level white P.V.C.flushing cistern, including flush pipe, manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever require:White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests |
| 182 | OD Fixing, testing and commissioning of 15mm CP health faucet with one no. of CP angle cock, CP flexible tube 1.0m long, CP crutch, nozzle, All necessary item required to complete install the Fixture etc. complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative. Note- Max flow RMTe should be 8ltr / min. |
| 183 | OD Fixing toilet paper holder:C.P. brass of approved quality & make and as per the direction of Engineer in charge. |
| 184 | OD Fixing 6V Dc Dual Flush Sensor Urinals of approx. size 350 x 295 x 685 mm ,white colour,glossy finish, All necessary item required complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 185 | OD Providing & fixing, of Urinal HPL Partition moulding to outer edge size 0.45m x 1.2m inserted 12 mm inside wall. Complete as per approved make, manufacturer standard, Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 186 | OD Fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever required. Stainless Steel AISI 304 (18/8) round basin, 405 x 355 mm, with single 15 mm C.P. brass pillar tap, 15 mm C.P. brass angular stop cock, and all necessary items required to complete the installation of the fixture, including sealant, etc.complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 187 | OD Fixing CP Brass 32mm size Bottle trap of approved quality & make and as per the direction of Engineer in charge. |
| 188 | OD Fixing, testing and commissioning of Above Counter / Under Counter Rectangular Type wash basin with ASC white / colour and of vitreous China with best quality manufactured by an approved firm and size as specified, (Disabled / Handicap Toilet and other rooms)•Single lever mixer/Pillar Cock •15mm CP brass angular stop cock.•CP / copper / SS inlet connecting pipes with end nuts. •32mm CP waste coupling. •CP wall flanges •32mm CP Bottle Trap with extension pipe (casted type) •40mm die PVC connecting pipe up to floor trap. •Angle Supportswith all necessary item required to complete install the Fixture including sealant etc. complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 189 | OD Providing and fixing of Liquid Soap Dispenser shall be of automatic battery operated and sensor type made of ABS plastic / CP with necessary accessories required to complete install the Fixture etc. complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 190 | OD Providing, fixing, testing and commissioning of Stainless Steel Hand dryer Euronics / Dyson (Recommended brand and model), fixing with required stainless steel screws, All necessary item required to complete install the Fixture etc. complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative |
| 191 | OD DISABLED ARM SUPPORT & GRAB BAR FOR WC - Providing & fixing of Stainless steel floor or wall mounted hand railing of 50mm dia, 1.6mm thick S/S pipe with necessary bend & termination at all height confirming to SS 304 grade, Sating finish, with) fixing at C/C 900mm using neck S/S pipe 19 X 2mm complete as per approved make, manufacturer standard, Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 192 | OD DISABLED ARM SUPPORT (FIXED) FOR WASH BASIN- Providing & fixing of Stainless steel Arm Support System made of round SS 304 grade of dia38.1 x 1.5 mm the with 100 x 5 mm the Flange. Over all size:- 450 x 215mm (fixed on both sides of WB) complete as per approved make, manufacturer standard, Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 193 | OD Providing, Fixing of Bip tap with all required accessories like Teflon etc., complete as per approved make, manufacturer standard, Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 194 | OD Providing and fixing of Floor Trap shall include CP frame and grating, The trap shall be fitted with anti- cockroach grating, A minimum of 70mm depth of water seal shall be provided in the trap and shall be with all necessary accessories required to complete install the Fixture etc. complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative |
| 195 | OD Providing and facing of Floor Cleanout (FCO), consisting of a cast iron body, with brass cleanout plug and stainless steel or nickel bronze cover, including all necessary fittings and accessories, complete as per approved drawings, specifications, and plumbing codes. The cleanout shall be installed flush with the finished floor level. Cleanout as per Technical Specification, drawings and directed by Employer/Employer Representative.OD 75mm dia |
| 196 | OD Providing and facing of Floor Cleanout (FCO), consisting of a cast iron body, with brass cleanout plug and stainless steel or nickel bronze cover, including all necessary fittings and accessories, complete as per approved drawings, specifications, and plumbing codes. The cleanout shall be installed flush with the finished floor level. Cleanout as per Technical Specification, drawings and directed by Employer/Employer Representative.OD 110 mm dia |
| 197 | OD Providing, fixing, testing and commissioning of Shower and Shower Arm with necessary accessories, fittings required to complete install the fixture etc. as per Technical Specification, drawings and directed by Employer/Employer Representative. |
| 198 | OD Providing, fixing, testing and commissioning of Hot /Cold CP Wall Mixer tap for Shower with necessary accessories required to complete install the fixture etc. as per Technical Specification, drawings and directed by Employer/Employer Representative. |
| 199 | ODFixing Glamour Towel Rail(600 mm) of approved quality & make and as per the direction of Engineer in charge. |
| 200 | OD Providing and fixing of 6mm thick Mirror with silver backing and 12mm thick Plywood with necessary accessories required to complete the fixing, complete as per Technical Specification, drawings and directed by Employer/Employer Representative. |
| 201 | OD Providing and fixing of Stainless steel / ABS plastic plain pedal Dustbin of 20 litre capacity with necessary accessories required to complete install the fixture etc., complete as per Technical Specification, drawings and directed by Employer/Employer Representative. |
| 202 | OD Fixing Glamour Soap Dish of approved quality & make and as per the direction of Engineer in charge. |
| 203 | OD Providing, fixing, testing and commissioning of Electric Geyser with specified capacity and shall have necessary fixing material such as 2 no\"s angle cock with connection tubes and accessories to complete install the fixture etc. complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative .25 Litre Capacity |
| 204 | OD Providing, laying, jointing, testing and commissioning approved make UPVC pipes SWR grade confirming to IS 13592 Class \"B\" with solvent joints confirming to IS 5382 for solvent jointing for Suspended piping in ceiling Lvl. The quoted RMTe shall include necessary fittings like Tees, 45 or 90 deg. Bends, Couplers, Offsets, etc., G.I. brackets with pvc coated GI clamps, nuts & bolts, anchor fasteners, grip bolts, GI threaded, rods, vent cowl etc., complete. (internal piping in toilet slab).40 MM DIA |
| 205 | ODProviding, laying, jointing, testing and commissioning approved make UPVC pipes SWR grade confirming to IS 13592 Class \"B\" with solvent joints confirming to IS 5382 for solvent jointing for Suspended piping in ceiling Lvl. The quoted RMTe shall include necessary fittings like Tees, 45 or 90 deg. Bends, Couplers, Offsets, etc., G.I. brackets with pvc coated GI clamps, nuts & bolts, anchor fasteners, grip bolts, GI threaded, rods, vent cowl etc., complete. (internal piping in toilet slab).75 MM DIA |
| 206 | OD Providing, laying, jointing, testing and commissioning approved make UPVC pipes SWR grade confirming to IS 13592 Class \"B\" with solvent joints confirming to IS 5382 for solvent jointing for Suspended piping in ceiling Lvl. The quoted RMTe shall include necessary fittings like Tees, 45 or 90 deg. Bends, Couplers, Offsets, etc., G.I. brackets with pvc coated GI clamps, nuts & bolts, anchor fasteners, grip bolts, GI threaded, rods, vent cowl etc., complete. (internal piping in toilet slab).50 MM DIA -SOIL PIPE |
| 207 | OD Providing, laying, jointing, testing and commissioning approved make UPVC pipes SWR grade confirming to IS 13592 Class \"B\" with solvent joints confirming to IS 5382 for solvent jointing for Suspended piping in ceiling Lvl. The quoted RMTe shall include necessary fittings like Tees, 45 or 90 deg. Bends, Couplers, Offsets, etc., G.I. brackets with pvc coated GI clamps, nuts & bolts, anchor fasteners, grip bolts, GI threaded, rods, vent cowl etc., complete. (internal piping in toilet slab).75 MM DIA -SOIL PIPE |
| 208 | ODProviding, laying, jointing, testing and commissioning approved make UPVC pipes SWR grade confirming to IS 13592 Class \"B\" with solvent joints confirming to IS 5382 for solvent jointing for Suspended piping in ceiling Lvl. The quoted RMTe shall include necessary fittings like Tees, 45 or 90 deg. Bends, Couplers, Offsets, etc., G.I. brackets with pvc coated GI clamps, nuts & bolts, anchor fasteners, grip bolts, GI threaded, rods, vent cowl etc., complete. (internal piping in toilet slab).110MM DIA -SOIL PIPE |
| 209 | OD Providing, laying, jointing, testing and commissioning approved make UPVC pipes SWR grade confirming to IS 13592 Class \"B\" with solvent joints confirming to IS 5382 for solvent jointing for Suspended piping in ceiling Lvl. The quoted RMTe shall include necessary fittings like Tees, 45 or 90 deg. Bends, Couplers, Offsets, etc., G.I. brackets with pvc coated GI clamps, nuts & bolts, anchor fasteners, grip bolts, GI threaded, rods, vent cowl etc., complete. (internal piping in toilet slab).160MM DIA |
| 210 | OD Providing, laying, jointing, testing and commissioning approved make UPVC pipes SWR grade confirming to IS 13592 Class \"B\" with solvent joints confirming to IS 5382 for solvent jointing for Suspended piping in ceiling Lvl. The quoted RMTe shall include necessary fittings like Tees, 45 or 90 deg. Bends, Couplers, Offsets, etc., G.I. brackets with pvc coated GI clamps, nuts & bolts, anchor fasteners, grip bolts, GI threaded, rods, vent cowl etc., complete. (internal piping in toilet slab).75 mm dia -WASTE PIPE |
| 211 | OD Providing, laying, jointing, testing and commissioning approved make UPVC pipes SWR grade confirming to IS 13592 Class \"B\" with solvent joints confirming to IS 5382 for solvent jointing for Suspended piping in ceiling Lvl. The quoted RMTe shall include necessary fittings like Tees, 45 or 90 deg. Bends, Couplers, Offsets, etc., G.I. brackets with pvc coated GI clamps, nuts & bolts, anchor fasteners, grip bolts, GI threaded, rods, vent cowl etc., complete. (internal piping in toilet slab).110 dia -SOIL PIPEINTERNAL WATER Providing SYSTEM CLASS OF PIPESTANDARDSIZESCLASS-1 SDR-11 ASTM D 2846 1/2\" to 2\"CLASS-2 SDR-13.5ASTM D 2846 1/2\" to 2\"SCH40 ASTM F 4412-1/2\" to 8\"SCH80 ASTM F 4412-1/2\" to 8\"CLASS OF FITTINGSTANDARD SIZESSDR-11 ASTM D 2846 1/2\" to 2\"SCH40 ASTM F 4382-1/2\" to 4\"SCH80 ASTM F439 2-1/2\" to 8\"SOLVENT CEMENTASTM F 493- |
| 212 | 18.8.2Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.20 mm nominal outer dia pipes |
| 213 | 18.8.3Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.25 mm nominal outer dia pipes |
| 214 | 18.8.4Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.32 mm nominal outer dia pipes |
| 215 | 18.7.5Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall40 mm nominal outer Dia pipes |
| 216 | 18.7.6Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall50 mm nominal outer Dia pipes |
| 217 | 18.8.2Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.20 mm nominal outer dia pipes |
| 218 | 18.8.3Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.25 mm nominal outer dia pipes |
| 219 | 18.8.4Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.32 mm nominal outer dia pipes |
| 220 | 18.7.5Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall40 mm nominal outer Dia pipes |
| 221 | 18.7.6Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall50 mm nominal outer Dia pipes |
| 222 | 18.7.6Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall50 mm nominal outer dia pipes (DWC Shaft) |
| 223 | OD Providing, fixing, testing and commissioning of Ball valves as specified below,1)All ball valves shall be heavy duty of approved make. Valves shall have suitable for test pressure of 25 Kg/Sqcm. Ball valves shall conform to the following specifications. 2)Construction - Bronze body S.S. Working Part stainless steel balls, spindle, Teflon seating and gland packing.3) Ends - Screwed. Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative.20 mm dia |
| 224 | OD Providing, fixing, testing and commissioning of Ball valves as specified below,1)All ball valves shall be heavy duty of approved make. Valves shall have suitable for test pressure of 25 Kg/Sqcm. Ball valves shall conform to the following specifications. 2)Construction - Bronze body S.S. Working Part stainless steel balls, spindle, Teflon seating and gland packing.3) Ends - Screwed. Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative.25 mm dia |
| 225 | OD Providing, fixing, testing and commissioning of Ball valves as specified below,1)All ball valves shall be heavy duty of approved make. Valves shall have suitable for test pressure of 25 Kg/Sqcm. Ball valves shall conform to the following specifications. 2)Construction - Bronze body S.S. Working Part stainless steel balls, spindle, Teflon seating and gland packing.3) Ends - Screwed. Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative.32 mm dia |
| 226 | OD Providing, fixing, testing and commissioning of Ball valves as specified below,1)All ball valves shall be heavy duty of approved make. Valves shall have suitable for test pressure of 25 Kg/Sqcm. Ball valves shall conform to the following specifications. 2)Construction - Bronze body S.S. Working Part stainless steel balls, spindle, Teflon seating and gland packing.3) Ends - Screwed. Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative.40 mm dia |
| 227 | OD Providing, fixing, testing and commissioning of Ball valves as specified below,1)All ball valves shall be heavy duty of approved make. Valves shall have suitable for test pressure of 25 Kg/Sqcm. Ball valves shall conform to the following specifications. 2)Construction - Bronze body S.S. Working Part stainless steel balls, spindle, Teflon seating and gland packing.3) Ends - Screwed. Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative.50 mm dia |
| 228 | OD 1)All butterfly valves shall be heavy duty cast steel/iron of approved make. The valves shall be suitable for 15-20 Kg/Sqcm test pressure & shall conform to the following specifications Butterfly valve shall be of best quality conforming to BS 5155.2)Construction - Cast steel/iron 3)Ends - Flanged Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative.50 mm Dia |
| 229 | 18.19.4.2Providing and fixing gun metal non-return valve of approved quality (screwed end):50 mm nominal boreVertical50 mm Dia NON RETURN VALVE |
| 230 | 18.19.3.2Providing and fixing gun metal non-return valve of approved quality (screwed end):50 mm nominal boreVertical40 mm Dia NON RETURN VALVE |
| 231 | OD Providing, fixing, testing and commissioning of Y- Strainers shall be of Y-pattern bucket type of not less than full line size shall be constructed of cast iron body with stainless steel screen of perforationsa. Size 15 - 50 mmY-type strainers with screwed cover, 18/8 stainless steel screen, 26 swg with 0.8 mm perforations. Ends screwed BS 21 taper thread.b. Service Rating : 10 deg C to 100 deg C , 10.5 bar 186 deg C sat steam.Y-type single basket strainer, 20 mesh stainless steel screen, bolted cover. Flanged and drilled to BS 4504.with all arrangement of following size etc. complete as per Technical Specification, drawings and directed by Employer/Employer Representative.50 mm Dia Y - STARINER |
| 232 | OD Providing, fixing, testing and commissioning of Y- Strainers shall be of Y-pattern bucket type of not less than full line size shall be constructed of cast iron body with stainless steel screen of perforationsa. Size 15 - 50 mmY-type strainers with screwed cover, 18/8 stainless steel screen, 26 swg with 0.8 mm perforations. Ends screwed BS 21 taper thread.b. Service Rating : 10 deg C to 100 deg C , 10.5 bar 186 deg C sat steam.Y-type single basket strainer, 20 mesh stainless steel screen, bolted cover. Flanged and drilled to BS 4504.with all arrangement of following size etc. complete as per Technical Specification, drawings and directed by Employer/Employer Representative.40 mm Dia Y - STARINER |
| 233 | OD Providing, fixing testing and commissioning of Hydro Pneumatic Pump System - Flushing Water Providing with VFD drive,Pumps shall be multistage, monobloc vertical , centrifugal pumps with C.I body and bronze impeller, stainless steel shaft, mechanical seal and coupled to a TEFC electric induction motor, All parts in contact with water shall be corrosion resistant stainless-steel DIN- Nr.1.4401. drive. Package to include :(1) Two water pumps (1W+1S).(2) Pressure Transmitter.(3) Non Return Valve at discharge of each pump(4) Isolating Valves at suction and discharge of each pump.(5) Pressure Gauge-Gun metal Bourdon type with ball valve.(6) Discharge Header(HDPE).(7)Suction Header (HDPE).(8) Base Frame.(9) Stand.(10) VFD & CONTROL PANEL ( Local):Providing1 Nosuitable for ( 2 Nos ) Pumps.11) Manifold with associated valves & gauges.(12) Pressure tank capacity: (as per approved make, manufacturer recommendation) (13) The discharge manifold shall include a socket to install a pressure transducer with a 4-20mA output. The pressure transducer shall be factory installed and wired.All components shall be provided by OEM. Provide skid mounted complete assembly with single point electrical connection.Capacity - 2 LPS @ 40 Meter Head etc. 1.9 KW & 2.5 HP Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 234 | OD Providing, fixing testing and commissioning ofFilter Feeder System comprising of Vertical Centrifugal pump mounted on a skid with company supplied automatic control panel including overload relays, on-off push button switches, phaseindicator lamps, dry run protection relays, pressure Switches &gauges, CM 5-4 Pump with Motor Rating as 0.7 KW/ 1 HP, 1PH/230V, 50Hz, 2900 RPM, The pump shall run on 440V, 3PH, 50Hz Electric Providing Filter Feeder Pump - (1W + 1S)(1) Pressure Transmitter.(2) Non Return Valve at discharge of each pump(3) Isolating Valves at suction and discharge of each pump.(4) Pressure Gauge-Gun metal Bourdon type with ball valve.(5) Discharge Header(HDPE).(6)Suction Header (HDPE).(7) Base Frame.(8) Stand.Duty of pumps : 3 LPS@15mts head 0.7 KW & 1 HPcut - in pressure = 2.5 Barscut - off pressure = 3.0 Barsetc. complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative.Pump Location: Raw Water Pump to WTP |
| 235 | OD Providing, fixing testing and commissioning ofFilter Feeder System comprising of Vertical Centrifugal pump mounted on a skid with company supplied automatic control panel including overload relays, on-off push button switches, phaseindicator lamps, dry run protection relays, pressure Switches &gauges, CM 5-4 Pump with Motor Rating as 0.7 KW/ 1 HP, 1PH/230V, 50Hz, 2900 RPM, The pump shall run on 440V, 3PH, 50Hz Electric Providing Filter Feeder Pump - (1W + 1S)(1) Pressure Transmitter.(2) Non Return Valve at discharge of each pump(3) Isolating Valves at suction and discharge of each pump.(4) Pressure Gauge-Gun metal Bourdon type with ball valve.(5) Discharge Header(HDPE).(6)Suction Header (HDPE).(7) Base Frame.(8) Stand.Duty of pumps : 2.5 LPS@ 40mts head 1.9 KW & 2.5 HPcut - in pressure = 2.5 Barscut - off pressure = 3.0 Barsetc. complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative.Pump Location: Rain Water Pump to WTP |
| 236 | OD Providing, fixing testing and commissioning of Hydro Pneumatic Pump System - Irrigation water Providing with VFD drive,Pumps shall be multistage, monobloc vertical , centrifugal pumps with C.I body and bronze impeller, stainless steel shaft, mechanical seal and coupled to a TEFC electric induction motor, All parts in contact with water shall be corrosion resistant stainless-steel DIN- Nr.1.4401. drive. Package to include :(1) Two water pumps (1W+1S).(2) Pressure Transmitter.(3) Non Return Valve at discharge of each pump(4) Isolating Valves at suction and discharge of each pump.(5) Pressure Gauge-Gun metal Bourdon type with ball valve.(6) Discharge Header(HDPE).(7)Suction Header (HDPE).(8) Base Frame.(9) Stand.(10) VFD & CONTROL PANEL ( Local):Providing1 Nosuitable for ( 2 Nos ) Pumps 11) Manifold with associated valves & gauges(11) Pressure tank capacity: (as per approved make, manufacturer recommendation) (12) The discharge manifold shall include a socket to install a pressure transducer with a 4-20mA output. The pressure transducer shall be factory installed and wired.All components shall be provided by OEM. Provide skid mounted complete assembly with single point electrical connection.Capacity - 2 LPS @ 30 Meter Head etc. 1.1 KW & 1.5 HP Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 237 | OD Providing, fixing, Testing & Commissioning of submersible Borewell Pumps Capacity -approx.20 HP with VFD panel with its associated accessories, Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 238 | OD Providing, fabrication, fixing, testing and commissioning of GI Class\" C \"puddle flanged pipes of required sizes for inlet, outlet, vent and overflow pipes for Over Head Tank, UG Sump Tank, STP etc. . The puddle flanged pipes shall be threaded end up to 50 mm Dia and flanged ends above 100 mm Dia and length of flange should be 600 mm. All the puddle flanged pipes, plates and fittings shall be galvanized after fabrication as per IS specifications.Note : All puddle flanges to be hot dip galvanised.100 mm Dia-Inlet puddle flanges |
| 239 | OD Providing, fabrication, fixing, testing and commissioning of GI Class\" C \"puddle flanged pipes of required sizes for inlet, outlet, vent and overflow pipes for Over Head Tank, UG Sump Tank, STP etc. . The puddle flanged pipes shall be threaded end up to 50 mm Dia and flanged ends above 100 mm Dia and length of flange should be 600 mm. All the puddle flanged pipes, plates and fittings shall be galvanized after fabrication as per IS specifications.Note : All puddle flanges to be hot dip galvanised.50 mm Dia-Inlet puddle flanges |
| 240 | OD Providing, fabrication, fixing, testing and commissioning of GI Class\" C \"puddle flanged pipes of required sizes for inlet, outlet, vent and overflow pipes for Over Head Tank, UG Sump Tank, STP etc. . The puddle flanged pipes shall be threaded end up to 50 mm Dia and flanged ends above 100 mm Dia and length of flange should be 600 mm. All the puddle flanged pipes, plates and fittings shall be galvanized after fabrication as per IS specifications.Note : All puddle flanges to be hot dip galvanised.32 MM DIA-Inlet puddle flanges |
| 241 | OD Providing, fabrication, fixing, testing and commissioning of GI Class\" C \"puddle flanged pipes of required sizes for inlet, outlet, vent and overflow pipes for Over Head Tank, UG Sump Tank, STP etc. . The puddle flanged pipes shall be threaded end up to 50 mm Dia and flanged ends above 100 mm Dia and length of flange should be 600 mm. All the puddle flanged pipes, plates and fittings shall be galvanized after fabrication as per IS specifications.Note : All puddle flanges to be hot dip galvanised.150 mm Dia-Outlet puddle flanges |
| 242 | OD Providing, fabrication, fixing, testing and commissioning of GI Class\" C \"puddle flanged pipes of required sizes for inlet, outlet, vent and overflow pipes for Over Head Tank, UG Sump Tank, STP etc. . The puddle flanged pipes shall be threaded end up to 50 mm Dia and flanged ends above 100 mm Dia and length of flange should be 600 mm. All the puddle flanged pipes, plates and fittings shall be galvanized after fabrication as per IS specifications.Note : All puddle flanges to be hot dip galvanised.65 mm Dia -Outlet puddle flanges |
| 243 | OD Providing, fabrication, fixing, testing and commissioning of GI Class\" C \"puddle flanged pipes of required sizes for inlet, outlet, vent and overflow pipes for Over Head Tank, UG Sump Tank, STP etc. . The puddle flanged pipes shall be threaded end up to 50 mm Dia and flanged ends above 100 mm Dia and length of flange should be 600 mm. All the puddle flanged pipes, plates and fittings shall be galvanized after fabrication as per IS specifications.Note : All puddle flanges to be hot dip galvanised.50 mm Dia-Outlet puddle flanges |
| 244 | OD Providing, fabrication, fixing, testing and commissioning of GI Class\" C \"puddle flanged pipes of required sizes for inlet, outlet, vent and overflow pipes for Over Head Tank, UG Sump Tank, STP etc. . The puddle flanged pipes shall be threaded end up to 50 mm Dia and flanged ends above 100 mm Dia and length of flange should be 600 mm. All the puddle flanged pipes, plates and fittings shall be galvanized after fabrication as per IS specifications.Note : All puddle flanges to be hot dip galvanised.40 mm Dia-Outlet puddle flanges |
| 245 | OD Providing, fabrication, fixing, testing and commissioning of GI Class\" C \"puddle flanged pipes of required sizes for inlet, outlet, vent and overflow pipes for Over Head Tank, UG Sump Tank, STP etc. . The puddle flanged pipes shall be threaded end up to 50 mm Dia and flanged ends above 100 mm Dia and length of flange should be 600 mm. All the puddle flanged pipes, plates and fittings shall be galvanized after fabrication as per IS specifications.Note : All puddle flanges to be hot dip galvanised.32 mm Dia-Outlet puddle flanges |
| 246 | OD Providing, fixing of Swan neck bend for Vent pipe with brass performed grating complete as per approved make, manufacture standard ,Technical Specification, drawings and as directed by Employer/Employer Representative.(100mm Dia)-Swan neck bend for Vent pipe |
| 247 | OD Providing, fixing, testing & commissioning of Microprocessor based fully automatic Electronic water level controller with indicator and the following parameters facility: 1) Auto. 2) Manual 3) Sump Low. 4) Sump high. 5) Over head Tank Low. 6) Over Head Tank High. 7) Pump on. 8) Pump Fault. 9) Water flow indication. 10) Voltage display. Etc., with float switch (PVC Moulded Magnetic Float Sensors ) of approved make as required by the site engineer. WATER LEVEL CONTROLLER |
| 248 | OD Providing, fixing, testing & commissioning of wafer type 40 mm Motorized Butterfly valve, PN 16, body cast iron SS disc. Non spring return rotary type on/off actuator, torque 40 Nm, close off pressure 1200 Kpa, power supply 230 VAC, with 2 auxiliary switches, IP 67shall be including with control wiring Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 249 | OD Providing, laying, joining, testing and commissioning of HDPE pipe confirming to IS 4984, SDR 11.HDPE Specials and Fittings used for HDPE pipes shall conform to IS:8008 and IS:8360. Include all joints, supports and accessories required for the complete system. Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative.50 mm Dia ( DWC Line) |
| 250 | OD Providing, laying, joining, testing and commissioning of HDPE pipe confirming to IS 4984, SDR 11.HDPE Specials and Fittings used for HDPE pipes shall conform to IS:8008 and IS:8360. Include all joints, supports and accessories required for the complete system. Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative.40 mm Dia (FWS Line) |
| 251 | OD Providing, laying, joining, testing and commissioning of HDPE pipe confirming to IS 4984, SDR 11.HDPE Specials and Fittings used for HDPE pipes shall conform to IS:8008 and IS:8360. Include all joints, supports and accessories required for the complete system. Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative.100 MM DIA (Waste Pipe) |
| 252 | ODProviding, laying, joining, testing and commissioning of HDPE pipe confirming to IS 4984, SDR 11.HDPE Specials and Fittings used for HDPE pipes shall conform to IS:8008 and IS:8360. Include all joints, supports and accessories required for the complete system. Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative.160 MM DIA (Waste Pipe) |
| 253 | OD Providing, laying, joining, testing and commissioning of HDPE pipe confirming to IS 4984, SDR 11.HDPE Specials and Fittings used for HDPE pipes shall conform to IS:8008 and IS:8360. Include all joints, supports and accessories required for the complete system. Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative.160MM DIA (Soil Pipe) |
| 254 | OD Providing, laying, joining, testing and commissioning of HDPE pipe confirming to IS 4984, SDR 11.HDPE Specials and Fittings used for HDPE pipes shall conform to IS:8008 and IS:8360. Include all joints, supports and accessories required for the complete system. Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative.200MM DIA(Soil Pipe) |
| 255 | 18.60.2Providing and fixing enclosed type water meter (bulk type) conforming to IS: 2373 and tested by Municipal Board complete with bolts, nuts, rubber insertions etc. ( The tail pieces if required will be paid separately):100 mm dia nominal bore |
| 256 | OD Providing, fixing testing & Commissioning of PVC SWR pipes Type A for rain water Pipes. The quoted RMTe shall include necessary fittings like vent Pipes, Tees, 45 or 90 deg. Bends, Couplers, Offsets, Floor clean out and and pipe specific joining solvents ,etc. complete as per Technical Specification, drawings and directed by Employer/Employer Representative.110 mm Dia External |
| 257 | OD Providing, fixing testing & Commissioning of PVC SWR pipes Type A for rain water Pipes. The quoted RMTe shall include necessary fittings like vent Pipes, Tees, 45 or 90 deg. Bends, Couplers, Offsets, Floor clean out and and pipe specific joining solvents ,etc. complete as per Technical Specification, drawings and directed by Employer/Employer Representative.160 mm Dia External |
| 258 | 2.8.1Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil |
| 259 | 2.25Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m. |
| 260 | 2.26.1Extra for every additional lift 1.5 m or part there of in excavation / banking excavated or stacked materials.All kinds of soil Providing, laying, jointing and testing Socketed and Spigotted RCC Hume Pipes (NP2 class) confirming to IS:458 collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 find sand) laid to correct levels below ground in trenches Up to required depth. The Cost shall be inclusive of Excavation, Backfilling and Restoration of the surface , Providingand laying cement concrete mix M-20 up to haunches of R.C.C. pipes including bed concrete 15 cms thick as per standard design & specification. All work Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative. (Note: Contractor should ensure to take the necessary connection from the nearest points available in existing line) |
| 261 | 14.14.1Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 100 mm dia |
| 262 | 14.14.2Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 150 mm dia |
| 263 | 14.14.3Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 250 mm dia |
| 264 | OD Providing and Constructing in position brick masonryrain water Catch Basin depth up to 900 mm including the following. as per direction of Engineer in Charge.i. 230 thick brick walls in cement mortar 1:5 plastered inside and outside in C.M. 1:3ii. 150 thick bed concrete in C.C. 1:3:6iii. FRP Heavy duty cover.Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative Catch Basin Type - 1600mm x 600mm x 900mm |
| 265 | OD Providing and Constructing in position brick masonryrain water Catch Basin depth up to 900 mm including the following. as per direction of Engineer in Charge.i. 230 thick brick walls in cement mortar 1:5 plastered inside and outside in C.M. 1:3ii. 150 thick bed concrete in C.C. 1:3:6iii. FRP Heavy duty cover.Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative Rainwater Catch Basin with surface & Subsurface inlet of 300mmx300mmx300mm |
| 266 | OD Construction of brick masonry Inspection Chamber/manhole with one brick thick using bricks of designation - 5 in cement mortar 1:4 (1 cement, 4 sand), 100 mm thick foundation concrete 1:4:8 mix (1 cement, 4 coarse sand, 8 graded stone aggregate 40 mm and down), projecting 75 mm all round brick work including cost of shuttering, inside and outside plastering 15 mm thick with cement mortar 1:4 (1 cement, 4 sand) and inside plaster finished with a floating coat of neat cement, channel and benching with PCC 1:2:4 ( 1 cement, 2 coarse sand, 4 stone aggregate with 20 mm and down) and finished with 6mm thick cement plaster in cement mortar 1:4 ( 1 cement, 4 sand), and cement concrete of M15 grade all around and finished with neat cement., with 100 mm thick (average) RCC top slab in 1:2:4 mix (1 cement, 2 coarse sand, 4 graded stone aggregate 20mm and down), finished smooth (top and sides) with a floating coat of neat cement, all inside corners to be rounded to 75 mm radius with cement mortar 1:4 (1 cement, 4 sand), providing heavy duty CI cover and frame as per IS:1726,560 mm internal diameter (total weight of cover and frame to be not less than 25 Kg) CI cover shall be embossed with year, sewer, and arrow showing direction of flow or as specified in the drawings. The manhole cover and frame shall be painted with 3 coats of anti-corrosive paint after fixing in position., excavation in all kinds of soil with due allowance for working space for plastering, shuttering etc. including back filling, disposal of surplus earth where directed up to 1 Km lead,etc.Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative.Manhole Type 1 -Diameter: 1200mm and depth up to 2.5 mtrs |
| 267 | OD Construction of brick masonry Inspection Chamber/manhole with one brick thick using bricks of designation - 5 in cement mortar 1:4 (1 cement, 4 sand), 100 mm thick foundation concrete 1:4:8 mix (1 cement, 4 coarse sand, 8 graded stone aggregate 40 mm and down), projecting 75 mm all round brick work including cost of shuttering, inside and outside plastering 15 mm thick with cement mortar 1:4 (1 cement, 4 sand) and inside plaster finished with a floating coat of neat cement, channel and benching with PCC 1:2:4 ( 1 cement, 2 coarse sand, 4 stone aggregate with 20 mm and down) and finished with 6mm thick cement plaster in cement mortar 1:4 ( 1 cement, 4 sand), and cement concrete of M15 grade all around and finished with neat cement., with 100 mm thick (average) RCC top slab in 1:2:4 mix (1 cement, 2 coarse sand, 4 graded stone aggregate 20mm and down), finished smooth (top and sides) with a floating coat of neat cement, all inside corners to be rounded to 75 mm radius with cement mortar 1:4 (1 cement, 4 sand), providing heavy duty CI cover and frame as per IS:1726,560 mm internal diameter (total weight of cover and frame to be not less than 25 Kg) CI cover shall be embossed with year, sewer, and arrow showing direction of flow or as specified in the drawings. The manhole cover and frame shall be painted with 3 coats of anti-corrosive paint after fixing in position., excavation in all kinds of soil with due allowance for working space for plastering, shuttering etc. including back filling, disposal of surplus earth where directed up to 1 Km lead,etc.Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative.Inspection Chamber Type 1- 450x450x450mm |
| 268 | OD Construction of brick masonry Inspection Chamber/manhole with one brick thick using bricks of designation - 5 in cement mortar 1:4 (1 cement, 4 sand), 100 mm thick foundation concrete 1:4:8 mix (1 cement, 4 coarse sand, 8 graded stone aggregate 40 mm and down), projecting 75 mm all round brick work including cost of shuttering, inside and outside plastering 15 mm thick with cement mortar 1:4 (1 cement, 4 sand) and inside plaster finished with a floating coat of neat cement, channel and benching with PCC 1:2:4 ( 1 cement, 2 coarse sand, 4 stone aggregate with 20 mm and down) and finished with 6mm thick cement plaster in cement mortar 1:4 ( 1 cement, 4 sand), and cement concrete of M15 grade all around and finished with neat cement., with 100 mm thick (average) RCC top slab in 1:2:4 mix (1 cement, 2 coarse sand, 4 graded stone aggregate 20mm and down), finished smooth (top and sides) with a floating coat of neat cement, all inside corners to be rounded to 75 mm radius with cement mortar 1:4 (1 cement, 4 sand), providing heavy duty CI cover and frame as per IS:1726,560 mm internal diameter (total weight of cover and frame to be not less than 25 Kg) CI cover shall be embossed with year, sewer, and arrow showing direction of flow or as specified in the drawings. The manhole cover and frame shall be painted with 3 coats of anti-corrosive paint after fixing in position., excavation in all kinds of soil with due allowance for working space for plastering, shuttering etc. including back filling, disposal of surplus earth where directed up to 1 Km lead,etc.Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative.Inspection Chamber Type 2- 600x600x900mm |
| 269 | OD Construction of brick masonry Inspection Chamber/manhole with one brick thick using bricks of designation - 5 in cement mortar 1:4 (1 cement, 4 sand), 100 mm thick foundation concrete 1:4:8 mix (1 cement, 4 coarse sand, 8 graded stone aggregate 40 mm and down), projecting 75 mm all round brick work including cost of shuttering, inside and outside plastering 15 mm thick with cement mortar 1:4 (1 cement, 4 sand) and inside plaster finished with a floating coat of neat cement, channel and benching with PCC 1:2:4 ( 1 cement, 2 coarse sand, 4 stone aggregate with 20 mm and down) and finished with 6mm thick cement plaster in cement mortar 1:4 ( 1 cement, 4 sand), and cement concrete of M15 grade all around and finished with neat cement., with 100 mm thick (average) RCC top slab in 1:2:4 mix (1 cement, 2 coarse sand, 4 graded stone aggregate 20mm and down), finished smooth (top and sides) with a floating coat of neat cement, all inside corners to be rounded to 75 mm radius with cement mortar 1:4 (1 cement, 4 sand), providing heavy duty CI cover and frame as per IS:1726,560 mm internal diameter (total weight of cover and frame to be not less than 25 Kg) CI cover shall be embossed with year, sewer, and arrow showing direction of flow or as specified in the drawings. The manhole cover and frame shall be painted with 3 coats of anti-corrosive paint after fixing in position., excavation in all kinds of soil with due allowance for working space for plastering, shuttering etc. including back filling, disposal of surplus earth where directed up to 1 Km lead,etc.Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative.Inspection Chamber Type 3- 900x900x12000mm |
| 270 | 19.32.1Making soak pit 2.5 m diameter 3.0 metre deep with 45 x 45 cm dry brick honey comb shaft with bricks and S.W. drain pipe 100 mm diameter, 1.8 m long complete as per standard design.With common burnt clay F.P.S. (non modular) bricks of class designation 7.5- RAIN WATER recharge pit |
| 271 | 19.4.3.2Providing and fixing square-mouth S.W. gully trap class SP -1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design:180x150 mm size P typeWith sewer bricks conforming to IS: 4885 |
| 272 | 18.9.5Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings. This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching , refilling & testing of joints complete as per direction of Engineer- in-Charge. External work40 mm nominal outer Dia pipes |
| 273 | OD Providing, installing, testing and commissioning of Quick Coupling Valves shall be include of suitable air release valewith fabricated from high quality metal brass / Aluminium shall have rubber seal and able to withstand high pressure with necessary Unions and fittings etc.. complete as per Technical Specification, drawings and directed by Employer/Employer Representative.20 mm Dia |
| 274 | OD Providing, fixing testing and commissioning of Hydro Pneumatic Pump System - Flushing water Providing with VFD drive,Pumps shall bemultistage, monobloc vertical, centrifugal pumps with C.I body and bronze impeller, stainless steel shaft, mechanical seal and coupled to a TEFC electric induction motor, All parts in contact with water shall be corrosion resistant stainless-steel DIN- Nr.1.4401. drive. Package to include :(1) Two water pumps (1W+1S).(2) Pressure Transmitter.(3) Non Return Valve at discharge of each pump(4) Isolating Valves at suction and discharge of each pump.(5) Pressure Gauge-Gun metal Bourdon type with ball valve.(6) Discharge Header(HDPE).(7)Suction Header (HDPE).(8) Base Frame.(9) Stand.(10) VFD & CONTROL PANEL ( Local):Providing1 Nosuitable for ( 2 Nos ) Pumps.11) Manifold with associated valves & gauges(12) Pressure tank capacity: (as per approved make, manufacturer recommendation) (13) The discharge manifold shall include a socket to install a pressure transducer with a 4-20mA output. The pressure transducer shall be factory installed and wired.All components shall be provided by OEM. Provide skid mounted complete assembly with single point electrical connection.Capacity - 2 LPS @ 40 Meter Head etc. 1.9 KW & 2.5 HP Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 275 | ELECTRICAL WORKS, HT WORKS |
| 276 | OD 5 WAY Ring Main Unit Supply, Installation, Testing and Commissioning of Outdoor type IP55 11kV RING MAIN UNIT as per KSEB requirement comprising of 2 Nos. 11KV 630A, 20kA for 3sec, LBS as Incomer & 3 No. 11KV, 630A, 20kA for 3sec VCB as outgoing with earth switch with all accessories and all metering and protection for satisfactory operation to meet local EB supply authority and CEIG complilence etc., as required.Switchgear shall be as specified in Single line diagram and complete as per Technical Specification, drawings and directed by Employer/Employer Representative. |
| 277 | OD HT Metering cubicle Supply, Installation, Testing and Commissioning of Outdoor type IP55 11kV HT Metering cubicle unit with suitable ratio CT and PT &Trivector Meters unit with complete accessories as per latest specifications of KSEB authorities and Engineer in charge and complete as per Technical Specification, drawings and directed by Employer/Employer Representative. |
| 278 | OD Supplyof 11 kV Unearthed grade, stranded aluminium conductor, XLPE insulated HT cable. Cables laid in ready made trenches/ cable tray/ hume pipes & the cables shall conform to IS 7098 Part II (latest edition) in all respects complete as per Technical Specification, drawings and directed by Employer/Employer Representative\"3C X 185 Sq.mm XLPE, Aluminium Armoured cable (UE). |
| 279 | 8.3.2Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Above 120 sq. mm and upto 400 sq. mm |
| 280 | 10.5.3Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :240 sq. mm |
| 281 | OD Supplying and making termination with heatshrinkablestraightthroughoutdoor cable jointing kits complete with all accessories including lugs suitable for following size of 3 core x 185 Sq.mm, XLPE aluminium conductor cable of 11 KV grade. |
| 282 | OD Laying of 1.1KV grade PVC insulated Copper cables ( YFY). complete as per Technical Specification, drawings and directed by Employer/Employer Representative-12 Core x 2.5 Sqmm Cable (PVC). |
| 283 | OD Laying of 1.1KV grade PVC insulated Copper cables ( YFY). complete as per Technical Specification, drawings and directed by Employer/Employer Representative-24 Core x 2.5 Sqmm Cable (PVC). |
| 284 | OD Laying of 1.1KV grade PVC insulated Copper cables ( YFY). complete as per Technical Specification, drawings and directed by Employer/Employer Representative12 Core x 2.5 Sqmm Cable (PVC). |
| 285 | OD Laying of 1.1KV grade PVC insulated Copper cables ( YFY). complete as per Technical Specification, drawings and directed by Employer/Employer Representative 24 Core x 2.5 Sqmm Cable (PVC). |
| 286 | OD Supply, Termination for For Double Compression Gland with related all Accessories.complete as per Technical Specification, drawings and directed by Employer/Employer Representative 12 Core x 2.5 Sqmm Cable (PVC) |
| 287 | OD Supply, Termination for For Double Compression Gland with related all Accessories.complete as per Technical Specification, drawings and directed by Employer/Employer Representative 24 Core x 2.5 Sqmm Cable (PVC) |
| 288 | OD Supply,Manufacturing,Testing and Commissioning of the following panels, 415, 3 Phase, 50 Hz, 50 cycles, 4 wire system, Main Distribution & Sub-Main Distribution Panels as per IS 8623/IEC61439.Panels shall be fabricated out of 2 mm thick CRCA sheet steel for load bearing & 1.6 mm thick CRCA sheet steel for non-load bearing, in cubical formation, compartmentalized in form 4b construction, floor mounted, free standing and shall be dust and vermin proof. 3 mm thick cable gland plate, shall be provided both at the top and the bottom of the panel. Distribution panels shall comply with the latest Relevant Indian Standards and Electricity Rules and Regulations and shall be as per IS 8623. Panels for outdoor equipment shall be suitable for outdoor duty application. Panels shall be strictly based on IEC61439, type tested design of a switchgear OEM from a system integrator who has a license partnership with the switchgear OEM.The general construction shall confirm to IS-8623-1977 (Part-1) for factory built assembled switchgear & control gear for voltage up to and including 1100 V AC.The base channel of 75 mm x 40 mm x 5 mm thick shall be provided at the bottom for floor mounted panels. Complete as per Technical Specification, drawings and directed by Employer/Employer Representative.Complete as per Technical specification, Data Sheet, Drawings & directed by employer / employer representative. Note : All Distribution panels shall be CPRI tested design and manufactured by a approved manufacturer. CPRI certificate shall be made available.Main LT Panel - 1 (Ground Floor) (As per SLD) |
| 289 | ODSupply,Manufacturing,Testing and Commissioning of the following panels, 415, 3 Phase, 50 Hz, 50 cycles, 4 wire system, Main Distribution & Sub-Main Distribution Panels as per IS 8623/IEC61439.Panels shall be fabricated out of 2 mm thick CRCA sheet steel for load bearing & 1.6 mm thick CRCA sheet steel for non-load bearing, in cubical formation, compartmentalized in form 4b construction, floor mounted, free standing and shall be dust and vermin proof. 3 mm thick cable gland plate, shall be provided both at the top and the bottom of the panel. Distribution panels shall comply with the latest Relevant Indian Standards and Electricity Rules and Regulations and shall be as per IS 8623. Panels for outdoor equipment shall be suitable for outdoor duty application. Panels shall be strictly based on IEC61439, type tested design of a switchgear OEM from a system integrator who has a license partnership with the switchgear OEM.The general construction shall confirm to IS-8623-1977 (Part-1) for factory built assembled switchgear & control gear for voltage up to and including 1100 V AC.The base channel of 75 mm x 40 mm x 5 mm thick shall be provided at the bottom for floor mounted panels. Complete as per Technical Specification, drawings and directed by Employer/Employer Representative.Complete as per Technical specification, Data Sheet, Drawings & directed by employer / employer representative.Note : All Distribution panels shall be CPRI tested design and manufactured by a approved manufacturer. CPRI certificate shall be made available. Main LT Panel - 2 (Ground Floor) (As per SLD) |
| 290 | ODSupply,Manufacturing,Testing and Commissioning of the following panels, 415, 3 Phase, 50 Hz, 50 cycles, 4 wire system, Main Distribution & Sub-Main Distribution Panels as per IS 8623/IEC61439.Panels shall be fabricated out of 2 mm thick CRCA sheet steel for load bearing & 1.6 mm thick CRCA sheet steel for non-load bearing, in cubical formation, compartmentalized in form 4b construction, floor mounted, free standing and shall be dust and vermin proof. 3 mm thick cable gland plate, shall be provided both at the top and the bottom of the panel. Distribution panels shall comply with the latest Relevant Indian Standards and Electricity Rules and Regulations and shall be as per IS 8623. Panels for outdoor equipment shall be suitable for outdoor duty application. Panels shall be strictly based on IEC61439, type tested design of a switchgear OEM from a system integrator who has a license partnership with the switchgear OEM.The general construction shall confirm to IS-8623-1977 (Part-1) for factory built assembled switchgear & control gear for voltage up to and including 1100 V AC.The base channel of 75 mm x 40 mm x 5 mm thick shall be provided at the bottom for floor mounted panels. Complete as per Technical Specification, drawings and directed by Employer/Employer Representative.Complete as per Technical specification, Data Sheet, Drawings & directed by employer / employer representative. Note : All Distribution panels shall be CPRI tested design and manufactured by a approved manufacturer. CPRI certificate shall be made available. Main LT Panel - 2 (Ground Floor) (As per SLD) APFCR PANEL-1( 120 KVAR) (As per SLD) |
| 291 | ODSupply,Manufacturing,Testing and Commissioning of the following panels, 415, 3 Phase, 50 Hz, 50 cycles, 4 wire system, Main Distribution & Sub-Main Distribution Panels as per IS 8623/IEC61439.Panels shall be fabricated out of 2 mm thick CRCA sheet steel for load bearing & 1.6 mm thick CRCA sheet steel for non-load bearing, in cubical formation, compartmentalized in form 4b construction, floor mounted, free standing and shall be dust and vermin proof. 3 mm thick cable gland plate, shall be provided both at the top and the bottom of the panel. Distribution panels shall comply with the latest Relevant Indian Standards and Electricity Rules and Regulations and shall be as per IS 8623. Panels for outdoor equipment shall be suitable for outdoor duty application. Panels shall be strictly based on IEC61439, type tested design of a switchgear OEM from a system integrator who has a license partnership with the switchgear OEM.The general construction shall confirm to IS-8623-1977 (Part-1) for factory built assembled switchgear & control gear for voltage up to and including 1100 V AC.The base channel of 75 mm x 40 mm x 5 mm thick shall be provided at the bottom for floor mounted panels. Complete as per Technical Specification, drawings and directed by Employer/Employer Representative.Complete as per Technical specification, Data Sheet, Drawings & directed by employer / employer representative.Note : All Distribution panels shall be CPRI tested design and manufactured by a approved manufacturer. CPRI certificate shall be made available. Main LT Panel - 2 (Ground Floor) (As per SLD)APFCR PANEL-2 ( 150 KVAR) (As per SLD) |
| 292 | ODSupply,Manufacturing,Testing and Commissioning of the following panels, 415, 3 Phase, 50 Hz, 50 cycles, 4 wire system, Main Distribution & Sub-Main Distribution Panels as per IS 8623/IEC61439.Panels shall be fabricated out of 2 mm thick CRCA sheet steel for load bearing & 1.6 mm thick CRCA sheet steel for non-load bearing, in cubical formation, compartmentalized in form 4b construction, floor mounted, free standing and shall be dust and vermin proof. 3 mm thick cable gland plate, shall be provided both at the top and the bottom of the panel. Distribution panels shall comply with the latest Relevant Indian Standards and Electricity Rules and Regulations and shall be as per IS 8623. Panels for outdoor equipment shall be suitable for outdoor duty application. Panels shall be strictly based on IEC61439, type tested design of a switchgear OEM from a system integrator who has a license partnership with the switchgear OEM.The general construction shall confirm to IS-8623-1977 (Part-1) for factory built assembled switchgear & control gear for voltage up to and including 1100 V AC.The base channel of 75 mm x 40 mm x 5 mm thick shall be provided at the bottom for floor mounted panels. Complete as per Technical Specification, drawings and directed by Employer/Employer Representative.Complete as per Technical specification, Data Sheet, Drawings & directed by employer / employer representative.Note : All Distribution panels shall be CPRI tested design and manufactured by a approved manufacturer. CPRI certificate shall be made available. Main LT Panel - 2 (Ground Floor) (As per SLD)LIFT PANEL (As per SLD) |
| 293 | ODSupply,Manufacturing,Testing and Commissioning of the following panels, 415, 3 Phase, 50 Hz, 50 cycles, 4 wire system, Main Distribution & Sub-Main Distribution Panels as per IS 8623/IEC61439.Panels shall be fabricated out of 2 mm thick CRCA sheet steel for load bearing & 1.6 mm thick CRCA sheet steel for non-load bearing, in cubical formation, compartmentalized in form 4b construction, floor mounted, free standing and shall be dust and vermin proof. 3 mm thick cable gland plate, shall be provided both at the top and the bottom of the panel. Distribution panels shall comply with the latest Relevant Indian Standards and Electricity Rules and Regulations and shall be as per IS 8623. Panels for outdoor equipment shall be suitable for outdoor duty application. Panels shall be strictly based on IEC61439, type tested design of a switchgear OEM from a system integrator who has a license partnership with the switchgear OEM.The general construction shall confirm to IS-8623-1977 (Part-1) for factory built assembled switchgear & control gear for voltage up to and including 1100 V AC.The base channel of 75 mm x 40 mm x 5 mm thick shall be provided at the bottom for floor mounted panels. Complete as per Technical Specification, drawings and directed by Employer/Employer Representative.Complete as per Technical specification, Data Sheet, Drawings & directed by employer / employer representative. Note : All Distribution panels shall be CPRI tested design and manufactured by a approved manufacturer. CPRI certificate shall be made available. Main LT Panel - 2 (Ground Floor) (As per SLD)PHE PANEL (As per SLD) |
| 294 | ODSupply,Manufacturing,Testing and Commissioning of the following panels, 415, 3 Phase, 50 Hz, 50 cycles, 4 wire system, Main Distribution & Sub-Main Distribution Panels as per IS 8623/IEC61439.Panels shall be fabricated out of 2 mm thick CRCA sheet steel for load bearing & 1.6 mm thick CRCA sheet steel for non-load bearing, in cubical formation, compartmentalized in form 4b construction, floor mounted, free standing and shall be dust and vermin proof. 3 mm thick cable gland plate, shall be provided both at the top and the bottom of the panel. Distribution panels shall comply with the latest Relevant Indian Standards and Electricity Rules and Regulations and shall be as per IS 8623. Panels for outdoor equipment shall be suitable for outdoor duty application. Panels shall be strictly based on IEC61439, type tested design of a switchgear OEM from a system integrator who has a license partnership with the switchgear OEM.The general construction shall confirm to IS-8623-1977 (Part-1) for factory built assembled switchgear & control gear for voltage up to and including 1100 V AC.The base channel of 75 mm x 40 mm x 5 mm thick shall be provided at the bottom for floor mounted panels. Complete as per Technical Specification, drawings and directed by Employer/Employer Representative.Complete as per Technical specification, Data Sheet, Drawings & directed by employer / employer representative. Note : All Distribution panels shall be CPRI tested design and manufactured by a approved manufacturer. CPRI certificate shall be made available. Main LT Panel - 2 (Ground Floor) (As per SLD)MAIN ELDB(As per SLD) |
| 295 | ODSupply,Manufacturing,Testing and Commissioning of the following panels, 415, 3 Phase, 50 Hz, 50 cycles, 4 wire system, Main Distribution & Sub-Main Distribution Panels as per IS 8623/IEC61439.Panels shall be fabricated out of 2 mm thick CRCA sheet steel for load bearing & 1.6 mm thick CRCA sheet steel for non-load bearing, in cubical formation, compartmentalized in form 4b construction, floor mounted, free standing and shall be dust and vermin proof. 3 mm thick cable gland plate, shall be provided both at the top and the bottom of the panel. Distribution panels shall comply with the latest Relevant Indian Standards and Electricity Rules and Regulations and shall be as per IS 8623. Panels for outdoor equipment shall be suitable for outdoor duty application. Panels shall be strictly based on IEC61439, type tested design of a switchgear OEM from a system integrator who has a license partnership with the switchgear OEM.The general construction shall confirm to IS-8623-1977 (Part-1) for factory built assembled switchgear & control gear for voltage up to and including 1100 V AC.The base channel of 75 mm x 40 mm x 5 mm thick shall be provided at the bottom for floor mounted panels. Complete as per Technical Specification, drawings and directed by Employer/Employer Representative.Complete as per Technical specification, Data Sheet, Drawings & directed by employer / employer representative.Note : All Distribution panels shall be CPRI tested design and manufactured by a approved manufacturer. CPRI certificate shall be made available. Main LT Panel - 2 (Ground Floor) (As per SLD)AMF Panel - 1 - IP65 ( As per SLD ) |
| 296 | ODSupply,Manufacturing,Testing and Commissioning of the following panels, 415, 3 Phase, 50 Hz, 50 cycles, 4 wire system, Main Distribution & Sub-Main Distribution Panels as per IS 8623/IEC61439.Panels shall be fabricated out of 2 mm thick CRCA sheet steel for load bearing & 1.6 mm thick CRCA sheet steel for non-load bearing, in cubical formation, compartmentalized in form 4b construction, floor mounted, free standing and shall be dust and vermin proof. 3 mm thick cable gland plate, shall be provided both at the top and the bottom of the panel. Distribution panels shall comply with the latest Relevant Indian Standards and Electricity Rules and Regulations and shall be as per IS 8623. Panels for outdoor equipment shall be suitable for outdoor duty application. Panels shall be strictly based on IEC61439, type tested design of a switchgear OEM from a system integrator who has a license partnership with the switchgear OEM.The general construction shall confirm to IS-8623-1977 (Part-1) for factory built assembled switchgear & control gear for voltage up to and including 1100 V AC.The base channel of 75 mm x 40 mm x 5 mm thick shall be provided at the bottom for floor mounted panels. Complete as per Technical Specification, drawings and directed by Employer/Employer Representative.Complete as per Technical specification, Data Sheet, Drawings & directed by employer / employer representative.Note : All Distribution panels shall be CPRI tested design and manufactured by a approved manufacturer. CPRI certificate shall be made available. Main LT Panel - 2 (Ground Floor) (As per SLD)AMF Panel - 2 - IP 65( As per SLD ) |
| 297 | OD Supply, Installation, Testing and Commissioning of 1 x 5 kVA inverter with 3 phase input and 3 phase output. Consisting of the following. Supply, unload, store at site,Tubular batteries suitable for 90 minutes backup for above Inverter. Complete as per Technical specification, Data Sheet, Drawings & directed by employer / employer representative.Supply, unload, store at site, Battery accessories: \">> Battery breakers.\">> Interconnecting cable between batteries.\">> Cable between inverter and batteries. |
| 298 | OD Supply, Installation, Testing and Commissioning of15 KVA Online UPS, 3 phase input & 3 phase output and SMF type of batteries for 30 minutes backup with Ingress protection of enclosureIP42. Complete with all accessories. Such as suitable ratedMCCB isolators/ MCB Isolators on both I/P and O/P sides, DC Breaker , Battery rack, Interconnecting cables, termination of cables, Cu Bus Bar etc., Complete as per Technical Specification, drawings and directed by Employer/Employer Representative. |
| 299 | OD Supply, Installation, Testing and Commissioning of the 100 KWp(3 Phase) Solar PV System complete as per Technical Specification, drawings and directed by Employer / Employer Representative. |
| 300 | 90.12.5.36 Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 300 sq mm |
| 301 | 90.12.5.35Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required. 3.5 core 240 sq. mm |
| 302 | 90.12.5.34 Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required. 3.5 core 185 sq mm |
| 303 | 90.12.5.31 Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required. 3.5 core 95 sq mm |
| 304 | 90.12.5.29Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required. 3.5 core 50 sq mm |
| 305 | 90.12.5.28Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required. 3.5 core 35 sq mm |
| 306 | 90.12.5.27Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required. 3.5 core 25 sq mm |
| 307 | 90.12.5.42Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 25 sq mm |
| 308 | 90.12.5.41 Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required. 4 core 16 sq mm |
| 309 | 90.12.5.40 Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 10 sq mm |
| 310 | 90.12.5.39 Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required. 4 core 6 sq mm |
| 311 | 90.12.5.12Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required. 3 core 4 sq mm |
| 312 | 90.12.39.34 Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 16 sq mm |
| 313 | 90.12.39.6 Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3 core 6 sq mm |
| 314 | 90.12.39.5 Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3 core 4 sq mm |
| 315 | 9.1.30 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 300 sq. mm (70mm) |
| 316 | 9.1.29Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 240 sq. mm (62mm) |
| 317 | 9.1.27 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm) |
| 318 | 9.1.24 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 95 sq. mm (45mm) |
| 319 | 9.1.22 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm) |
| 320 | 9.1.21 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm) |
| 321 | 9.1.20Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X25 sq.mm (28mm) |
| 322 | 9.1.33 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm) |
| 323 | 9.1.33 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm) |
| 324 | 9.1.32 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.\"4 X 10 sq. mm (25mm) |
| 325 | ODSupplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4C x 6 Sq mm |
| 326 | ODSupplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4C x 4 Sq mm |
| 327 | OD Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE Copper conductor cable of 1.1 KV grade as required. \"4 X 16 sq. mm |
| 328 | OD Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE Copper conductor cable of 1.1 KV grade as required.3 core 6 sq mm |
| 329 | OD Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE Copper conductor cable of 1.1 KV grade as required.\"3 core 4 sq mm |
| 330 | 2.8.6Supplying and fixing following way prewired TP&N MCB Phase Segregated distribution board of steel sheet for 415 volts on surface/ recess complete with loose wire box, terminal connectors for all incoming and outgoing circuits, duly prewired with suitable size FRLS PVC insulated copper conductor up to terminal blocks, tinned copper bus bar, neutral link, earth bar, din bar, detachable gland plate, interconnections, powder painted including earthing etc. as required.(But without MCB/ RCCB/Isolator)6 way, Double door (ELDB - 1 - GF) |
| 331 | 2.8.8Supplying and fixing following way prewired TP&N MCB Phase Segregated distribution board of steel sheet for 415 volts on surface/ recess complete with loose wire box, terminal connectors for all incoming and outgoing circuits, duly prewired with suitable size FRLS PVC insulated copper conductor up to terminal blocks, tinned copper bus bar, neutral link, earth bar, din bar, detachable gland plate, interconnections, powder painted including earthing etc. as required.(But without MCB/ RCCB/Isolator)12 way, Double door (LPDB - 1 - GF & LPDB - 3 - FF ) |
| 332 | 2.8.7Supplying and fixing following way prewired TP&N MCB Phase Segregated distribution board of steel sheet for 415 volts on surface/ recess complete with loose wire box, terminal connectors for all incoming and outgoing circuits, duly prewired with suitable size FRLS PVC insulated copper conductor up to terminal blocks, tinned copper bus bar, neutral link, earth bar, din bar, detachable gland plate, interconnections, powder painted including earthing etc. as required.(But without MCB/ RCCB/Isolator)8 way, Double door (HVAC DB - GF,LPDB - 1 - FF) |
| 333 | ODSupplying and fixing following way prewired TP&N MCB Phase Segregated distribution board of steel sheet for 415 volts on surface/ recess complete with loose wire box, terminal connectors for all incoming and outgoing circuits, duly prewired with suitable size FRLS PVC insulated copper conductor up to terminal blocks, tinned copper bus bar, neutral link, earth bar, din bar, detachable gland plate, interconnections, powder painted including earthing etc. as required.(But without MCB/ RCCB/Isolator)12 Way VTPN DB Double door |
| 334 | 2.3.3 Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator)\"2.3.312 way, Double door (ELDB - 1 - FF) |
| 335 | 2.10.5Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.25A Triple pole and neutral |
| 336 | OD Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.40A Triple pole and neutral |
| 337 | OD Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.40A Triple pole and neutral |
| 338 | 2.10.1Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 339 | OD Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"B\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.16A Single pole |
| 340 | 2.14.1Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. \"25 amps |
| 341 | 2.14.2Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.\"40 amps |
| 342 | OD Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 100 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.40A DP 100mA RCCB |
| 343 | OD Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required32 Amp,16 KA,FP MCCB |
| 344 | OD External Lighting Panel- Supply, Installation, Testing and Commissioning of 415V, 3phase, distribution board with IP54 for outdoor,shall be provided with all accessories & following arrangements complete in all respect & direction of IEC / IS (before fabrication of panel board drawing is to be approved by Engineer-in- charge).The DB shall be fabricated out of 14/16-gauge CRCA sheet steel, totally enclosed, fully compartmentalized, Double Door type, dust and vermin proof, free standing, floor mounting type Complete as per Technical Specification, drawings and directed by Employer/Employer Representative. Incomer:40A TPN MCB - 1 No\"s,Sub Incomer:32A TPN 100mA RCCB - 3 No\"s, Outgoing:16A TPN MCB ( TYP ) - 12 No\"s, 24/7 Timer and 32A TPN Contactor, Bus Bar , Accessorises, others |
| 345 | 1.24.5 Providing, laying and fixing following Dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required.6 pin 15/16 amp socket outlet |
| 346 | 1.24.3Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch |
| 347 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 348 | 1.24.56 pin 15/16 amp socket outlet - 2 Nos |
| 349 | 1.24.315/16 amp switch |
| 350 | 1.27.1Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm) |
| 351 | 1.27.2Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm) |
| 352 | 1.27.4Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm) |
| 353 | OD.90.4.5.2Supply, conveyance, installation, testing and commissioning of ceiling fans of the following sizes using standard accessories excluding resistance type regulator, wiring the down rod with 16/0.20mm PVC insulated and PVC sheathed 650/1100V grade 3 core round copper conductor flex wire or with extended original wiring etc. as required.1200mm sweep -5star rated ceiling fan complete with 300mm down rod , canopies, shackles and blades working on 230V/240V single phase A/C |
| 354 | 1.25Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 355 | OD Supply, Installation, Testing and Commissioning of 25A Key Tag . |
| 356 | OD Supply, Installation, Testing and Commissioning of 30W Junction Box. |
| 357 | 2.12.1Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 358 | OD Supplying and fixing following rating, TPN , 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 359 | 2.13.3 Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.100 amps |
| 360 | 2.13.2 Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 361 | 2.13.1 Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 362 | 2.13.1Supplying and fixing following rating, TPN, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 363 | 2.16Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts DP Isolator complete with connections, testing and commissioning etc. as required. |
| 364 | OD Supplying and fixing of IP 65 Enclosure for 125 amps TPN Isolator |
| 365 | OD Supplying and fixing of IP 65 Enclosure for 100 amps FP Isolator |
| 366 | OD Supplying and fixing of IP 65 Enclosure for 63 amps FP Isolator |
| 367 | OD Supplying and fixing of IP 65 Enclosure for 40amps FP Isolator |
| 368 | OD Supplying and fixing of IP 65 Enclosure for 25amps FP Isolator |
| 369 | 1.17.32Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.5 x 6 sq. mm |
| 370 | 1.17.21 Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm |
| 371 | OD90.6.4.64Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.16.00 sq.mm 6 Run |
| 372 | ODSupply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3.5C X 25 Sqmm Al Un Arm Cable. |
| 373 | 1.17.12Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm |
| 374 | 1.17.21 Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm |
| 375 | OD 2R X 4 + 1R 2.5 SQMM FRLS Cu Wire |
| 376 | OD 2R X 2.5 + 1R 1.5 SQMM FRLS Cu Wire |
| 377 | 1.21.2 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 378 | 1.21.2 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm |
| 379 | 1.10.3Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. |
| 380 | 1.9Wiring for twin control light point with 1.5 sq.mm FRLC PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm. FRLC PVC insulated copper conductor single core cable etc as required. |
| 381 | Supply, Installation, Testing and Commissioning (Including supply and fixing flexible wires from holder to fixtures hardware\"s etc.) complete as per Technical Specification, drawings and directed by Client/Engineer-in-charge. This cost including supports, Fittings and hanging special Supports also complete as per technical specification & Drawings & directed by employer / employer representative. |
| 382 | OD Supply and Installation of 2X6W LED 3000K Ø65 Circular up/down Wall Light, Extruded aluminium housing duly pure polyester powder coated Dark Gray color,Toughened glass with IK06 protection, Luminaire with integral driver is pre- wired up to terminal block, IP65. lm/(W) 100 |
| 383 | OD Supply and Installation of 10W LED 5700K Bulkhead Luminaire, aluminium die cast housing, powder coated in dark Gray, Polycarbonate diffuser, Electronic Driver,IP65 Rated. lm/(W) 100 |
| 384 | OD Supply and Installation of 18W LED 5700K Surface mounted downlight, housing made of pressure die cast aluminium, white powder coated with polycarbonate cover, transmissivity diffuser, IP20 Electronic driver, IP40 |
| 385 | OD Supply and Installation of 15W LED 5700K Surface mounted downlight, housing made of pressure die cast aluminium, white powder coated with polycarbonate cover, transmissivity diffuser, IP20 Electronic driver, IP40. lm/(W) 66 |
| 386 | OD Supply and Installation of 15W LED 5700K Surface mounted downlight, housing made of pressure die cast aluminium, white powder coated with polycarbonate cover, transmissivity diffuser, IP20 Electronic driver, IP40, lm/(W) 66 |
| 387 | OD Supply and Installation of 30W/40W LED 5700K Surface mounted downlight, aluminium powder coated in white, clear glass diffuser, high efficiency reflector optics, Electronic driver, IP20 |
| 388 | OD Supply and Installation of 15W/m LED Strip 3000K 12VDC constant voltage driver, IP20, 1 driver for every roll. (5m = 1 roll Strip) |
| 389 | ODSupply and Installation of 10W/12W LED 5700K Surface mounted downlight, aluminium powder coated in white, clear glass diffuser, high efficiency reflector optics, Electronic driver, IP20 |
| 390 | OD Supply and Installation of7W LED 3000K 1m Bollard, IP65, Housing made of extruded aluminium, PC diffuser, Inbuilt electronic driver, IP65 |
| 391 | OD Supply and Installation of 4ft 30W/40W Suspended Linear Luminaire, Extruded Aluminium housing duly powder coated White and with black colour as a option, High Efficiency Translucence (HET) diffuser, UGR<19 Diffuser, Driver is pre-wired up to terminal block on the housing, Provision for loop in loop out for ease of wiring, Electronic Driver. IP20 |
| 392 | OD Supply and Installation of 18W LED 5700K Recessed mounted downlight, housing made of pressure die cast aluminium, white powder coated with polycarbonate cover, transmissivity diffuser, IP20 Electronic driver, IP40 |
| 393 | OD Supply and Installation of 24W/30W LED 5700K Surface mounted downlight, aluminium powder coated in white, clear glass diffuser, high efficiency reflector optics, Electronic driver, IP20 |
| 394 | OD Supply and installation of 8ft 60W/80W Suspended Linear Luminaire, Extruded Aluminium housing duly powder coated White and with black colour as a option, High Efficiency Translucence (HET) diffuser, UGR<19 Diffuser, Driver is pre-wired up to terminal block on the housing, Provision for loop in loop out for ease of wiring, Electronic Driver. IP20 |
| 395 | OD Supply, Fixing, Testing and Commissioning of 40W LED Recessed Linear Light Fixture. |
| 396 | OD Supply, Fixing, Testing and Commissioning of 3W LED Signage with Light Fixture. |
| 397 | OD Supply, Fixing, Testing and Commissioning of 6W LED Signage with Light Fixture. |
| 398 | OD Supply, Fixing, Testing and Commissioning of 6W LED Cylindrical Downlight Fixture. |
| 399 | OD Supply, Fixing, Testing and Commissioning of 10W LED Signage with Light Fixture. |
| 400 | OD Supply, Fixing, Testing and Commissioning of 3W LED Strip Light. |
| 401 | 90.15.3.9Supply installation testing and commissioning of Octagonal Pole made of hot dip galvanised GI sheet 70 mm top diameter, 155 mm bottom diameter thickness 3mm base plate dimensions of 250x250x16 mm suitable for wind speed as per IS 875 Part III single arm bracket 0.5mt including connector foundation bolt 4 nos fixed in existing RCC foundation and junction box , MCB etc, complete 9 Meters |
| 402 | 90.15.3.10Supply installation testing and commissioning of Octagonal Pole made of hot dip galvanised GI sheet 70 mm top diameter, 155 mm bottom diameter thickness 3mm base plate dimensions of 250x250x16 mm suitable for wind speed as per IS 875 Part III double arm bracket 0.5mt including connector foundation bolt 4 nos fixed in existing RCC foundation and junction box, MCB etc, complete 9 Meters |
| 403 | OD 60W Street light fixtures for the above pole |
| 404 | 90.12.39.31Supply & laying of one number PVC insulated and PVC sheathed armoured copper power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required. |
| 405 | OD Supply,Installation,Testing and commissioning of Hot dip Galvanized bolted type factory fabricated out of CRCA sheet of ladder Type cable trays with its tee, bends, couplers etc.,.complete as per technical specification & Drawings & directed by employer / employer representative. 1)Zinc to be used shall conform to minimum Zn 98 grade as per requirement of IS:209-1992.2)Minimum weight of zinc coating for mild steel flats with thickness up to 6 mm in accordance with IS:6745-1972 shall be 400 g/sqm. Necessary supports, brackets, angle iron, suspension are measured separately under the heading \"Steel Items\". |
| 406 | ODSupply,Installation,Testing and commissioning of Hot dip Galvanized bolted type factory fabricated out of CRCA sheet of Perforated Type cable trays with its tee, bends, couplers etc.,.complete as per technical specification & Drawings & directed by employer / employer representative. 1)Zinc to be used shall conform to minimum Zn 98 grade as per requirement of IS:209-1992.2)Minimum weight of zinc coating for mild steel flats with thickness up to 6 mm in accordance with IS:6745-1972 shall be 400 g/sqm. Necessary supports, brackets, angle iron, suspension are measured separately under the heading \"Steel Items\".450mm (W)X 50mm (H) X 1.6 mm (T) |
| 407 | ODSupply,Installation,Testing and commissioning of Hot dip Galvanized bolted type factory fabricated out of CRCA sheet of Perforated Type cable trays with its tee, bends, couplers etc.,.complete as per technical specification & Drawings & directed by employer / employer representative. 1)Zinc to be used shall conform to minimum Zn 98 grade as per requirement of IS:209-1992.2)Minimum weight of zinc coating for mild steel flats with thickness up to 6 mm in accordance with IS:6745-1972 shall be 400 g/sqm. Necessary supports, brackets, angle iron, suspension are measured separately under the heading \"Steel Items\".300mm (W)X 50mm (H) X 1.6 mm (T) |
| 408 | ODSupply,Installation,Testing and commissioning of Hot dip Galvanized bolted type factory fabricated out of CRCA sheet of Perforated Type cable trays with its tee, bends, couplers etc.,.complete as per technical specification & Drawings & directed by employer / employer representative. 1)Zinc to be used shall conform to minimum Zn 98 grade as per requirement of IS:209-1992.2)Minimum weight of zinc coating for mild steel flats with thickness up to 6 mm in accordance with IS:6745-1972 shall be 400 g/sqm. Necessary supports, brackets, angle iron, suspension are measured separately under the heading \"Steel Items\".100mm (W)X 50mm (H) X 1.6 mm (T) |
| 409 | OD Supply, fabrication & installation of MS channels / angles / Base Plate for Cable tray Support, Panel Support, etc. |
| 410 | OD Providing, laying and fixing following Dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. |
| 411 | 14.14.3250mm Hume Pipe |
| 412 | 14.14.4 Providing, laying and fixing following Dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required.300mm Hume Pipe |
| 413 | OD Supply, Installation, Testing and Commissioning of 8 mm Aluminium Round Conductor complete as specified in drawing & Meets the requirements of DIN EN 50164-2 (VDE 0175 part 202) & VDE 0175-305 (IS/IEC 62305). Complete as per technical specification & Drawings & directed by employer / employer representative. |
| 414 | OD Supply, Installation, Testing and Commissioning of Roof conductor holderfor parapet- Polyamide Conductor holder: With M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder. Weather and temperature resistant from -35 to +90 degree Celsius tested. Conductor holder @ 1 meter distance. complete as per technical specification & Drawings & directed by employer / employer representative. |
| 415 | OD Supply, Installation, Testing and Commissioning of Polyamide roof cable holder for flat roof: DIN 48829 Form B1. Closed form with bottom. Filling weight 1Kg (frost-resistant concrete). Sleeve from polyethylene, black@ 1 meter distance. Complete as per technical specification & Drawings & directed by employer / employer representative. |
| 416 | OD Supply, Installation, Testing and Commissioning of Polyamide roof cable holder for Tile roof: DIN 48829 Form B1. Closed form with bottom. Filling weight 1Kg (frost-resistant concrete). Sleeve from polyethylene, black@ 1 meter distance. Complete as per technical specification & Drawings & directed by employer / employer representative. |
| 417 | OD Supply Installation, Testing and Commissioning of 1 mtr vertical air terminal with mounting accessorieson the flat surface to meet the requirements of IS/IEC 62305. Tested for Electrical , mechanical and chemical as per IEC 62561. Complete as per technical specification & Drawings & directed by employer / employer representative. |
| 418 | OD Supply, Installation, Testing and Commissioning of cross universal connector: For T and cross connection,to route vertical down conductor /mesh formation made of hot dipped galvanisediron with necessary screws etc as required. Installed with 4 hexagonal bolts M8*25 with M8 hexagonal nuts . Complete as per technical specification & Drawings & directed by employer / employer representative. |
| 419 | OD Supply, Installation, Testing and Commissioning expansion piece with connector: For equalising temperature related length changes. Necessary on conductors length over 20 meters. For round conductor Rd 8/ALU. Complete as per technical specification & Drawings & directed by employer / employer representative. |
| 420 | OD Supply, Installation, Testing and Commissioning of 8 mm Aluminium Round Conductor complete as specified in drawing & Meets the requirements of DIN EN 50164-2 (VDE 0175 part 202) & VDE 0175-305 (IS/IEC 62305). complete as per technical specification & Drawings & directed by employer / employer representative. |
| 421 | OD Supply, Installation, Testing and Commissioning of Roof conductor holderfor parapet- Polyamide Conductor holder: With M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder. Weather and temperature resistant from -35 to +90 degree Celsius tested. Conductor holder @ 1 meter distance. complete as per technical specification & Drawings & directed by employer / employer representative. |
| 422 | OD Supply, Installation, Testing and Commissioning of cross universal connector: For T and cross connection,to route vertical down conductor /mesh formation made of hot dipped galvanisediron with necessary screws etc as required. Installed with 4 hexagonal bolts M8*25 with M8 hexagonal nuts . Complete as per technical specification & Drawings & directed by employer / employer representative. |
| 423 | OD Supply, Installation, Testing and Commission of 10 mm Copper coated Round Conductor complete as specified in drawing & Meets the requirements of DIN EN 50164-2 (VDE 0175 part 202) & VDE 0175-305 (IS/IEC 62305). Complete as per technical specification & Drawings & directed by employer / employer representative. |
| 424 | OD Supply, Installation, Testing and Commission of Roof conductor holderfor parapet- Polyamide Conductor holder: With M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder. Weather and temperature resistant from -35 to +90 degree Celsius tested. Complete as per technical specification & Drawings & directed by employer / employer representative. |
| 425 | OD Supply, Installation, Testing and Commissioning of Test Joint suitable to connect 8mm round conductor and max by 10mm Cu coated round conductor as specified in drawing and directed by Engineer, Quick SS installation using hexagonal bolt M10X30 high-grade stainless steel. Conforms to the requirements according to DIN VDE 0175-305 (IS-IEC 62305). Complete as per technical specification & Drawings & directed by employer / employer representative. |
| 426 | OD Supply, Installation, Testing and Commissioning of UL Listed & CPRI Tested maintenance free ,Low carbon copper coated earth rod of 3 metre electrode having diameter of 14mm with copper coating thickness of 250micron tested as per IEC 62561-2. With Universal clamp made of SS to connect rod with flat conductor. Earth conductivity enhancing compound shall be of 25 kg/pit tested as per IEC 62561-7,TCLP tested. Heavy duty earth champers of 5000kg load bearing capacity to ensure the safety of earthing system. complete as per technical specification & Drawings & directed by employer / employer representative. |
| 427 | OD Supply, Installation, Testing and Commissioning of Earthing electrode shall be 600 x 600 x 6.3 mm thick GI plate electrode, with 2 nos. 50 X 6 mm GI strips from earth plate electrode to inspection chamber, 50 mm Dia medium class GI pipe, CI funnel with 20 gauge GI wire mesh, masonry chamber 1000 X 500 mm with concrete base as per IS3043 with CI manhole cover with frame painted with bitumastic paint and packing with mixture of charcoal and common salt around plate electrode including digging of pit up to permanent moisture level but not less than 3 meters and back filling as required. complete as per technical specification & Drawings & directed by employer / employer representative. |
| 428 | OD Supply, Installation, Testing and Commissioning of Earthing electrode shall be 600 x 600 x 3.15 mm thick tined copper plate electrode, with 2 Nos 50 x 6 mm copper strips from earth plate electrode to inspection chamber, 50 mm Dia medium class GI pipe, CI funnel with 20 gauge GI wire mesh, masonry chamber 1000 x 500 mm with concrete base as per IS3043 with C I heavy duty / chequered plate manhole cover with frame painted with bitumastic paint and packing with mixture of charcoal and common salt around plate electrode including digging of pit up to permanent moisture level and as per soil condition but not less than 3 meters and back filling as required. complete as per technical specification & Drawings & directed by employer / employer representative. |
| 429 | OD Supply, Installation, Testing and Commissioning of 40x6mm Cu Flat. |
| 430 | OD Supply, Installation, Testing and Commissioning of 50x6mm GI Flat. |
| 431 | OD Supply, Installation, Testing and Commissioning of 25x6mm GI Flat. |
| 432 | Supply, Fixing, Testing and Commissioning of following safety accessories complete with fixing brackets etc. which shall be supplied by the tenderers with all necessary accessories, tools etc. |
| 433 | ODSupply, Fixing, Testing and Commissioning of following safety accessories complete with fixing brackets etc. which shall be supplied by the tenderers with all necessary accessories, tools etc.First Aid box |
| 434 | OD First Aid Chart in glassed wooden frame both in English and Hindi language. |
| 435 | OD Shock Treatment chart with teak wood frame and glass cover. |
| 436 | OD Fire buckets with floor / wall mounting stand and first filling of sand |
| 437 | OD 1.1 KV grade of 1.8Mtrs x 0.9 Mtrs Rubber mat and sufficient thickness. |
| 438 | OD 11 KV Rubber Hand Gloves |
| 439 | OD HT Cable Route markers |
| 440 | OD LT Cable Route markers |
| 441 | OD 1000mm (H) X 1000mm (W) X 1200mm (D) Inspection Chamber |
| 442 | OD 450mm (H) X 450mm (W) X 750mm (D) Inspection Chamber |
| 443 | ELV SYSTEM WORKS- FIRE ALARM SYSTEM |
| 444 | OD Supply, Installation, Testing and Commissioning of Fire Alarm Control Panel.The Panel shall be microprocessor based 2 loop panel and full capacity to connect 500 addressable devices in any combination. It shall have minimum 640 character liquid crystal display. It is recommended that number of devices per loop shall not be exceeding 90 percentage of full capacity. Panel shall have the networking capability with the other Fire alarm control panels. Each loop of Panel shall accommodate, monitor and control a minimum of 250 intelligent addressable devices in any combination. Each loop shall not exceed more than 3 km where the size of wire shall not be less than 1.5 sq mm. The Panel shall be a minimum store capacity up to 850 events. The panel shall support multiple languages, minimum 10 languages and shall be with aesthetically pleasing coloured LED panel lighting. Panel shall drive power to all devices over loop. The panel shall have facility to select open or closed loops.The panel shall carry minimum of 5years OEM warranty. The Panel shall be installer friendly and can be easily programmable with use of TCP/IP and there should be LED indication for activate zone. The fire alarm panel shall be UL approved and FM listed.The analogue interface board shall receive analogue information from all intelligent device and shall process this information to determine normal, alarm, or trouble conditions. The analogue information may also be used for automatic test and determination of maintenance requirements.Communication with all connected devices shall be performed every 5 seconds or less. Average time to alarm shall be less than 5 seconds. Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative.The system shall provide the following ports as communication ports:Ports for remote LCD or LED annunciatorEthernet port for IP connectivity1. One (1) Form C relay for Alarm status2. One (1) RS232 port for serial printer & one RS232 port for other serial port utilities3. One (1) Form C relay for Supervisory status4. One (1) port for Voice Evacuation Subsystem connection.5. One (1) Form C relay for Trouble status6. Ports for the connection to NAC expander module |
| 445 | OD Supply, Installation, Testing and Commissioning of Addressable Manual Call Point. Manual call points with Red LED alarm indicator and UL listed and FM approved. Operating temperature range of 0°C to 49°C and humidity range up to 93% RH non-condensing. Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 446 | OD Supply, Installation, Testing and Commissioning of Addressable Sounder with strobe Light. The unit shall have both audible and visual output units housed within the same device. It is UL Listed and FM approved. The audible output shall be multi-tone horn output up to 98dB and strobe output shall have selectable intensity of 15, 30, 75 and 110 candela. It is have an operating temperature range of 0°C to 50°C and humidity range up to 93% RH non-condensing. It shall be possible to poll each and every hooter with strobe unit from the HMI / Display / Operator Console at FACP, isolate and include in the circuit (NAC), activate and deactivate, view the voltage received by it from the HMI / Display / Operator Console at the FACP & Network Repeater. Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 447 | OD Supply, Installation, Testing and Commissioning of Addressable Weather Proof Sounder with strobe Light. Weatherproof outdoor sounder strobe shall have IP65 protection. The unit shall have both audible and visual output units housed within the same device. It is UL Listed and FM approved. The audible output shall be multi-tone horn output up to 98dB and strobe output shall have selectable intensity of 15, 30, 75 and 110 candela. It is have an operating temperature range of 0°C to 50°C and humidity range up to 93% RH non-condensing. It shall be possible to poll each and every hooter with strobe unit from the HMI / Display / Operator Console at FACP, isolate and include in the circuit (NAC), activate and deactivate, view the voltage received by it from the HMI / Display / Operator Console at the FACP & Network Repeater. Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 448 | OD Supply, Installation, Testing and Commissioning of Addressable Input Monitor Module. The operating temperature range of 0°C to 49°C and humidity range up to 93% RH non-condensing. Monitor Module shall be UL listed, Global, FM approved. Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 449 | OD Supply, Installation, Testing and Commissioning ofAddressable Output Control Module. The operating temperature range of 0°C to 49°C and humidity range up to 93% RH non-condensing. Control module shall provide two Form C contact, rated 3.0A at 30VDC; 0.9A at 125VAC resistive. The module shall have an LED that is controlled by the panel to indicate module status. Control Module shall be UL listed , FM approved.Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 450 | OD Supply, Laying, Testing and Commissioning of 2CX1.5 Samm Fire Resistance Cable with GI Saddle, Glands, terminals,Ferruling etc complete.Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 451 | OD Supply, fixing, test and commission Intelligent Addressable Heat Detector and with rate of rise of temperature feature, programmable for timed automatic sensitivity selection with Standard Base, junction box and other accessories. Detector shall be UL listed. |
| 452 | Public Address System |
| 453 | OD Supply, Installation, Testing and Commissioning of 6W Ceiling Mounted Speaker. Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative.Rated power 6 WTapping’s 100V line 6/3/1.5WOperation Voltage 100V or 70VEffective frequency range 120 ~ 17.5Hz (10% Variation allowed)SPL @ 1W/m >90 dBS.P.L. ,@Full power/ 1m, dB >95 dBColour As per project requirementApproval EN54-24 |
| 454 | OD Supply, Installation, Testing and Commissioning of Pagging Microphone. 16 buttons (8 Programmable buttons as standalone unit + 8 buttons with additional keypads) All call Key.Power LED, EVAC LED, status and fault LEDRJ45 Port CAT6 ConnectivityCable Distance: 500m from PA ProcessorFrequency response: 100 Hz to 16 kHzVoltage Range: 24 VDC +/- 2VCurrent Consumption <500mALED Indicators: Power/General fault/ Evacuation activeMonitored from PA ProcessorMicrophone Flex Length: 250mm MinimumOperating Temperature: 0 to 55 Degree CelsiusLoudspeakers |
| 455 | OD Supply, Installation, Testing and Commissioning of 2CX1.5 Samm Fire Rated copper Cable for Speaker with Related all Accessories. Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 456 | OD Supply, Installation, Testing and Commissioning of the 90MM Dia ELV Sleeve with related all accessories. |
| 457 | ACCESS CONTROL SYSTEM |
| 458 | OD Supply, Installation, Testing and Commissioning of the Card Reader. Card readers shall support contactless Smart Card technology/biometric system (as per client requirements). Card readers shall support the proximity smart cards compliant with ISO 14443 A or B Standard and ISO 15693.The reader shall include beepers, and red and green LEDs, to provide feedback to users. Readers must comply with at least IP54 environmental protection rating. All outdoor readers shall have a vandal resistant enclosure to IP66 rating. Complete as per approved make, manufacturer standard ,Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 459 | OD Supply, Installation, Testing and Commissioning of the Emergency Break Glass complete as per approved make, manufacturer standard, Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 460 | OD Supply, Installation, Testing and Commissioning of fully compliant,Retriggerable, Single gang or Narrow stile Push Button. The Operating Voltage of Push button shall be 12 or 24V DC Supply.(must be same voltage as the installed lock).complete as per approved make, manufacturer standard, Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 461 | OD Supply, Installation, Testing and Commissioning of Brushed Anodized Aluminium or Brushed Dark Bronze finish, fully compliant, Electro Magnetic Lock. The Electro Magnetic lock includes Adjustable keyhole mounting bracket with Convenient plug-in wiring terminals. Complete as per approved make, manufacturer standard, Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 462 | OD Supply, Installation, Testing and Commissioning offully compliant, Magnetic Door Contact. The housing design shall feature a rugged unibody construction with flexible ribbed sides for quick, secure installation without gluing. Complete as per approved make, manufacturer standard, Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 463 | OD Supply, Installation, Testing & Commissioning of IP based Single Door Reader Controller which supports all major reader technologies and biometrics on the same network.The Door controller should communicate over RS485/RS232 or Ethernet/LAN connection and store events.The same shall include fail safe/fail secure lock jumper, power supply, in-built battery backup or POE, complete as per approved make, manufacturer standard, Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 464 | OD Supply, Installation, Testing & Commissioning of IP based Two way Door Reader Controller which supports all major reader technologies and biometrics on the same network.The Door controller should communicate over RS485/RS232 or Ethernet/LAN connection and store events.The same shall include fail safe/fail secure lock jumper, power supply, in-built battery backup or POE, complete as per approved make, manufacturer standard, Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 465 | OD Supply and laying of armoured FRLS cable with saddles and accessories for ,complete as per approved make, manufacturer standard, Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 466 | 6 Core 1 Sq.mm Access control cable |
| 467 | 4 Core 1 Sq.mm Access control cable |
| 468 | 2 Core 1 Sq.mm Access control cable |
| 469 | OD Supply and Installation of 2MP Fixed Camera- 2MP IR IP H.265 Compact Dome Camera with 2.8mm Fixed Lens, PoE, SD Card Slot, Built-in Mic and 30m IR Support |
| 470 | OD Supply and Installation ofFixed Outdoor Bullet IP Camera Wheather Proof - 2MP IR IP H.265 Bullet Camera with 4mm Fixed Lens, PoE, SD Card Slot, Built-in Mic and 30m IR Support |
| 471 | OD Supply and Installation ofOutdoor PTZ IP Camera Wheather Proof- 2MP Starlight IR IP H.265 PTZ Dome Camera with 25X Optical Zoom, PoE+, WDR, SD Card Slot, Smart Analytics and 150m IR Support |
| 472 | OD Supply and Installation of Automatic Number Plate Recongnition Camera - 2MP IR IP H.265 Bullet Camera with 5~60mm Motorized Lens, LPR,PoE, WDR, SD Card Slot and 35m IR Support |
| 473 | OD Supply and Installation of NVR- 64Ch Embedded Network Video Recorder with 8 HDD Bays Supports 4K Cameras, HDMI, VGA, RAID, Smart Analytics and ONVIF. With minimum of 90 days recording ( biider need to consider the storage accordingly for the solution) |
| 474 | OD Preparation of constructed finished Manhole as per the drawings and as per local standards with size of800 (L) X 800 (W) X 800 (D)mm Manhole For ELV (Fire alarm, Public Address,Security,CCTV,Access Control, Telecom, Data) |
| 475 | OD Supply and Laying of 96MM uPVC HDPE pipe For ELV @ 600mm Depthfor Fire Alarm,PA,Security,CCTV& ACS, Telecom & DATA , with all its accessories complete as required.Complete as per approved make, manufacturer standard, Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 476 | OD Supply,Installation,Testing and Commissioning ofVideo Wall Panel.,Complete as per approved make, manufacturer standard, Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 477 | 1.21.2Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 478 | Supply and installation of GI Ceiling Trunking with Minimum 1.6mm Thickness. complete with accessories like, Junction boxes, Collars, Bends, Supports etc. ,Complete as per approved make, manufacturer standard, Technical Specification, drawings and as directed by Employer/Employer Representative. |
| 479 | 100X50mm GICeiling Trunking |
| 480 | 150X50mm GI Ceiling Trunking |
| 481 | 300X50mm GI Ceiling Trunking |
| 482 | OD Supply and Installation of Core Switch24 10/100/1000BASET ports+ 2 10GBASET ports + 4 10G SFP ports L3 Stackable Managed Switch loaded with 1000BaseLX SingleMode 10KM SFP Transceive |
| 483 | OD Supply and Installation of EdgeSwitch- 24 Port 10/100/1000with PoEwith4Ports Gigabit SFP Smart Managed Switchloaded with 2 Nos of1000BaseLX SingleMode 10KM SFP Transceive |
| 484 | OD Supply,Installation,Testing and Commissioning ofWireless LAN AccessPointswith Software |
| 485 | OD Supply,Installation,Testing and Commissioning of Gigabit Ethernet to Fiber Media Converter 10/100/1000 BaseT to 100/1000 BaseX SFP |
| 486 | Supply of Single RJ45 Outlet- Face Plate Plain 01 Port with Category 6A UTP Keystone Jack Tool Less |
| 487 | Supplyof Twin RJ45 Outlet - Face Plate Plain 02 Port with 2 nos of Category 6A UTP Keystone Jack Tool Less |
| 488 | CAT6 A UTP Cable - Category 6A U/UTP 4 Pair Cable PVC (Mtrs) |
| 489 | Patch Pannel24 Port Loaded with Category 6 UTP Patch Panel Blank Tool Less 24 Port andwith 6 UTP Keystone Jack Tool Less |
| 490 | Patch Cords 3 Mtr - Category 6A U/UTP Patch Cord LSZH 03m |
| 491 | Patch Cords 1 Mtr ategory 6A U/UTP Patch Cord LSZH 01m |
| 492 | Fibre Cable -06 Core OS2 SM Central Loose Tube Armoured External Cable |
| 493 | 24 Port Loaded LC LIU - Sliding Module Type Fibre Patch Panel Rack Mount with LC 3 Port Duplex Adaptor Plate 2 Nos and LC Singlemode Duplex Adapter 4 Nos |
| 494 | LC-LC Patch Cord- LC/PC-LC/PC Singlemode OS2 3m Duplex LSZH Patch Cord |
| 495 | CAT6A STP, PE External ( Mtrs) Category 6A S/FTP 4 Pair External Cable PE |
| 496 | Supply and Installation of 42”U 800 x 1000 Front glass & Rear Perforated Door Floor Standing Cabinet with 4 fan and PDU and acessorries for Control room |
| 497 | 9U/ 15U 800 x 800 Front glass & Rear Perforated Door wall mounted Cabinet with 2 fan |
| 498 | Booster Pump |
| 499 | OD Providing, Installing, Testing & Commissioning of electrical motor driven Booster Pump of Monoblock type capable to deliver 900LPM at 35MWC.The quoted rate shall include with pump panel and the pump shall be coupled to motor of suitable HP with speed of 2900RPM and complete set shall be mounted on common base frame as recommended by manufacturer, including all supports and the civil works completed by civil team. |
| 500 | OD Providing, Installing, testing and commissioningof C.I. flanged \"Y\" type Strainer shall have a removable bronze screen with 3 mm perforations and permanent magnet, suitable flanges, nuts, bolts, gaskets etc., and the Strainers shall be provided with isolating valves so that they may be cleaned without draining the entire system. with all arrangement of following size etc. complete as per Technical Specification, drawings and directed by Employer/Employer Representative.100mm nominal dia |
| 501 | OD Providing, Installing, testing and commissioningof Swing type Non-return valve shall be of cast iron with gunmetal seat, non-return valves shall be of flanged type. Spring-loaded valves shall not be used. The valves shall be suitable for a test pressure of 16 Kgs/cm².of following size.Provide hangers, supports, anchor, nuts and bolts, rollers, flanges, union, clamps, pipe markers. IS Approved etc., completeas per Technical Specification, drawings and directed by Employer/Employer Representative.100mm nominal dia |
| 502 | OD Providing, Installing, testing and commissioningof Cast iron Butterfly valves. The valves shall conform to IS 5312 and shall be CI construction, including nuts, bolts, washers, 3mm thick insertion rubber gasket complete as per the specifications. The valves shall be tested to a pressure of 16 Kg/sq.cm. Butterfly Valves shall be provide with hangers, supports, anchor, nuts and bolts, rollers, flanges, union, clamps, pipe markers, etc. IS Approved etc., as per Technical Specification, drawings and directed by Employer/Employer Representative. |
| 503 | 100mm nominal dia |
| 504 | 65mm nominal dia ( valve for sprinkler line ) |
| 505 | 16.8Providing, Installing, testing and commissioning in position the industrial type pressure gauges with gun metal / brass valves complete as required- 100 mm nominal dia |
| 506 | OD \"Providing, Installing, testing and commissioning of differentials type pressure switch for each type of pumps. It shall be factory calibrated and shall be employed for auto start/stop of pumps with suitable Needle Valve and necessary accessories etc., complete as per Technical Specification, drawings and directed by Employer/Employer Representative. |
| 507 | OD Providing, Installing, Testing and Commissioning of Air release valve with 20mm screwed inlet GM single acting air release valve on all high points in the system or as shown in the drawings, IS Approved etc., complete as per Technical Specification, drawings and directed by Employer/Employer Representative. |
| 508 | OD \"Providing, Installing, testing and commissioningof Bronze Body Ball valve witha pressure rating of 175 PSI, with all arrangement of following size. Provide hangers, supports, anchor, nuts and bolts, rollers, flanges, union, clamps, pipe markers, etc., IS Approved etc., completeas per Technical Specification, drawings and directed by Employer/Employer Representative.20 mm Dia |
| 509 | OD Providing, Installing, Testing and Commissioning of Heavy Grade GI Pipes (Class C) confirming to IS:3589 for 150mm dia above & IS:1239 part-I for up to 150mm dia with malleable specials confirming to IS:1239 part-II, such as Tees, Elbows, Check nut, Unions, Flanges, Nipples etc. Including treading, cutting, V groove welding and each support shall be as per chart that is CPWD clause 7.13 and provide anchor or channel supports for the pipes traveling above ground and painting the exposed GI. pipes with one coat of etching primer with two coats of synthetic enamel paint of approved colour/shade. The quoted rate shall also include for chasing / chipping walls, making bore holes in walls / floor and making them good with filler material and finished in cement mortar etc. complete. Make: ISI Approved.Vendor shall Providing and install fittings, pipe mounting &all required supports for piping shall be as per IS compliance. At least 10 percent of all the welded joints shall be radio graphically tested and half of the joints radio graphed shall be the ‘field joints complete etc. as per Technical Specification, drawings and directed by Employer/Employer Representative. |
| 510 | 100mm nominal dia |
| 511 | 80mm nominal dia |
| 512 | OD \"Providing, Installing, Testing and Commissioning of Heavy Grade GI Pipes (Class C) confirming to IS:1239 with malleable specials confirming to IS:1239, such as Tees, Elbows, Check nut, Unions, Flanges, Nipples etc. Including treading, cutting, V groove welding and3 meters provide anchor or channel supports supports for the pipes traveling above & Under ground and painting the exposed M.S. pipes with two coat of etching primer with 4mm anti corrosive wrapped . The quoted rate shall also include for chasing / chipping walls, making bore holes in walls / floor and making them good with filler material and finished in cement mortar, excavation, backfilling suitable masonry support, and concreate anchor blocks, pedestal where ever required etc. the pipe shall be laid not less than one meter below the ground level complete. Make: ISI Approved. Vendor shall Providing and install fittings, pipe mounting & all required supports for piping shall be as per IS compliance. At least 10 percent of all the welded joints shall be radio graphically tested and half of the joints radio graphed shall be the ‘field joints. Under ground pipe shall be wrapped as per IS A10221 and in masonry culverts with removable covers of incombustible construction according to the provisions given in IS 5822,All underground pipes and fittings shall be cleaned by rough cloth. The first coat of bituminous paint shall be applied, over which 400-micron polyethylene sheet of suitable width is to be wrapped spirally by overlapping at least by 15mm. Similarly, a second coat of bituminous paint shall be applied over which PVC wrapping followed by a second layer of PVC sheet wrapping. It is important to ensure that PVC sheet wrapping joints, of both the layers, are staggered. Hume pipes to be considered in road crossing,complete etc. as per Technical Specification, drawings and directed by Employer/Employer Representative.100mm nominal dia |
| 513 | ODProviding, Installing, testing and commissioning ofSingle headed gunmetal fire hydrant valve (Landing Valve) confirm to IS: 5290with 80 mm N.B. flanged inlet, brass spindle, 63 mm Dia instantaneous type Gun Metalconfirm to IS: 901 complete with hand wheel, quick coupling, spring, and blank cap with chain. Including tapping from wet riser complete etc. as per Technical Specification, drawings and directed by Employer/Employer Representative.As per specification |
| 514 | OD Providing, Installing, testing and commissioning ofRRL Hose pipe, 2 No\"s 63 mm dia and15 mtr long confirm to IS 636 suitable for bursting pressure not less than 35.7 Kg/Sqcm. type A with Gunmetal heavy duty instantaneous type coupling (Pair male & female parts), with branch pipe & nozzle complete as per Technical Specification, drawings and directed by Client/PMC Engineer\" |
| 515 | ODProviding, Installing, Testing & Commissioning of1 no. SS short Branch Pipe with gun metal nozzle. Branch pipes shall be of gun metal to fit into the instantaneous coupling. Nozzle shall be of spray or fog type of diameter of not less than 16 mm and not more than 25mm. Branch pipe and nozzle shall be of instantaneous pattern. |
| 516 | OD Providing, Installing, Testing & Commissioning of Hose Reel Drum of swinging type with 19mm dia rubber hose of 30mtrs. length with with gunmetal nozzles and control valve, shut off valve, all mounted on a circular hose reel drum of mild steel construction and cast-iron bracket complete. Quoted rate includes Tapping from Riser with 19 mm pipe & a Gun metal chrome finished Ball valves with crimpling collar on both sides, required length of Connection Hose Pipe & all other required accessories to complete the job |
| 517 | OD Providing and Installing Fire Hose Cabinet and frame, fabricated out of M.S. sheet of 16 swg and spray painted to scarlet red colour with word “FIRE”. shutter size shall be up to 900mm x 1200 mm min. & fixed with 4 mm thick Glass, suitable Rubber beading and Locking arrangement. Quoted rate shall be including all fasteners etc, and complete shutter shall be powder coated of approved colour both inside and outside .The hose cabinet shall be of suitable size to accommodate the following: -o Landing valves (Single Headed).o 63 mm hose pipe (2 lengths of 15 metres each).o Branch pipe and nozzles (one set).o Two keys of break glass recess for keys. |
| 518 | OD \"Providing, Installing, Testing and Commissioning of 2-Way Fire Brigade Inlet connection with 2 nos. 63 mm dia instantaneous coupling type arranged on 100 mm dia. Pipe manifold and connected to hydrant ring main. Quoted rate shall be included withinlets with caps and chains complete with non-return valvehoused in a 16-gauge MS cabinet with 4mm thick glass fronted door. The cabinet shall be sized for recessmounting. drain valve, blank cap, chain, seat washer and fittings such as suitable flanges, nuts, bolts, gaskets etc. complete. Make: IS Approved etc., complete as per Technical Specification, drawings and directed by Employer/Employer Representative. |
| 519 | OD \"Providing, Installing, Testing and Commissioning of Heavy Grade GI Pipes (Class C) confirming to IS:3589 for 150mm dia above & IS:1239 part-I for up to 150mm dia with malleable specials confirming to IS:1239 part-II, such as Tees, Elbows, Check nut, Unions, Flanges, Nipples etc. Including treading, cutting, V groove welding and each support shall be as per chart that is CPWD clause 7.13 and provide anchor or channel supports for the pipes traveling above ground and painting the exposed GI. pipes with one coat of etching primer with two coats of synthetic enamel paint of approved colour/shade. The quoted rate shall also include for chasing / chipping walls, making bore holes in walls / floor and making them good with filler material and finished in cement mortar etc. complete. Make: ISI Approved.Vendor shall Providing and install fittings, pipe mounting &all required supports for piping shall be as per IS compliance. At least 10 percent of all the welded joints shall be radio graphically tested and half of the joints radio graphed shall be the ‘field joints complete etc. as per Technical Specification, drawings and directed by Employer/Employer Representative. |
| 520 | OD Providing and Installing G.I. pipes complete with G.I. fittings and clamps, including cutting and making good the walls etc. Internal work- Exposed on wall 65 mm dia nominal bore |
| 521 | 18.10.6Providing and Installing G.I. pipes complete with G.I. fittings and clamps, including cutting and making good the walls etc. Internal work- Exposed on wall 50 mm dia nominal bore |
| 522 | 18.10.5Providing and Installing G.I. pipes complete with G.I. fittings and clamps, including cutting and making good the walls etc. Internal work- Exposed on wall 40 mm dia nominal bore |
| 523 | 18.10.4Providing and Installing G.I. pipes complete with G.I. fittings and clamps, including cutting and making good the walls etc. Internal work- Exposed on wall 32 mm dia nominal bore |
| 524 | 18.10.3Providing and Installing G.I. pipes complete with G.I. fittings and clamps, including cutting and making good the walls etc. Internal work- Exposed on wall 25 mm dia nominal bore |
| 525 | OD Painting G.I pipes and fittings with synthetic enamel white paint with two coats over a ready mixed priming coat, both of approved quality for new work: 65 mm dia nominal bore |
| 526 | OD Painting G.I pipes and fittings with synthetic enamel redpaint with two coats over a ready mixed priming coat, both of approved quality for new work: 50 mm dia nominal bore |
| 527 | OD Painting G.I pipes and fittings with synthetic enamel red paint with two coats over a ready mixed priming coat, both of approved quality for new work: 40 mm dia nominal bore |
| 528 | OD Painting G.I pipes and fittings with synthetic enamel red paint with two coats over a ready mixed priming coat, both of approved quality for new work:32 mm dia nominal bore |
| 529 | ODPainting G.I pipes and fittings with synthetic enamel red paint with two coats over a ready mixed priming coat, both of approved quality for new work\"s 25 mm dia nominal bore |
| 530 | OD Providing, Installing, testing & commissioning of pendent sprinkler bulb with 15mm screwed end of 79 deg C. temperature rating, K 80and orifice shall not be less than 6mm. Sprinklers shall beFM approved with Chrome finished with required all accessories as per Technical Specification, drawings and directed by Employer/Employer Representative. |
| 531 | OD \"Providing, Installing, Testing and Commissioning of Flow switch on sprinkler distribution header on each floor and shall be connected to Annunciation panel through cable. Cable shall be measured separately. The quoted rate shall include cover, pipe saddle, plastic vane, saddle gasket, U-bolts, supports etc. Make: FM Approved \"65 mm nominal dia |
| 532 | OD\"Providing, Installing, testing and commissioning of Test and Drain valve with 3-positions consist of OFF, TEST and DRAIN. Pressure rating shall be 300 PSI, Threaded to Grooved end.Provide hangers, supports, anchor, nuts and bolts, rollers, flanges, union, clamps, pipe markers, etc., FM Approved etc.,\"25 mm Nominal dia |
| 533 | OD Providing, Dry chemical powder ABC type fire extinguisher with initial filling in brand new cylinder with powder coated finish, fitted with gun metal union, high pressure gas cartridge, discharge hose, wall mounting bracket etc. Complete conforming to IS 15683 near parking area, Integrated ,kitchen, Employee/customer parking as per technical specification, drawings, directed by client/ client representative etc.\"6 kg |
| 534 | OD \"Providing, Installing, Testing & Commissioning of Carbon Dioxide type fire extinguisher with initial filling in brand new cylinder with powder coated finish, fitted with gun metal union, high pressure gas cartridge, discharge hose, wall mounting bracket etc, confirming conforming to IS 2878, located in Electrical room,Cafeteria, all entry-exit points., complete as per technical specification, drawings, directed by client/ client representative etc. |
| 535 | 2kg |
| 536 | 4.5 kg |
| 537 | OD \"Providing, Installing, Testing & Commissioning of Mechanical Foam Extinguisher with initial filling in brand new cylinder with powder coated finish, fitted with gun metal union, high pressure gas cartridge, discharge hose, wall mounting bracket etc, confirming to IS:15683, located near each staircaselanding. complete as per technical specification, drawings, directed by client/ client representative etc.\"9ltrs Mechanical foam |
| 538 | OD Providing & Installing 2 Nos of Fire Buckets of 24 gauge galvanized sheet standard 9 lts capacity and ofround bottom type enamel painted, white inside & Red out side and Letter \"FIRE\" in black with stand for 2 bucket, complete as per technical specification, drawings, directed by client/ client representative etc. |
| 539 | Providing and installing in position the following type of sign boards made out of 3mm thick \"Opaque\" PVC foam board with computer cut, PVC non-reflective self adhesive vinyl painted foam board, complete with mirror fasteners. |
| 540 | OD Signage with printed\"ASSEMBLY POINT\" NO SMOKING, FIRE BUCKET, NO Entry, DANGER of 1.5cm height letters in red with white back ground. The size of the board shall be 25cm x 30 cm and shall be fixed at the height of 2 mts. from finished floor. Exits shall be clearly visible and the route to reach the exits shall be clearly marked and signs posted to guid the occupants of the floor concerned. Complete as per Technical Specification, drawings and directed by Client/PMC Engineer\" NOTE: This provision shall not apply to A-2 and A-4 occupancies less than 15 m in heightas per NBC.(Site Escape Plan) |
| 541 | OD Floor identification signage ( i.e., GROUND FLOOR …etc.) at each stair enclosure on every floor, indicating the floor number in words, lettering size shall be 7.5 cm with contrasting colour from back ground. Size shall be 15cm x 60cm. |
| 542 | OD Providing, Installing of Fire Barrier Sealant FD 150+ shall be a one-component, ready-to-use, gun-grade, elastomeric sealant. All wall penetration shall be sealed with 2 hours fire rating. The sealant shall be listed by independent test agencies such as Intertek or UL. Fire Barrier Sealant FD 150+ shall be tested to and pass the criteria of ASTM E 814 (UL 1479) Standard Test Method for Fire Tests of Penetration Firestop Systems, ASTM E 1966 (UL 2079) Standard Test Method for Fire Resistive Joint Systems and CAN/ULC-S115 Standard Method of Fire Tests of Firestop Systems. Fire Barrier Sealant FD 150+ shall meet the requirements of the IBC, IRC, IFC, IPC, IMC, NFPA 5000, NEC (NFPA 70), NFPA 101 and NBCC. etc. .complete as per Technical Specification, drawings and directed by Employer/Employer Representative. |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy