| 1 | M&L for point wiring for one 5 pin socket outlet 15 Amps on independent board with 2.5 Sqmm copper cable FRLS & 2.5 Sqmm FRLScopper cable for earth continuity wire complete all as specified and as directed & making good the disturbed surface to match with existing surface/wall complete all as specified and as directed. (For power point) |
| 2 | All as per Item No 1 here-in-before but for one 5 pin socket outlet 15 Amps on independent board with 4 Sqmm copper cable FRLS & 4 Sqmm FRLScopper cable for earth continuity wire complete all as specified and as directed (For AC Point). |
| 3 | S&F for switch socket combination 5 Pin, 6/15 Amp universal complete all as specified and as directed. |
| 4 | S&Fsheet metal enclosures for DB’s double door suitable for mounting of MCB’s/Isolators, 240 Volt, SPN, 4 way with built in bus bar complete including making good the distrubed surface and matching with existing colour complete all as specified and asdirected. |
| 5 | S&F VTPN distribution board with provision of MCCB as incommer,double door suitable for mounting MCB\"s/Isolators, 240 Volt,4 way with built in160A rated bus bar and with out MCCBcomplete after taking down old unserviceable DB\"s and including making good the distrubed surface and matching with existing colour complete all as specified and as directed. |
| 6 | M&L forMCCB, 4P, 415V, overload adjustable 0.63 - 0.8-1 x in short circuit fixed 63 Amps breaking capacity 16KA complete all as specified and as directed. |
| 7 | M & L for MCB, SPN, 240 V, 40 to 63A Amps, and ‘C’ series breaking capacity 10 KA complete ISI marked , all as specified and as directed. |
| 8 | M & L for MCB, SP, 240V, 6 to 32 Amps and \" C \" series breaking capacity 10 KA ISI markedcomplete, all as specified and as directed. |
| 9 | S&F metal clad box enclosure with socket plugtop and MCB SP 20 Amp flush of 240v mounting enclosure with 2 pin earth plug socket complete all as directed |
| 10 | Supply and fixingsub main wiring with two run of single core 6 Sqmm PVC insulated unsheathed stranded cable (FRLS) copper conductor drawn through PVC casing caping with all fittings including 6.0 sq mm PVC insulated unsheathed single core copper conductor as earth wire and including PVC casing caping and including PVC casing caping all as specified and as directed.Note : (i) Two run of single core cable 6.0 sq mm and one run earth wire 6.0 sq mm will be measured as one length. |
| 11 | M&L for earthing complete with galvanised steel earth plate electrode 600x600x 6mm thick burried in ground (earth pit not less than 2.25 m deep below ground level0with top edge of the plate not less than 1.5 m below normal ground level, connected to GI strip 25x4 mm as earthing lead by means of bolts, nuts, check nuts, and washers of GI or steel, GI strip protected by 40 mm bore medium grade GI pipe and other end connected to earth test point as directed including funnel with watering pipe 20 mm bore light grade GI, wire mesh charcoal or coke common salt laid in altrnative layer of 15 cm (complete thickness) all round the earth electrode, concrete earth pit in PCC(1:3:6) type C-1, 50 mm thick pre-cast RCC(1:2:4) type B-1 normally mix cover slab reinforced with in 8 mm dia TMT bar 10 cm C/C both ways and single handle of 10 mm dia round bar including necessary excavation, earth work etc. in soft/loose/hard soil and disposal of soil to a distance n.exc 50 m and necessry testing on completion all as shown in electrical plate No 3 MES schedule part-I complete all as specified and as directed. |