| 1 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. |
| 2 | Earthingwith G.I. earth pipe4.5mtr long x 40mm dia including accessories and providing masonary enclosure with cover platehaving locking arrangement and watering pipe etc. withcharcoalor coke and salt complete as required. |
| 3 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 4 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required |
| 5 | Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.a) 200 Amp, 16 KA, TPMCCB |
| 6 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. A) Above 35 sq. mm and upto 95 sq. mm |
| 7 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. A) Above 35 sq. mm and upto 95 sq. mm |
| 8 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. A) Above 35 sq. mm and upto 95 sq. mm |
| 9 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. A) Above 95 sq. mm and upto 185 sq. mm |
| 10 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. A) Above 95 sq. mm and upto 185 sq. mm |
| 11 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. A) Above 95 sq. mm and upto 185 sq. mm |
| 12 | Supplying, Installation, testing and commissioning of heavy duty exhaust fan, metalic body 230V, 300 mmsweep,single phase including making the hole to suit the size of the above fan, making good the damage i/c P/F louver and shutter complete with frame for exhaust fan of size connections, testing and commissioning etc as required. |
| 13 | Supplying, Installation, testing and commissioning of heavy duty exhaust fan, metalic body 230V, 380 mmsweep, single phase including making the hole to suit the size of the above fan, making good the damage i/c P/F louver and shutter complete with frame for exhaust fan of size connections,testing and commissioning etc as required.Make - Havells (Turboforce;FHEHDSPDB150) or equivalent specification make in Crompton/Bajaj/Orient. |
| 14 | Providing and fixing of 20 Watt, 6500K LED batten lighting fixture with extruded polycarbonate directly on ceiling/ wall, including connection with connector, testing and dismantling the existing complete etc. as required. Cat no LHEXACP7IN1W020 Havells(E-Lite LED Pride Plus Neo) make or equivalent model & specification in philips/Crompton-LDLSR-20-CDL/Bajaj |
| 15 | Providing and fixing of 60 watt LED Flood lightmade for energy saving, long life die-cast aluminium IP66 directly on the surface/wall including making connection, testing commissioning etc as required. Make Havells (JETA QUANTO PLUS) equivalent model and specification in Crompton/Bajaj/Philips. |
| 16 | Providing and fixing of maintenance free, dust and moisture free,Engineering plastic injection moding Cooler Body, Cooling pad- 4D honey combo cellulose wet pad with anti bacterial resins fibre body ducting air cooler of following specification : Air flow 18000 CMH, Cooling area 2500 sqft (without ducting), Motor-Inverter high torque motor 380 to 415 volt/50 Hz, 1.1 Kw ( Three phase turbo axial fan) with 1400 RPM, , Air pressure - 180 P.A., Water tank capacity - 35 Ltr, Air outlet size - 670 mm x 670 mm,etc as per direction of engineer in charge. Make - Sky air cooler model -Merqury or equivalent make and model in Symphony, Maharaja, Cool wind complete as per requirement or as decided by Engg-In-Charge. |
| 17 | Providing and fixing of 20 mm nominal outer dia chlorinated polyvinyl chloride (CPVC) pipes, having thermal stability for hot and cold water supply including all CPVC plains& brass threaded fittings i/c jointing of pipes & fittings with one step CPVC solvant cement, trenching, refilling & testing of joints complete. make- Ashirvad/vectus/Astral or as per direction of Engg. incharge. |
| 18 | Providing and placing of double layer polyethylene (PVC) water storage tank (ISI Marked) of 500 Ltr capacity with cover and suitable lacking arrangement and making necessary holes for inlet , outlet and overflow pipes but without fittings and the base support for tank.Make- Sintex/Vectus/Frontline or as per direction of Engg. incharge. |
| 19 | Supplying and fixing 0.5 HP centrifugal monoblock motor to supplying water from main water tank to ducting cooler with following specification, make Havells, Model No. -CMM05, size-25x25, HP/KW -0.5/0.37,Head range- 10-15 mtrs, Discharge range-6000 - 2100 L/H, or equivalent make in Crompton/CRI or As per direction of Engg- In -Charge |
| 20 | Suppling and making of duct through 24 Gauge GSS sheet of suitable size ducting will be insulated through high quality insulating material etc as required as per direction of Engineer- in- Charge. |
| 21 | Supplying and fixing of the heavy duty and manualy air controling louvers/ shutters complete with matelic frame as per site requirement. |
| 22 | Providing and fixing of angle iron frame of suitable size for placing of duct cooler made out of 50 mm x 50 mm x 5 mm thick angle iron including making of stand as per site requirement and installation of duct cooler, as per direction of Engg- in -Charge, Make - Jindal/TATA/ equivalent ISI Marked. |
| 23 | SITC of various sizes water protected outdoor (Water proof)huttype compartmentalized type double door cubical panelboth side opening havingdepth up to 600 mmsuitable for 415 Volt, 3 phases, 50 Hz made out of 2mm thick CRCA sheet with required hardware duly painted with powder coated .Panel having separate detachable gland plate, end termination as per cable of size,angle iron base frame made out of 50mmx50mmx5mm angle iron of suitable size of the feeder pillar (minimum height 60cm), hinged door, both side opening with locking arrangement, earth bar/stud, led pilot light for phase indicator (R,Y,B) on top, 400A/415V 4 strip aluminum bus bar duly PVC sleeved, connection inter–connection with 25% extra current carrying capacity busbars to MCCBs spreader links and with solid copper conductor cable 10 sqmm/ solid aluminium rodfor connection toMCBs and heavy duty connectors of required current carrying capacity to be fixed back side including incoming/Outgoing cables connection for three and single phaseMCBs where as required, testing on loadand marking of location for incoming and out going distribution i/c grouting the legs in existing floor with 1:3:6 cement concrete foundation and dsimantling the existing panel, incoming/outgoing cable connections etc complete as required i/c dismentling the existing feeder pillar and UG cable. (Panel should beas per design &drawing approved by Engg in charge).LED light min 5 watt with on/off switch to be provided in the panel. |
| 24 | Providing And Fixing Of100 Amp MCCB three pole Breaking Capacity10 ka with spreader links for ACThreephase, 415 vIcs=100% Icu, EZC Fixed thermal Magnetic trip unit (TMD) as per details specificationin the LT panel and making inter connections with busbar as per the detail specifications mentioned inabove new panel item etc as required. |