| 1 | NOTE: Schedule ‘A’ Part Iunder Ser No. 1 is not Prepriced by MES and prepriced rates indicated as 0.00 under column no. 5 signifies this fact only (ie. TO BE QUOTED BY THE CONTRACTOR). Structural design of buildings/ structures covered under this schedule is to be done by the contractor. |
| 2 | Provision of OFFICER\"S MESS BLOCK INCLUDING VERANDAH AND CONNECTING PASSAGE in RCC framed structure including structural designing complete all as shown in architectural drawings and schedule of finishes and as specified and directed. |
| 3 | NOTE: Schedule ‘A’ Part IIto VIII are under Ser No. 2 to 8 are Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only. |
| 4 | Lump sum price worked out for DEMOLITION/ DISMANTLING as listed in Sch \"A’ Part II |
| 5 | Lump sum price worked out for EXCAVATION AND EARTHWORK as listed in Sch \"A’ Part III |
| 6 | Lump sum price worked out for INTERNAL ELECTRIFICATION as listed in Sch \"A’ Part IV |
| 7 | Lump sum price worked out for PATH as listed in Sch \"A’ Part V |
| 8 | Lump sum price worked out for AREA DRAINAGEas listed in Sch \"A’Part VI |
| 9 | Lump sum price worked out for SEWAGE DISPOSAL as listed in Sch \"A’Part VII |
| 10 | Lump sum price worked out for EXTERNAL ELECTRIFICATION as listed in Sch \"A’Part VIII |
| 11 | SCHEDULE `A\" PART-IX MISCELLANEOUS ITEMS(Note for items 9 to 24: The contractor shall quote his rate for each of these items separately. The estimated rate is left blank since the same is not prepriced by MES) |
| 12 | INTERNAL ELECTRIFICATION |
| 13 | Taking down existing split A/C indoor and outdoor unit of capacity 1.5/ 2.0 TRcomplete, including fixture and fittings such as metal plates, copper pipe, out door stand etc. removing materials and depositing to MES store for keeping in safe custody and refixing the same as per direction of Engineer-in-Charge complete all as specified and directed. |
| 14 | Taking down old LT cable with junction boxes and DBs etc. and depositIng to MES store for keeping in safe custody and making good disturbed surfaces of walls, floors, etc. complete all as specified and directed. |
| 15 | Supply and fix wall mounting fans 400 mm sweep, single phase, 240 volts complete all as specified and directed. |
| 16 | Supply and fix vertical load line TPN DB double door complete encloser type (TPN) six way 415 Volts with IP 54 protection complete, including the following: Incoming side:(a) MCCB of 160 amps 4 pole 25 KA, 50 Hz Outgoing side:(a) 40 Amp MCB TP 10 KA, C-Series- 06 nos for outgoingincluding complete grouting on wall with nut and bolt properly and as directed by Engr-In-Charge. |
| 17 | Supply and fix vertical load line TPN DB double door complete encloser type (TPN) six way 415 Volts with IP 85 protection complete, including the following: Incoming side:(a) MCCB of 160 amps 4 pole 25 KA, 50 Hz Outgoing side:(a) 8-32 Amps MCB SP10 KA, C-series - 12 Nos(b) 40 Amp MCB TP 10 KA, C-Series- 02 nos for outgoingincluding complete grouting on wall with nut and bolt properly and as directed by Engr-In-Charge. |
| 18 | Supply and fix SPN DB double door complete encloser type (SPN) Eight way of capacity 220-230 Volts with IP 65 protection complete, including provision of incoming MCB SPN of capacity 40 Amp and out going SP- 6-32 Amp 6 nos complete including complete grouting on wall with nut and bolt properly and as directed by Engr-In-Charge. |
| 19 | Supply and fix integral Bollard light cast aluminium housing aluminium louvers, opal acrylic diffuser with IP 65 with LED 10 Watt including driver complete all as specified and directed.Note: Light should have minimum lumen output of 910 lumens and minimum system efficiancy>100 lumen/watt., PF>0.90. The light should have a colour temp of 6500 K & CRI >80 of cool white and mounted on necessary steel fabricated stand upto 400 mm length including in ground PCC work (1x1) in feet complete. |
| 20 | Supply, installation, commisioning and testing factory made and tested, CPRI approved,LT feeder pillar box (KIOSK) of size 3(L) x 3(H) x 1.5(W) in feet, outdoor type, mounted on rigid angle iron frame, suitable size, having independent compartment for insulated aluminium bus bar, incoming feeder and each out going feeder, dust and vermin proof, factory made, fabricated out of not less than 3.15 mm thick CRCA sheet with IP-65 protection suitable for 3 Phase 415 volts 50 Hz, AC supply, bus bar chamber with aluminium bus bar of400 Amp rating for 3 phase and neutal4 wire system duly insulated with heat shrinkable type sleeves as per colour code, supported on epoxy insulators- 01 Set, Cable glands with independent plates at bottom for each outgoing and incoming cables in cable alley and complete board painted with powder coating in siemens grey colour front and rear opening type with double door shutter and locking arrangement including provision of 65 mm Godrej (freedom) lock with 2 keys, suitable aprons for cable entry/ exist, including taking down and refixing of exisiting cable properly with lugs and thimable all as approved andcomprising as under: |
| 21 | INCOMING SIDE:(a) MCCB 4 Pole, current rating 63 Amp, with Thermal Magnetic release, breaking capacity 25 kA at 415V, 50Hz- 01 Nos.(b) Digital voltmeter with selector switch- 01 set. (c) DigitalAmp meter with selector switch- 01 set. OUTGOING SIDE:(a) MCB SPN 32 Amp 10 KA \"C\" Series- 04 Nos(b) Angle iron base frame for above panel, total leg height 450 mm and grouting in side PCC 150 mm legs and made out of ISA 50 x 50 x 6 mm thick angle iron duly painted - 01 No.Note: Necessary excavation and required PCC work 1:3:6 (40 mm graded aggregate) Type C2 for foundation of angle iron legs frame shall be deemed to be included in quoted rates. |
| 22 | Supply and fix SPN DB double door complete encloser type (SPN) four way of capacity 220-230 Volts with IP 65 protection complete, including provision of incoming MCB SPN of capacity 32 Amp - 01 Nos and out going SP- 10 Amp -2 Nos complete including complete grouting on wall with nut and bolt properly and complete all as specified and as directed |
| 23 | EXTERNAL ELECTRIFICATION |
| 24 | Boring of holes under road, pavement, hardstanding using trenchless technology using manual technology incl HDPE pipe of 150mm dia suitable for 0.4 Mpa working pressurecomplete all as specified and directed. |
| 25 | M & L forDWC pipe laying in trenches/under floors/on walls for protection of UGcables of 110mm OD, complete with coupler and connected accessories all as specified and directedNote : Cutting of floor/road and making the surface good with PCC type B1 1:2:4 (20mm graded aggregate) isdeemed to be included in the Item rate. |
| 26 | M & L forDWC pipe laying in trenches/under floors/on walls for protection of UGcables of 90mm OD, complete with coupler and connected accessories all as specified and directedNote : Cutting of floor/road and making the surface good with PCC type B1 1:2:4 (20mm graded aggregate) isdeemed to be included in the Item rate. |
| 27 | Supply, installation, commisioning and testing factory made and tested, CPRI approved, LT feeder pillar box (KIOSK) of size 3 (L) x 3 (H) x 1.5 (W) in feet, outdoor type, mounted on rigid angle iron frame of suitable size (50 x 50 x 8mm), having independent compartment for insulated aluminium bus bar, incoming feeder and each outgoing feeder, dust and vermin proof, factory made, fabricated out of not less than 3.15 mm thick CRCA sheet suitable for 3 phase 415 volts 50 Hz AC supply, bus bar chamber with aluminium bus bar of 1200 Amp rating for 3 phase and neutral 4 wire system duly insulated with heat shrikable type sleeves as per colour code, supported on epoxy insulators - 01 set, cable glands with independent plates at bottom for each outgoing and incoming cable in cable alley and complete board painted with powder coating in siemens grey colour front and rear opening type with double door shutter and locking arrangement including provision of 65 mm Godrej (freedom) lock with 2 keys, suitable aprons for cable entry/ exit, necessary excavation as required and PCC 1:3:6 (40 mm graded aggregate) type C2 for foundation for angle iron leg frame work including fixing of existing cable properly with lugs and thimble complete all as specified and approved and comprising following accessories: |
| 28 | INCOMING SIDE:(i) AI bus bar 1200 Amp cap- 1 set (set of four strips)(ii) ACB 630 Amp 415V TPN 50 KA- 1 no. (incoming)(iii) Digital voltmeter 0- 500 V- 1 no.(iv) Digital amperemeter 0- 1000 A- 1 no.(v) Indicator lamp LED type R, Y, B - 3 no.s(vi) Change Over Switch On load 630 A- 1 no.OUTGOING SIDE:(i) MCCB 500 Amp, 415 V, 4 pole, 36 KA with spreader links- 2 no.(ii) Space for MCCB 250 Amp, 4 pole- 1 no.(iii) MCCB 400 Amp, 35 KA, 4 pole- 1 no.s (for APFC) |
| 29 | Supply, installation, commisioning and testing factory made and tested, CPRI approved, LT feeder pillar box (KIOSK) of size 3 (L) x 3 (H) x 1.5 (W) in feet, outdoor type, mounted on rigid angle iron frame of suitable size (50 x 50 x 8mm), having independent compartment for insulated aluminium bus bar, incoming feeder and each outgoing feeder, dust and vermin proof, factory made, fabricated out of not less than 3.0 mm thick CRCA sheet suitable for 3 phase 415 volts 50 Hz AC supply, bus bar chamber with aluminium bus bar of 400 Amp rating for 3 phase and neutral 4 wire system duly insulated with heat shrikable type sleeves as per colour code, supported on epoxy insulators - 01 set, cable glands with independent plates at bottom for each outgoing and incoming cable in cable alley and complete board painted with powder coating in siemens grey colour front and rear opening type with double door shutter and locking arrangement including provision of 65 mm Godrej (freedom) lock with 2 keys, suitable aprons for cable entry/ exit, necessary excavation as required and PCC 1:3:6 (40 mm graded aggregate) type C2 for foundation for angle iron leg frame work including fixing of existing cable properly with lugs and thimble complete all as specified and approved and comprising following accessories: |
| 30 | INCOMING SIDE:(i) AI bus bar 800 Amp cap- 1 set (set of four strips)(ii) On load Change Over Switch 400 Amp cap- 1 no.(iii) MCCB 500 Amp, 415 V TPN 35 KA- 1 no.(iv) Digital voltmeter 0- 500 V- 1 no.(v) Digital amperemeter 0- 500 A- 1 no.(vi) Indicator lamp LED type R, Y, B - 3 no.sOUTGOING SIDE:(i) MCCB 100 Amp, 4 pole, 25 KA with spreader links- 2 no.s(ii) MCCB 200 Amps, 4 Pole, 35 KA with spreader links - 1 Nos(iii) MCCB 125 Amps, 4 Pole, 35 KA with spreader links - 1 Nos |
| 31 | Supply and Installation, testing and commissioning of Auto Power factor improvement capacitor panel outdoor type having aggregate capacity 250 KVAR in 7 stage with micro processor based control, factory made indoor type, platform mounted, suitable for 440 volts 3 Phase 4 wire, 50 Hz AC supply system, having duly insuated copper bus bars, dust and vermin proof, IP 54 class protection and made of 1.6mm CRCA MS sheet and 40x40x6mm thick angle iron frame work, fixed on PCC, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door shutter and locking arrangement (incl provn of 65mm Godrej (Navtal) lock with 2keys , internal wiring with PVC insulated, solid copper conductor, FRLS cables, IS -694 marked of adequate size but not less than 2.5 sqmm and comprising of followings ;-(i) Power factor corrector relay 7 stage Microprocessor based, modular type, intelligent thyristor switch module (VTSM) type APFC relay capable of having auto operation to maintain power factor between 0.85 to 0.99 with digital indication of power factor, preset parameters and having in built capability of indication and elimination of defective capacitor steps - 01 Nos |
| 32 | (ii) Power Capacitor MPP-H ype of under mentioned capacity :(a) 50 KVAR - 4 Nos(b) 15 KVAR - 1 Nos(c)25 KVAR-1 Nos(d)10 KVAR-1 Nos(iii) Main Incoming MCCB 250 Amp, 35 KA, 415 V, 4 Pole, 50 Hz -01 Nos(iv) VTSM-10 of 3 Phase capacitor bank 10 KVAR - 01 Nos(v) VTSM-15 of 3 Phase capacitor bank 15 KVAR - 01 Nos(vi) VTSM-25 of 3 Phase capacitor bank 25 KVAR - 01 Nos(vii) VTSM-50 of 3 Phase capacitor bank 50 KVAR - 04 Nos(viii) MCB TP 63 Amp - 02 Nos (ix) MCB TP 32 Amp - 02 Nos (x) MCB TP 25 Amp - 01 Nos(xi) MCB TP 20 Amp - 01 Nos(xii) MCB TP 10 Amp - 01 Nos(xiii) Protection Fuse 16 Amp HRC type(xiv) Auto/Manual selector switch(xv) ON-OFF Push button(xvi) Aux, contactor 4 Nos+4NC of L & T or equivalent - 7 Set |
| 33 | Supply and fix chain link fencing, MS galvanised, of any size and shape, for transformer protection with clear distance around transformer, with two side opening, including excavation, MS angle iron posts, drilling holes, fixing with nuts and bolts or welding and applying two coats synthetic enamel paint to all steel surfaces complete all as specified and directed. |
| 34 | NOTE: Amount of credit of Rs. 28,300.00 for retrieved materials is mentioned in schedule of credit on Srl Page No. 52 of tender documents in pdf form which will be deducted offline while acceptance of tender. |