| 1 | Supply and replacement, installation, testing & commissioning of addressable micro processor based 2 wire fault tolerant loop, required loop net workable type Single loop (each loop accessing maximum 99 detectors and 99 modules) fire alarm/detection control panel.The panel shall be able to give location of all fire/fault signal with address.The panel shall have rectifier, loop cards,LCD display unit to indicate Fire/Fault signal with address.The panel shall have a built in power supply and battery charger alongwith maintenance freeSMF lead acid batteries as per manufacturers design with battery charger complete as required and as per specifications duly approved by EN 54 complete including making connections all as specified and directed by Engr-in-Charge. Make :- Morley-IAS by Honeywellmodel Name/Number. DXc2/ 714-001-225 or Bosch model No. FPA-1000-V2 / Apollo model No. Elite RS 10860-10 |
| 2 | Supply and fixing in repair Addressable manual call point resettable type complete all as specified and directed Make :- Morley-IAS by Honeywell/Bosch/Apollo |
| 3 | Supply and fixing in repair red colour PVC insulated PVC sheathed armoured copper conductor cable of size 2 Core x 1.5 Sqmm including fixing on walls with saddles not more than 60 cm intervals complete all as specified and directed. |
| 4 | Supply and fixing in repair Addressable sounder range 900 dblwith strobe complete all as specified and directed Make :- Morley-IAS by Honeywell/Bosch/Apollo |
| 5 | Supply and fixing in repair detectors Complying with and type certified to EN - 45 Addressable type optical multi Sensor detector heat and smokecombination Photoelectric /Optical with base with self built intelligence as per IS: 11360 complete all as specified and directed. Make :- Morley-IAS by Honeywell/Bosch/Apollo |
| 6 | Supply and fixing in repair addressable fault Isolator suitable for fire alarm system complete all as specified and directed.Make :- Morley-IAS by Honeywell/Bosch/Apollo |
| 7 | Supply and fixing in repair addressable control module suitable for fire alarm system complete all as specified and directed. Make :- Morley-IAS by Honeywell/Bosch/Apollo |
| 8 | M&L for earthing complete with galvanized earth plate 60cm x 60cm x 6mm thick buried directly in ground vertically to a depth not less than 2.25 mtr deep below normal ground level connecting with 4 mm diaGI wire by means of bolts nuts, check nuts and washers of galvanized iron all shown in electrical plate No 03 of SSR Part-I including necessary excavation earth workusing PCC 1:2:4 for earthing pit and pit cover with handle of 8mm dia MS rod and connected to test point all as specified and directed.Note : (a) The item rate inclusive of fixing of earth continuity conductor from earth plate upto 7.5 mtr.(b) The item rate inclusive of provisioning necessary charcoal and salt upto the level of the earth plate in alternate layers. |
| 9 | M & L for earthing complete with galvanized earth plate 60cm x 60cm x 6mm thick buried directly in ground vertically to a depth not less than 2.25 mtr deep below normal ground level connecting with 25 x 4 mm GI strip by means of bolts nuts, check nuts and washers of galvanized iron all shown in electrical plate No 03 of SSR Part-I including necessary excavation earth workusing PCC 1:2:4 for earthing pit and pit cover with handle of 8mm dia MS rod and connected to test point all as specified and directed.Note : (a) The item rate inclusive of fixing of earth continuity conductor from earth plate upto 7.5 mtr.(b) The item rate inclusive of provisioning necessary charcoal and salt upto the level of the earth plate in alternate layers. |
| 10 | M&L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4 mm dia galvanised iron or steel wire complete all as specified and directed. |
| 11 | M&L for Earth continuity conductor or main earthing lead fixed to wall on FRPinsulators or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 25 x4 mmgalvanised iron or steel strip complete all as specified and directed. |
| 12 | Supply, install testing and commissioning of Booster pumps for 440 V, 3 Phase, 50 Hz Confirming to IS- 12469 :1988, Size (mm) Suction x delivery : 80 x65 mm With CI Casing bronze impeller and stainless steel shaft mounted on heavy duty bearings suitable for 440 volts, 3 phase, 50 Hz 35mtr head, 900 LPM discharge including PCC foundation not less than 20 CM height, pump fixed on angle iron base frame from the manufacturer size and model with vibration pads, PVC insulated and sheathed three core cable of suitable size from starter to pump and Fibre sheet 2 mm thicknessfor shed not less than 4 sqm with angle iron as required at site for protection of pump from rain and water complete all as specified and directed.Make :- Kirloskar Model No. KDI-1555+ CI MS SS IP55 FCL or technocommercial equivalent make in CGNote :- The item rate also includes PCC foundation, Fibre sheet, angle iron frames, Pump base frame, vibration pads, grouting of nut bolts and three core cable from starter to pump as required at site including testing. |
| 13 | Supply and Fix of Automatic Star Delta starter control panel for 3 phase, 15 HP (11.30 KW)motor which includes contactors, relays range 20-32A, control wiring, Selector switches, Ammeter, Voltmeter, LED Phase indicating lamps complete in sheet metal enclosure company made including connecting and testing, fixing on walls with grouting and providing out side box for to protect from weather and rain complete including configuration with existing panel with authorised rep all as specified and directed.Make :- CG model No. CP200320SD or equivalent in Havells/L&T |
| 14 | Supply and fixing MCCBs 40 Amp 3 pole 415 volts, 16KA, 50 HZ including factory made SS enclosure fixed on wall and making connections complete all as specified and directed |
| 15 | Supply and fixing MCB double pole 16 Amps, 10 KA, \"C\" series with factory made SS enclosure fixed on wall and making connections complete all as specified and directed. |
| 16 | S&F in repair XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 6 sqmm 4 core fixed on wall with steel saddles as approved by Engineer-in-Charge. |
| 17 | Supply and laying in replacement of spigot and socket ductile iron water tubing,class K-9,100 mm dia cement mortar lining on inner surface and one coat of bituminous paint over exposed surface ISI marked, IS No. 8329: 2000, including rubber joint of suitable size laid on roof/floor/trenches with proper alignment as per site requirement and carryout testing against leakage before filling the trenches etc complete all as specified and directed.Make :- Jindal/Sri pipes/Tata/Lanco/Electro steel |
| 18 | Supply and laying in replacement of spigot and socket ductile iron water tubing,class K-9,150 mm dia cement mortar lining on inner surface and one coat of bituminous paint over exposed surface ISI marked, IS No. 8329: 2000, including rubber joint of suitable size laid on roof/floor/trenches with proper alignment as per site requirement and carryout testing against leakage before filling the trenches etc complete all as specified and directed.Make :- Jindal/Sri pipes/Tata/Lanco/Electro steel |
| 19 | Supply & fix in repair 100mm dia ERW MS pipe heavy grade including MS fittings confirming IS-1239 and applying two coats of synthetic enamel paint over a coat of red oxide primer to pipeincluding welding, supporting brackets as required at site complete all as specified and directed.Make:- Jindal /Tata /Sail |
| 20 | Supply & fix in repair 80mm dia ERW MS pipe heavy grade including MS fittings confirming IS-1239 and applying two coats of synthetic enamel paint over a coat of red oxide primer to pipeincluding welding, supporting brackets as required at site complete all as specified and directed.Make:- Jindal /Tata /Sail |
| 21 | M&L factory fabricated Hose box made of 18 gauge MS Sheet 800mm X 600mm X 250mm with double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet painted fire red out side and brilliant white insideyard fixed on wall withnecessary nuts/bolts or welding to existing MS pipe by supporting angle complete all as specified & directed. |
| 22 | Supply & fix in repair rubber hose pipe red in colour 30 mtr,20mm dia plain 2 ply rayon confirming IS-12585 braided high pressure complete all as specified and directed. Make:-Minimax / Safex /Dunlop Note :- Rate is inclusive of shutoff nozzle and shank reducer and providing all possible connection for testing |
| 23 | Supply & fix in repaircanvas fire hose red in colour 63mm bore 15 m long confirming to IS 636-1988 having male/female brass coupling both end complete all as specified and directed. Make:-Minimax/Safex/Dunlop |
| 24 | Supply & fix in repair hose Reel drum with mounting base plate company made suitable for 30 mtrs X 20 mm dia rubber hose pipe complete all as specified and directed. Make:-Minimax/Safex/Dunlop |
| 25 | Supply & fix in repairsBranch pipe gun metal 63mm instantaneous inlet, made threaded outlet, 15mm bore nozzle complete all as specified and directed. Make :- Minimax / Safex / Dunlop |
| 26 | Supply and fix in replacement of Gun metal fire brigade in let connection for connecting to external fire hydrant ring main consisting of two nos 63mm dia instantaneous type male coupling with built in check valves and 80mm dia, flanged outlet complete with all accessories. |
| 27 | Supply & fix in repair double headed outlet hydrant valve 100mm having 65mm outlet with lock pin wheel complete all as specified and directed. Make:-Minimax/Safex/Dunlop |
| 28 | Supply & fix in repair single headed outlet hydrant valve 100mm having 65mm outlet with lock pin wheel complete all as specified and directed. Make:-Minimax/Safex/Dunlop |
| 29 | S&F in repair PVC water storage Tank 5000 ltr capacity 2 layers , ISI marked, Antimicrobial hosting and fixing in position at any locationremoving existing tank disconnecting all incoming & out going connection , provision of new tank fittings & connecting it at existing positionup to 50 mm GI Pipe connection including replacement of tank nipples and GI fittings as required at site completeall as specified and directed. Make :- Sintex/Plasto/Vectus |
| 30 | Supply & fixin repair sluice valve (ISI marked)150mm size both ends flanged with high tensile stainless steel spindle, I body as per IS-14846, ISI Marked,PN-1.6 including all joints with rubber or fibre board, nuts, bolts, washers complete all as specified and directed. |
| 31 | Supply & fixin repair sluice valve (ISI marked) 100mm size both ends flanged with high tensile stainless brass spindle, I body as per IS-14846, ISI Marked,PN-1.6 including all joints with rubber or fibre board, nuts, bolts, washers complete all as specified and directed. |
| 32 | Supply & fixin repair Non return valve (ISI marked)150mm size both ends flayed with high tensile stainless steel spindle, I bodyincluding all joints with rubber or fibre board, nuts, bolts, washers complete all as specified and directed. Make:Kirloskar/Leader/L&T (Andco) |
| 33 | Supply & fixin repair Non return valve (ISI marked) 100mm size both ends flayed with high tensile stainless steel spindle, I bodyincluding all joints with rubber or fibre board, nuts, bolts, washers complete all as specified and directed. Make:Kirloskar/Leader/L&T (Andco) |
| 34 | Supply and fixing in repair steel galvanised pipes medium grade, ISI marked of size 50 mm dia including necessary fittings as required at site complete all as specified |
| 35 | S&FBall brass valves 50 mm, high pressure,with polythene float and flynut complete, screwed for iron pipe or brassferrule and fixed |
| 36 | M&L cement concrete 1:2:4, type B-2 (using 40 mm graded stone aggregate) as in support of CI pipes, foundation and hardstanding finishing even and fair without using extra cement all as specified. |
| 37 | Supply and fixing in repairs in existing line, CP brass gate valve 50 mm bore with iron wheel head screwed both ends for iron pipe including fittings i.e. union, socket etc complete all as specified and directed. |
| 38 | Supply and fixing in repair/replacement by using Fe-410-W(GdeE-250) qualityB forCompound girders and stanchions, lattice girders, aerial masts,staging for water tanks , ladders, and the like including caps, bases, splices etc. built up from two or more beamor channel sections or angles with plates, including all lattice bars,stiffeners, gusset plates, nuts, bolts, washers etc. including necessary fabrication work with hinges, handle andapplying two coats of synthetic enamel paint over one coat of metal primer complete all as specified. |
| 39 | Supply and installation of water flow switch suitable for fire fighting system, pipe size 100 mm dia , operating pressure, withstand pressure as per manufacturer recommendations, including cutting, clamping, welding , control wiring, connecting and testing with allall accessories/items required at site and testing complete all as specified and directed. Make :- Honey well model No. WFS-1001-H or technocommercial equivalent make given in Appx B |
| 40 | Supply and installation of Pressure gauge 4\" dial 0-14 kgs rating complete all as specified and directed |
| 41 | Supply and installation Pressure switch universal type complete all as specified and directed. |
| 42 | Supply and fix Fire Alarm sounders / Sirens electronic type horizontal two stage continuous normal operation for at least 50 minutes with sound level 65 db to 120 db Measured at 1.5 m with sound output variation of + 5 db 1500m range complete all as specified and directed. |
| 43 | Construction of brick masonary valve chamber in repair of size 1.2 x 1.2 x 1.2 M (internal dimension) (above GL 0.30 mtr) suitable for fixing of sluice valves, 15cm thick foundation using PCC 1:4:8 type D-2 over 15cm thick hardcore of broken stone, 23cm thick brick walls built in cement and sand mortar 1:4, 15mm thick internal and external plaster including top of floor in cement and sand mortar 1:3, 15mm thick, finished even and smooth, without using extra cement, 8 mm thick plate cover on 50mm x 50mm x 6mm MS angle frame embeded in PCC 1:2:4 type B-1coping, having rectangular, hinged, opening of size 150 x 100mm with locking arrangements ,hold fasts, etc, applying one coat of red oxide primer and two coats of synthetic enamel paint to all steel surfaces and earth work in any type of soil including disposal of debris outside MD landcomplete all as specified. |
| 44 | M & L in repairs for CI/DIspecials conforming to IS - 1538& 9523, spigot /socket or flanged fitting I.e. bend, tee, collar, flanged/ socket /spigot, Tappers, flanges and tail pieces etc suitable for 100/150/200/250/300 mm boreCI/DI pipes (joints and joining material shall be measured and paid seperately) |
| 45 | Supply and fix in repairs CI foot valve (ISI marked) 100 mm (4\") dia flanged end IS 4038 PN 0.2 housing complete including replacement of nut bolts, cutting of pipe, welding complete all as specified and directed. |
| 46 | Supply and fixing Jockey pump horizontal end suction centrifugal type Confirming to IS- 12469: 1988 with CI casing , bronze impeller and stainless steel shaft mounted on heavy duty bearings suitable for automatic operation with nonover loading power characteristics for frequent start / stop operations for 440 V , 3 phase, 50 Hz 70 m head 180 LPM discharge complete all as specified and directed. |
| 47 | M&L for Providing and fixing (E.R.W. pipe conforming to IS 1239) with ISI marked with screwed or welded joints, including all fittings(R Brand/Kirti), supported by galvanized hangers(size and spacing as per drawing) including anchor fasteners for fixing in ceiling testing to 15 kgs/cm2 pressure , paintingwith a coat of Zinc Dichromate primer and two coat of approved enamel paint, making direction arrows and labelling etc. complete. (Pipes 65mm and above diameter will be welded and pipes 50mm and below will be screwed jointed) |
| 48 | A. 65 mm dia |
| 49 | B. 40 mm dia |
| 50 | C. 25 mm dia |
| 51 | M&L for Providing and fixing paddle type flowswitch (Switzer/Danfoss) on pipes with welded socket including stainless steel paddle suitable to pipe dia. 150mm to 25 mm testing and commissioning etc. complete. |
| 52 | Supply and fixing suitable C.I. air release valve (ISI marked) 20 mm dia, flanged ends ISI marked with all accessories and as per IS-14845 including 2 nos flanged joints complete with jointing material such as 3 mm thick rubber gasket, nuts, bolts, washers complete all as specified and directed. |
| 53 | M&L for Providing and fixingapproved quartezoid bulb 15mm dia sprinklerpendent type, IS No 15106 (Tyco/Viking/Spraysafe) chrome plated with rossette plate,with temperature rating 68 degree. C, with universal deflector as approved by T.A.C. complete with all necessary connections. |
| 54 | Supply and fixing pressure gauge 4\"dial 0-21 kgs rating complete all as specified. |
| 55 | Supply and fixing in position drain / test assembly comprised of2 nos. 65mm diabrass tested heavy duty ball valves with screwed ends confiming to IS 554 with ISI mark (Zoloto/Leader/RB), including necessary G.I. \"C\" class pipes, union(1 no)& site glass fitting etc. complete all as specified. |
| 56 | Supply Installation testing and commissioning Diesel Engine driven fire pump horizontal end suction with discharge 1620 LPM , head 70 m at 1800 RPM, 58 HP engine.Pump Construction: Pump With Diesel EngineComponent MaterialsCasing Material: Ductile Iron 65-45-12, Impeller Material: Bronze LTB2, Shaft Material: S.S AISI 410Seal Material: Gland Packing, Wear Ring Material: Counter Flange Material: AccessoriesBase Frame & Coupling: Pipework ConnectionSuction & Discharge Flange Rating: PN 16Casing Connection: Without Suction & Discharge FlangesDriver SpecificationsEngine Cooling System: Radiator CooledEngine Rating: 58 HP - 1800 RPM - 12V - EicherFire Pump Specifications - NFPA 20 ComplianceDiesel Tank With Accessories: 100 litre capacity, stand for TankBattery With Cable & Lugs: 12V , Stand for batteryBattery : 1 Nos.: Battery Charger: 12V Engine Mount Control Panel Suction & Discharge Pressure Gauges: Make of Engine : Cummins/Greaves Cotton/Ashok Leyland/Kirloskar |
| 57 | Cleaning of underground sump of any capacity 2.00 lakh Ltrs cleaning the floors, wall and ceiling portion of sump etcby Mechnical high pressure spray and steel wire brush to remove Algae/dirt/foreign dirt completely and soaking out the water/dirt with a high pressure wet vaccum pump and removing spoilsout side of MD land land distance exc 5 KMs & n.exc 10 KMs and applying spray of approved chemical etc. complete all as specified and as directed by Engineer-in-charge .Note :- 1.Rates deemed to be included for pumping out water left below foot valve.2.Rate include the painting of two coats of enamal paint with visible colour and capacity of sump about date of cleaning and due date for cleaning complete all as specified. |
| 58 | Demolition of cement concrete (unreinforced) in ground floors and pavings n.exc 15 cm thickness (below or above ground level)and debris out side MD land all as specified. |
| 59 | Supply and laying in replacement of spigot and socket ductile iron water tubing,class K-9,300 mm dia cement mortar lining on inner surface and one coat of bituminous paint over exposed surface ISI marked, IS No. 8329: 2000, including rubber joint of suitable size laid on roof/floor/trenches with proper alignment as per site requirement and carryout testing against leakage before filling the trenches etc complete all as specified and directed. |
| 60 | Supply & fixingin repair sluice valve (ISI marked) 300mm size both ends flanged with high tensile stainless brass spindle, I body as per IS-14846, ISI Marked,PN-1.6 including all joints with rubber or fibre board, nuts, bolts, washers complete all as specified and directed. |
| 61 | Demolition stone slabs and tiles of any description or thickness in floors, aprons etc. complete. |
| 62 | M &L for sand filling under floors or in foundation including watering and consolidation etc complete. |
| 63 | M&L Machine pressed precast colour glazed concrete interlocking paver block with grey cement & pigment glossy finish (reflective type)any shape and size (as approved by GE ) confirming to IS 15658-2006of 60 mm thickness, M-35 grade, as in pavements to required level & gradients set, jointed with clean dry sand sealing the ends using PCC 1:2:4 etc complete. |
| 64 | Supply and fixing bitumens patchment (paving grade bitumen VG-10 grade)on damaged road not exceeding 15 cm depth and make well ramming complete all as specified and directed |
| 65 | Supply and fixing in replacement of Butterfly Valve (ISI MARKED)150 mm dia along with supporting enclosures as required at site complete all as specified and directed |
| 66 | Supply and fixing in replacement of Butterfly Valve (ISI MARKED) 100 mm dia along with supporting enclosures as required at site complete all as specified and directed |
| 67 | Supply & fixing in repair 150mm dia ERW MS pipe heavy grade including MS fittings confirming IS-1239 and applying two coats of synthetic enamel paint over a coat of red oxide primer to pipeincluding welding, supporting brackets as required at site complete all as specified and directed.Make:- Jindal /Tata /Sail |
| 68 | M&L for Disconnecting motor power cables of various sizes from electrical motor of different capacities and decoupling from thepump sets,removing and taking down carefully and transporting to authorised workshop ,Dismantaling stator and rotor carefully andrewinding stator assembly with supper enamelled copper windingwire of suitable gauge matching to existing gaugeand cleaning of slots ,core with carbon tetra chloride solution and apply two coats of insulation varnish and keep stator assembly in heating chamber to improve insulation strength ,reassemble motor completey and transporation to site ,coupling pump to motor and check for proper shaft alignments such that no vibratiobn produce during opertioncoupling to pump with exact allinment ,connect power cables to motor including painting of pump motor and testing of following capacity motor |
| 69 | (a) 60/75 HP |
| 70 | (b) 20/15 HP |
| 71 | Supply and fixing in repairs CI foot valve 150 mm (ISI MARKED) (6\") dia flanged end IS 4038 PN 0.2 housing complete including replacement of nut bolts, cutting of pipe, welding complete all as specified and directed. |
| 72 | Supply ,installation , testing and commissioning in replacement of Indoor type LT Panel board from CPRI approved panel manufacturermade out of 3.15mm CRCA sheet cubical totally enclosed with frame made out of 50mm x 50mm x 6mmangle iron door front and back openable with locking arrangement indoor type vermin and weatherprooffloormounting type, suitable for 3 phase 4 wire,50 HZ , 415 Volt AC supply with 800A capacity copper bus bar (4 Nos) All MCCB shall be connected with suitable size of copper strip from main bus & with terminate point and complete wiring of panel board with suitable size PVC insulated multistranded copper conductor including lugs/thimbles etc with suitable Cable alleyfor provn of cable entries at bottom with cable glandsincluding the following :-(a) MCCB 4 pole, 415V,630Amps 36 KA - 01 No (incoming) thermo magnetic adjustable release type,ICS=ICU=100% (b) MCCB 4 pole,415V,125 Amps 36 KA - 03 No (outgoing) thermo magnetic adjustable release type,ICS=ICU=100% (c)MCCB 4 pole,415V,100Amps 16 KA - 02Nos (outgoing) thermo magnetic adjustable release type,ICS=ICU=100% (d)MCB 4 pole , 63 Amps, 10 KA, \"C\" Series -03 Nos(e) Phase indicating lamps(RYB)-04 set(f) Digital panel meter for Amp,Volt,KWH, power factor and other parameter flush mounting of size 96X96mm-01 set. (g)MCCB 4 pole,415V,40Amps 16 KA - 02Nos (outgoing) thermo magnetic adjustable release type,ICS=ICU=100% |
| 73 | Note :-Item No 67 include all necessary accessories for operation of paneland control wiringwith furrule indicator, current transformers ,push buttons ,indication lamps for RYB phases,ON and OFFswitches,digital voltmeter,ammemter, cable alley,terminal block,selector swithes complete as directed by Engr-in-ChargeNote :- The panel board shall be fabricated from CPRI approved firm and panel drawings shall be submitted by the contractor for approval before placing the order. |
| 74 | Supply and fixing in repair XLPE insulated, armoured heavy duty electric cable 3.5 core with aluminium conductor, 1100 volts grade, cross-sectional area 400 Sqmm fixing on wall with suitable saddles or under ground as required at site complete including lugs complete all as specified and directed. |
| 75 | Supply and laying in replacement of copper unamoured power cable of size 16 sqmmfrom motor starter panel to motor in and including HDPE pipe in ground/ floor including copper lugs, nut bolts and washers as reqd at site complete all as specified and directed. |
| 76 | Supply and laying in replacement of copper unamoured power cable of size 25 sqmmfrom motor starter panel to motor in and including HDPE pipe in ground/ floor including copper lugs, nut bolts and washers as reqd at site complete all as specified and directed. |
| 77 | Supply and laying in replacement of copper unamoured power cable of size 35 sqmmfrom motor starter panel to motor in and including HDPE pipe in ground/ floor including copper lugs, nut bolts and washers as reqd at site complete all as specified and directed. |
| 78 | Supply and laying in replacement of copper unamoured power cable of size 70 sqmmfrom motor starter panel to motor in and including HDPE pipe in ground/ floor including copper lugs, nut bolts and washers as reqd at site complete all as specified and directed. |
| 79 | Excavation in trenches not exceeding 1.5 mtr wide not exceeding 1.5 mtr in depth and getting out in soft/ loose soil all as specified. |
| 80 | Returning filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cms in any type of soil all as specified. |
| 81 | Removing excavated material exc 250m but n.exc 500m and depositing where directed all as specified. |