| 1 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed PVC conduit as required. |
| 2 | 2 X 4 sq.mm +1 X 4 Sq.mm earth wire |
| 3 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 4 | 4 X 6 sq.mm +2 X 6 Sq.mm earth wire |
| 5 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc.as required. |
| 6 | 1 or 2 Module |
| 7 | 3 Module |
| 8 | 6 Module |
| 9 | 8 Module |
| 10 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 11 | 15/16 A Switch |
| 12 | 6 pin 15/16 amp socket outlet |
| 13 | Supplying and fixing of below rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 14 | Single Pole (16A) |
| 15 | Single pole( 63A) |
| 16 | Double pole (63A) |
| 17 | Triple pole (32A) |
| 18 | Triple pole and neutral (32A) |
| 19 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 20 | 100A, 25KA, FPMCCB |
| 21 | Supplying and fixing of 32A, 415V , 3P+N+E Five pin Industrial type Plug and socket DBin sheet steel enclosure, on surface or in recess complete with connections, testing and commissioning etc. as required. (Similar to Make: Legrand, Model: 5078 62 Type: Plug & Socket DB) |
| 22 | 32A 3P+N+E 5Pin Plug & Socket DB |
| 23 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). |
| 24 | 12 way , Double door |
| 25 | Supplying and fixing of following way surface/recess mounting vertical type 415V,TPN MCB distribution board of sheet steeel dust protected duly powder painted inclusive of 200A tinned copper bus bar,common neutral link,earth bar,din bar for mounting MCBs(but without MCB and incomer) as required. |
| 26 | 8 way (4+24),double door |
| 27 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
| 28 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
| 29 | Upto 35 sq. mm (clamped with 25x3mm MS flat clamp) |
| 30 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 31 | Upto 35 sq. mm (clamped with 25x3mm MS flat clamp) |
| 32 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 33 | 3.5C X 35 sq. mm (32 mm) |
| 34 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 35 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 36 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 37 | Supply, loading, transportation, unloading at site, storage st site, shifting from storage place to site of following size of XLPE Insulated PVC Sheathed, Aluminium Conductor armoured power cable of 1.1 KV grade conforming to IS amended upto date and as per specifications |
| 38 | 3.5C X 35 sq. mm XLPE Al Cable |
| 39 | Sub-Head-B: LAN and Associated Networking works Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 40 | CAT6 UTP RJ-45 socket outletSimilar to Make: Commscope, Model: KJX-6A |
| 41 | Supplying and fixing of following sizes of medium class PVC Trunking along with bends,end caps and all required accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 42 | 105mm X 50mm |
| 43 | 80mm X 50mm |
| 44 | Supplying of 4 pair CAT 6A LAN Cable as per the specifications, each box should be of 300 mtrs standard package. |
| 45 | Laying/drawing of UTP 4 pair CAT 6A LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. |
| 46 | 1 run of cable |
| 47 | Supply Installation of the following size Portable RacksNetowrking/Server Rack |
| 48 | 12U |
| 49 | 15U |
| 50 | Supply, Installation of following length of Patch Cord in the existing Portable RacksNetowrking/Server Rack |
| 51 | Patch Panel CAT6A (24 Port, Fully Loaded) |
| 52 | Supply, Installation of following length of Patch Cord |
| 53 | 1 Meter CAT6A Patch Cord |
| 54 | Supply, Installation, Testing and Commissioing of following ports Network Switches |
| 55 | 48 Port |
| 56 | 24 Port |
| 57 | Sub-Head-C: Exhaust System:SITC of Exhaust fans (side inlet top Exhaust unit)Supplying, erecting, testing and commissioning,Fan - SISW bacward curved centrifugal fan ( with necessory supports arrangement)with sq cage induction motor, GSS frame support frame work, belt drive with required size pullys and belts, spring type vibratioin isolator, base frame, stater panel of motor shall be suitable for drive and 415+/-10% V, 50 hz, 3 phase AC supply. Fan shall be suible for exhaust Air. Complete fan, scroll and blade shall be powder coated with non stick paint.Exhaust fans shall be with insect mesh ( Opening ) to exhaust air.Openings for cable entry, gauges and devices,pressure testing probe and any Accessories entry shall be factory done and no penetration of casing at site shall be allowed for all types of AHU.Fans Are AMCA Certified for the sound and AirAllnecessory supports and accessories, vibration /spring isolator, pads etc shall be includedMotor shall be - IE3 motor (As per IS 12615).Mechanical and motor efficiency shall be 65%.Static pressure and motor rating - The indicated static pressure and motor rating is only provisional. Contractor to calculate static pressure based on final approved construction drawing and pressure drop of finalzed equipment selected.Toilet Exhaust ( Side Inlet-Top Exhaust Unit) |
| 58 | Capacity- 1000cfm (location @ Terrace)External Static pressure- 40mm wc |
| 59 | Capacity- 2000cfm (location @ Terrace)External Static pressure-40mm wc |
| 60 | Capacity- 5000cfm (location @ Terrace)External Static pressure- 40mm wc |
| 61 | SHEET METAL WORKSupplying, erecting, testing and commissioningof AIR DISTRIBUTION SYSTEM consists of Factory fabricated sheet metal ducting with reinforcement/stiffners(manufactured through computer aided machine which has automatic provision for plasma cutting for the profiles and for auto folding) complete tdc flanges, GI slotted channels and GI fully threaded rod supports, gaskets, supply air collars, vanes, splitters, painting of the ducts behind continous grills etc.(GSS duct shall confirm to Class-VII with 180gm/m2 zinc coating. Rectangular ductTDF flange and box sections to be provided Smoke test shall be required for 100% of ductingDuct shall be with all necessary support arrangement.factory fabricated120 GSM GSS ducting, TDC/TDF flanges, Guide vanes,reinforcement/stiffeners All TDF flanges supports , bracing required shall be consider as per the SMACNA standard Pressure ClassDuctingpassing through building expansion joints shall have the flexible connection.The selection of duct thickness shall be as under:24 G-0 - 750 mm22 G-751 - 1250mm20 G-1251 - 2100mm18 G- 2101 & Above |
| 62 | 24G GI |
| 63 | 22G GI |
| 64 | 20G GI |
| 65 | PVC Piping. |
| 66 | Supplying, erecting, testing and commissioningof AIR DISTRIBUTION SYSTEM consists of PVC pipe Working Presure 2 Kg/sqcm, PVC Round pipe With All type Fitting .(Elbow. T, And Joints..) Ø300MM |
| 67 | Manual control Volume control damper in 16G construction as specified, Al dampers( Low leakags), with TDF flange-Supply, installation and testing of AL construction of 16G opposed blade volume control dampers within ducts to be provided with suitable links, levers and quadrants for manual control of volume of air flow.The end flanges should be of TDF. |
| 68 | Electrical Cable Work |
| 69 | Supply of XLPE insulated 4 core 4Sqmm sheathed armoured copper cable with required terminations for voltage up to 1100V as per IS 694/1990. |
| 70 | Supply of XLPE insulated 4 core 2.5Sqmm sheathed armoured copper cable with required terminations for voltage up to 1100V as per IS 694/1990. |
| 71 | MS Structural supports |
| 72 | Supply and installation Structural steel Supports MS painted Structural Steel for supports. Two coats of red oxide and enamel paint to be applied. |