Providing Fire Fighting Arrangements To Mch Building In Government District Head Quarters Hospital At Kancheepuram In Kancheepuram District- 1 Servicing the SS Hydrant Valves by disconnecting from pipe line, dismantling, checking the operation of rotating spindle, replacing rubber O ring of valve seating, replacing rubber gasket of 80mm dia OD x 65mm dia ID, replacing the 5/8 x 21/2 bolt, nut, washers, reconnecting with hydrant system as per standard methods and as directed by the Departmental Officers. 2 Servicing the First Aid Hose Reel Drum assembly by disconnecting from hydrant line, replacing shut off nozzle, warm clip, lubricating the rotating assembly, replacing 20mm dia, 30 metres long rubber hose, reconnecting with hydrant system as per standard methods and as directed by the Departmental Officers. 3 Supply and Fixing in Position of Dos and Donts sign board made up of 3mm thick Plaque Foam board sizes of 24 x 19 (inches) of computerised cut, PVC non- reflective self adhesive vinyl painted foam board suitably mounted on wall using adhesive tape / sealant near every hydrant point as per standard methods and as directed by the departmental officers 4 Supply and laying of 2 core 1.5 sq.mm. armoured copper cable for control wiring to the Terrace Pump Motor with runs of 14 SWG TC wire for earthing, providing in wall with suitable size GI clamps, screws, wooden plug, end termination by using suitable size cable glands, copper sockets and etc., as directed by the Departmental Officers. 5 Supply, erection, testing and commissioning of following MS C Class Heavy Duty Pipe as per IS 1239 to withstand a developing pressure of 10 kg. / sq.cm including necessary fittings like MS flange of table „E‟, elbows, reducers, gaskets, bolt, nuts with washers & joints as per standard method of arc welding, including one coat metal primer and two coat Post Office Red painting including conveyance, all incidental charges, necessary scaffolding and re-doing the dismantled portions to its original condition wherever found necessary, etc., complete as per standard specification and as directed by the Departmental Officers. Make: JINDAL / EQUIVALENT. 6 150mm dia MS C Class Heavy 7 Servicing, testing and commissioning of 2280LPM, 70 Meter head, Diesel Engine Driven Main Fire Pump, Services include Cleaning of Diesel Tank, Fuel Indicator Tube with appopriate solvent, Cleaning of Fuel Filter, Cleaning wire contacts in a diesel engine starter and battery by removing Dirt, Grime, corrotion, Tigntening of any loose terminals, Testing battery voltage, Freeing of Impeller shaft, Greasing of Points, replacing Oil seal rope, recirculation, removing dust and forign particals from collant oil, Radiator cleaning, Checking of Belt tension and all related works as per standard specifications and as per direction departmental officers 8 Supply and fixing in position of 12 Volt 180 AH Lead Acid, Sealed Maintenance Free (SMF) batteries with connecting leads, lugs terminal post, etc., as per standard methods and including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers. Make: EXCELLENT / SAFETY FIRST / EQUIVALENT. 9 Dismanteling and Disassembly of Eletrical JockeyPump and its accessories for attending repairs like greezing, renewing gland pipes, ball bearing, servicing of pump shafts, impeller, coupled bolt nuts, electrical connections for the respective 180LPM, 70 Meter head 10 Horse Power, re-erection and assembly of the pumpset and it accessories, Reconneting the fire line as per Standard specifications and as directed by departmental officers 10 Dismanteling and Disassembly of Main Eletrical Fire Pump and its accessories for attending repairs like greezing, renewing gland pipes, ball bearing, servicing of pump shafts, impeller, coupled bolt nuts, electrical connections for the respective 2280LPM, 70 Meter head 60 Horse Power, re-erection and assembly of the pumpset and it accessories, Reconneting the fire line as per Standard specifications and as directed by departmental officers 11 Supply, and fixing inpositionof Fire Fighting Application 63mm dia stainless steel short length Branch Pipe with hexagonal type spray nozzle of 15mm (or) 20mm jet bore. Near every hydrant points including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers.Make: OMEX / KARTAR / LIFE GUARD / SAFE GUARD / EQUIVALENT. 12 Supply of Fire Fighting Application MS Hose Box to keep two number of hoses and 1 No. of branch pipe with nozzle having proper glass window type double door with universe open key, painted inside white and outside Post Office Red.Near every hydrant point including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers. Make: OMEX / KARTAR / LIFE GUARD / SAFE GUARD / EQUIVALENT. 13 Supply, installation, testing and commissioning of Conventional Smoke Detector suitably mounted on ceiling with MS junction box / false ceiling using fixing accessories like screws, plug, clamps, etc., as per standard methods and as directed by the Departmental Officers. (Make: Apollo / Equivalent) 14 Supply, installation, testing and commissioning of Manual Call Point (MCP) providing on wall using fixing accessories like screws, plug, clamps and etc., as per standard methods and as directed by the Departmental Officers.(Make: Ravel / Equivalent). 15 SUB TOTAL 16 GST @ 18 %