| 1 | Wiring for light / fan / exhaust fan / call bell point with 2 x1.5 sq. mm pvc insulated Copper conductor cable (FR) in pvc casing and capping complete with 6/10 amps modular type switch, cover plate, surface modular switch board |
| 2 | Short Point |
| 3 | Medium Point |
| 4 | Long Point |
| 5 | Supplying & fixing of the PVC casing and caping including all accessories as required 32x12 mm |
| 6 | Supplying & fixing of the PVC casing and caping including all accessories as required 38x16 mm |
| 7 | Providing and fixing of 3 pin 6/10 amps plug point withmodulartype 6/10ampsswitch andsocketincludingconnectionwith 2x1.5 sq. mm PVC insulated Copper conductor cable (FR) on surface modularswitch board, earthing the 3rd pin etc. as required. |
| 8 | Providing and fixing of 3/6 pin 16/20 amps plug point withmodulartype 16/20ampsswitch andsocketincludingconnectionwith 2x2.5 sq. mm PVC insulated Copper conductor cable(FR) on surface modular switch board, earthing the 3rd pin etc. as required. |
| 9 | Supplying and fixing of following outdoor LED luminaries in powder coated die cast housing complete with heat resistant tempered glass/diffuser including necessary connection etc. as required (50000 burning hours and minimum lumen output of 100 lm/watt):- |
| 10 | 25 watt LED street light fixture with integral driver and secondary lens (IP 66):- |
| 11 | Supplying and fixing of the following sizes PVC switch boards with cover etc. as required. |
| 12 | 152mm x 203mm (6\" X 8\") |
| 13 | 203mm x 254mm (8\" X 10\" |
| 14 | Wiring for circuit /Sub-main with following sizes PVC insulated copper conductor cable (FR) in PVC casing and capping etc. as required. |
| 15 | 2 X 1.5 sq mm |
| 16 | 2 X 2.5 sq mm |
| 17 | 2 X 4 sq mm |
| 18 | Supplying and fixing of the following electrical accessories including necessary connection etc. as required. |
| 19 | Ding dong call bell |
| 20 | Ceiling rose |
| 21 | 32 amps DP kit kat switch |
| 22 | Electronic 5 step fan regulator |
| 23 | Angle/batten holder |
| 24 | Supplying & installation of 10 KA breaking capacity, B/C curve MCB of following ratings in the existing MCB DB including connectionas required. |
| 25 | 6 to 32 amps SP MCB |
| 26 | Supplying & installation of isolators of following ratings in the existing MCB DB including connection etc as required:- |
| 27 | 40 amps DP isolator. |
| 28 | Providingearthing systemwith maintenance free earthing electrode of 50 mm dia & 3 mtr long of dual electrode technology filled with highly conductive compound and back fill compound of 2 nos. 25 kg bag, terminalsize 32mmx 6mm including accessories with masonry enclosure of CIcover plate size 12\"x 12\" having locking arrangement including CC works etc as required. |
| 29 | Proving and fixing / drawing of 4.06 mm dia (8 SWG) G.I. wire on surface or in existing G.I/ PVC/ Polythene pipe for loop earthing as required. |
| 30 | Providng and laying 15mm dia(medium gauge) G.I. pipe for drawing of4.06mm (8SWG) dia G.I./ Copper wire forearth connection from earth electrodes etc as required. |
| 31 | Wiring for Circuit/Sub-main with the following sizes of PVC insulated Copper conductor cable (FR) in existing PVC casing capping/ conduit in recess/surface including connection etc. as required:- |
| 32 | 1 X 2.5 sq mm |
| 33 | Supplying and installation of Switch disconnector fuse unit (main switch) of the following ratings with all accessories including necessary connection etc. as required |
| 34 | 32 amps 240 volts DP main switch (rewireable):- |
| 35 | Supplying and installation of powder coated steel sheet enclosure (MCB DB) suitable for 240/415 volts MCB/Isolator/RCCB (SP/SPN/DP/TP/TPN/FP) complete with necessary bus bar, neutral link, din rail, earth bar etc i/c connection as required. |
| 36 | (2+4) / 6way SPN MCB DB (single door):- |
| 37 | (2+10) / 12way SPN MCB DB (single door):- |