| 1 | xx |
| 2 | Wiring for light point/ fan point/ exhaust fan point/ call bell pointwith 1.5 sq.mm FRLS PVC insulated copper conductor singlecore cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthingthe point with 1.5 sq.mm FRLS PVC insulated copper conductorsingle core cable etc. as required.Group C |
| 3 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, singlecore cable in surface/ recessed medium class PVC conduit as required. Make-L&T/Finolex/Polycab2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 4 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 5 | 4 X 6sq. mm + 2 X 6 sq. mm earth wire |
| 6 | 4 X 10sq. mm + 2 X 6 sq. mm earth wire |
| 7 | Supplying and fixing suitable size GI/PVC box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required |
| 8 | Supplying and fixing suitable size GI box with modular plateand cover in front on surface or in recess, including providingand fixing 6 pin 5/6 A & 15/16 A modular socket outlet and15/16 A modular switch, connections etc. as required.Make-L&T/LEGRAND/ABB |
| 9 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Make-L&T/ABB/C&S/Legrand/Hagger/Seimens/SchneiderSingle Pole MCB Make-L&T/ABB/C&S/Legrand/Hagger/Seimens/Schneider |
| 10 | 2 /4 Way Enclosure Metal Box |
| 11 | Double poleMCB 32/40 Amp |
| 12 | TPMCB 32/40 A |
| 13 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required.3½ X 95 sq. mm (38 mm) |
| 14 | 3½ X 185 sq. mm (57 mm) |
| 15 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)8 way (4 + 24), Double door |
| 16 | 125Amp.36KA Amp,MCCBS Conforms to IS/IEC-60947-2 Make-L&T/ABB/Indoasian |
| 17 | Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but with charcoal/ coke and salt) as required |
| 18 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 meter below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50 mm) |
| 19 | Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep) and re-filling etc. as required80mm dia |
| 20 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosurewith cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required. |
| 21 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 22 | Supplying , installation testing and commissioning . TPN tap off box made of 1.6mm thick sheet steel encloser duly painted with powder coating on existing rising main complete wit TPN disconnector FSU and HRC fuse , connection , eartihing etc. as require 63Amp. |
| 23 | 100Amp. |
| 24 | 200Amp. |
| 25 | Supply and layingof 3.5CX185 SqmmArmoured AluminiumCable650/1100V grade as per IS 7098(Part 1) 1988 ,PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size, direct in ground including excavation , sand cushioning , protective covering and refilling the trench etc. as required as per site. Make- Gloster,Polycab KEI, |
| 26 | Supplying and fixing of 230VAC 1Ph. 1400mm dia Ceiling Fan (High Speed).(Make: Usha / Crompton / Bajaj ) |
| 27 | Supplying,Cutting of hook , painting and fixing ofMS Down down conduit forinstallation of ceiling fan upto 5 to 8 feet |
| 28 | Supplying and fixing of 230VAC 1Ph.Two module steeped type fan electronic regulator |
| 29 | Providing,Installation,Fixing,Connecting and Testing of LED Flood Light,70-100 W, as per site requirment. (Make: Wipro/ Philipse/ /CG/Panasonic/Wipro/Crompton / Bajaj ) |
| 30 | Providing,installation, fixing,Connecting and Testing of LED Batten,4 Feet,20W, as per site requirment. (Make: Wipro/ Philipse/ Syska/CG/Polycab/Panasonic ) |
| 31 | Supply, Installation ,testing & Commisionioning (SITC) of outdoor CPRI certified cubical Feeder pilar with EC grade Al busbar capacity 400Amp. 100% netural suitable >25ka for 3 sec for fault level ,compatiable for following incomming & outgoing . Custum built self fabricated out of 16SWG , CRCA sheet Foot mounted type Panel Furnished with siemen gray shade powder coated paint after necessary pre treatment fully dust & vermin proof, Copper wire ,Lugs and Netural & Insulating Material Engineering and Labor Charges , Panle size (H-W-D)mm. Details as Incoming-SFU400 Amp. TPN 2Nos. & 6 nos-HRC fuse, Incomer All Busbar capacity 400Amp.Outgoing DeatilsTP MCCB-250 Amp.TPN-2 Nos, TP MCCB-2 Nos 200 Amp. andMCCB 63 Amp.-2 NosCubicle Type Note-MCCB Make Legrand, L& T Simenice etc. |
| 32 | Supply and layingof 3.5CX95 SqmmArmoured AluminiumCable650/1100V grade as per IS 7098(Part 1) 1988 ,PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size, in existing trench/RCC/HUME/METAL Pipe as required from Precsion to near gate. |
| 33 | Supplying and fixing of FP MCB 40/63 A Make-L&T/ABB/C&S/Legrand/Hagger/Seimens/Schneider |